Airflow Meter vs Differential Pressure Meter for Data Centre Cooling Malaysia

A server room may show a normal average temperature while some network racks receive insufficient cooling air.

To investigate the problem correctly, technicians must determine whether they need to measure air velocity or pressure difference.

An airflow meter and a differential pressure meter are both useful for data-centre cooling inspection, but they measure different conditions and should not be treated as interchangeable instruments.

What Is an Airflow Meter?

An airflow meter, also known as an anemometer, measures air velocity.

Depending on the instrument and application, it may be used at:

  • Air-conditioning outlets

  • Ventilation grilles

  • Perforated raised-floor tiles

  • Server-rack air intakes

  • Server-rack exhaust areas

  • Cooling-unit outlets

  • Air ducts

  • Hot and cold aisles

It helps answer:

“How fast is the air moving at this location?”

What Is a Differential Pressure Meter?

A differential pressure meter measures the pressure difference between two locations.

It may be used to compare:

  • Raised floor and server room

  • Cold aisle and surrounding area

  • Server room and corridor

  • Upstream and downstream of a filter

  • Supply and return-air sections

  • Contained aisle and adjacent space

It helps answer:

“What is the pressure difference between these two points?”

Airflow Meter Versus Differential Pressure Meter

Inspection requirement Airflow meter Differential pressure meter
Measure air velocity Yes No
Check airflow from a grille Yes No
Compare pressure between two rooms No Yes
Measure pressure across a filter No Yes
Investigate weak airflow at a rack Yes Supporting measurement
Check raised-floor pressure Limited Yes
Compare cooling outlets Yes Limited
Assess room pressurisation No Yes

For some cooling investigations, both instruments are required.

Why Is Airflow Important in a Data Centre?

Cooling equipment may operate normally while air fails to reach the intended racks.

Poor airflow may cause:

  • High rack-inlet temperature

  • Hotspots at the top of racks

  • Hot-air recirculation

  • Uneven cooling

  • Repeated temperature alarms

  • Server fans operating continuously

  • Higher energy consumption

  • Reduced equipment reliability

Airflow measurement provides evidence that cooling air reaches the required locations.

Why Is Differential Pressure Important?

Pressure differences influence how air moves between spaces.

Incorrect pressure may contribute to:

  • Weak airflow through raised-floor tiles

  • Air moving in the wrong direction

  • Hot and cold air mixing

  • Containment leakage

  • Reduced cooling efficiency

  • Dust entering the server room

  • Unstable room conditions

  • Poor filter performance

The required pressure relationship depends on the facility and cooling-system design.

Where Should Airflow Be Measured?

Cooling-Unit Outlet

Measure airflow at several points across the outlet rather than relying on one centre reading.

Cooling-Unit Intake

The intake measurement can support comparison with the outlet and help identify restrictions.

Perforated Raised-Floor Tiles

Compare tiles serving:

  • High-load racks

  • Low-load racks

  • Problem areas

  • Locations near and far from cooling units

Rack Front

Measure near the equipment air intake at:

  • Bottom

  • Middle

  • Top

Rack Rear

Exhaust-air measurement can support investigation of heat removal and recirculation.

Hot and Cold Aisles

Measurements help determine whether air follows the intended path.

Where Should Differential Pressure Be Measured?

Raised Floor Versus Room

One pressure port is connected below the raised floor and the other measures the server-room side.

Record exactly which port is connected to each location.

Across a Filter

Measure upstream and downstream pressure to assess whether the filter may be restricting airflow.

Interpret the result according to the equipment manufacturer’s guidance.

Server Room Versus Corridor

This measurement helps determine the direction in which air is likely to move when openings or leakage paths are present.

Cold Aisle Versus Surrounding Space

For a contained aisle, pressure measurement may support assessment of containment performance.

How to Measure Airflow Correctly

Step 1: Define the Test Point

Record:

  • Cooling unit

  • Grille or tile

  • Rack number

  • Measurement height

  • Distance from outlet

  • Instrument orientation

Step 2: Confirm the Instrument Setting

Select the correct:

  • Measurement unit

  • Probe type

  • Range

  • Averaging mode

  • Area setting where volume calculation is required

Step 3: Hold the Sensor Correctly

The sensor should face the airflow according to the instrument instructions.

Incorrect angle can affect the reading.

Step 4: Allow the Reading to Stabilise

Airflow often fluctuates. Avoid recording the first number displayed.

Step 5: Take Multiple Readings

Measure at several points across a large outlet or grille.

Calculate or record an average where appropriate.

Step 6: Compare With Previous Measurements

Use consistent locations and operating conditions.

A trend is often more useful than one isolated reading.

How to Measure Differential Pressure Correctly

Step 1: Identify Both Test Locations

Clearly define the high-pressure and low-pressure sides.

Step 2: Check the Tubing

Ensure the tubing is:

  • Correctly connected

  • Not bent

  • Not blocked

  • Not leaking

  • Suitable for the measurement

Step 3: Zero the Instrument

Zero the meter according to the manufacturer’s procedure before connecting or measuring.

Step 4: Connect the Pressure Ports

Connect the positive and negative ports correctly.

A reversed connection may produce a negative result or opposite interpretation.

Step 5: Allow the Reading to Stabilise

Avoid recording while doors are opening, fans are changing speed or personnel are moving around the test point unless those events are part of the investigation.

Step 6: Record the Exact Conditions

Document:

  • Both test locations

  • Door position

  • Cooling-unit status

  • Fan status

  • Filter condition

  • Room operating condition

  • Measurement unit

  • Date and time

How to Investigate Weak Rack Cooling

Use this sequence:

  1. Measure room temperature and humidity.

  2. Check the rack inlet at different heights.

  3. Measure airflow at the rack front.

  4. Compare with nearby racks.

  5. Check the raised-floor tile or cooling outlet.

  6. Measure raised-floor pressure where applicable.

  7. Inspect for cable or equipment obstruction.

  8. Check blanking panels and containment.

  9. Scan the rack with a thermal camera.

  10. Correct the confirmed problem.

  11. Repeat all relevant measurements.

How to Check a Suspected Dirty Filter

Possible signs include:

  • Reduced outlet airflow

  • Increased fan noise

  • Cooling unit operating for longer periods

  • Repeated temperature alarms

  • Higher pressure difference across the filter

  • Visible dirt accumulation

Use:

  • Differential pressure meter

  • Airflow meter

  • Temperature meter

  • Visual inspection

Follow the cooling-unit manufacturer’s filter replacement limits.

Using a Thermal Camera With Airflow Measurements

The Noyafa NF-522 Thermal Camera can help locate:

  • Warm areas at rack fronts

  • Hot-air recirculation

  • Uneven cooling patterns

  • Hot equipment

  • Cooling-motor hotspots

  • Electrical problems

However, a thermal image does not directly measure air velocity.

Use an airflow meter to confirm whether insufficient air reaches the hotspot.

Using a Data Logger With Airflow Measurements

A data logger can reveal when rack temperature rises.

After identifying the time pattern:

  • Measure airflow during the affected period

  • Compare cooling-unit operation

  • Check pressure conditions

  • Inspect the rack thermally

  • Review server load

The Elitech RC-5 can support temperature recording, while a suitable temperature-and-humidity logger such as the Elitech GSP-6 Pro may be used when both parameters are required.

Common Airflow Measurement Mistakes

Avoid:

  • Measuring at only one point on a large grille

  • Holding the sensor at the wrong angle

  • Comparing readings taken at different distances

  • Measuring under different fan conditions

  • Blocking airflow with the technician’s body

  • Recording an unstable reading

  • Ignoring airflow direction

  • Failing to document the exact position

  • Comparing different units

  • Assuming high air velocity always means good rack cooling

Common Differential Pressure Measurement Mistakes

Avoid:

  • Reversing positive and negative ports

  • Failing to zero the meter

  • Using leaking or blocked tubing

  • Recording no information about test locations

  • Measuring while doors repeatedly open

  • Ignoring fan operating condition

  • Comparing readings in different units

  • Assuming one pressure target applies to every data centre

  • Failing to check manufacturer requirements

  • Not repeating measurements after maintenance

Which Instrument Should You Buy?

Choose an airflow meter when the primary task is:

  • Checking air velocity

  • Comparing cooling outlets

  • Testing rack airflow

  • Measuring grille or tile output

  • Investigating weak cooling

Choose a differential pressure meter when the primary task is:

  • Comparing pressure between two spaces

  • Checking raised-floor pressure

  • Measuring pressure across filters

  • Assessing room pressurisation

  • Investigating containment pressure

Choose both when performing a complete cooling-system assessment.

Recommended Data Centre Cooling Tool Kit

A practical kit may include:

  • Airflow meter

  • Differential pressure meter

  • Temperature and humidity meter

  • Temperature data logger

  • Temperature and humidity data logger

  • Thermal imaging camera

  • Sound level meter

  • Vibration meter

  • Clamp meter

Measure the Correct Cooling Parameter

An airflow meter and differential pressure meter provide different evidence.

The airflow meter shows how fast air moves at a particular location. The differential pressure meter shows the pressure relationship between two points.

Using the correct instrument—and documenting the exact test conditions—helps data-centre maintenance teams identify whether a cooling problem is caused by weak airflow, pressure imbalance, blocked filters or poor air distribution.

Contact MTM Precision

MTM Precision Sdn. Bhd.

Showroom & Service Centre

No. 29-1 & 29-2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia

🌐 Website: www.mtmpre.com.my
📧 Email: mtmpre@yahoo.com
📱 WhatsApp: +6016-660 7346

02 Sep 2026