Why Data Centre PUE Can Worsen During Low IT Load Malaysia

Why Data Centre PUE Can Worsen During Low IT Load Malaysia

 

Content

 

Power Usage Effectiveness, commonly known as PUE, is widely used to evaluate data-centre energy efficiency.

 

A lower PUE generally indicates that a larger proportion of total facility power is reaching IT equipment instead of being consumed by cooling, electrical losses, lighting and other supporting infrastructure.

 

However, PUE can worsen when IT load is low—even when the data centre has efficient cooling and electrical equipment.

 

This is particularly important during commissioning, phased expansion and early operation of new data-centre capacity in Malaysia.

 

What Is PUE?

 

PUE is calculated as:

 

PUE = Total Data Centre Energy ÷ IT Equipment Energy

 

Total facility energy includes:

 

Servers and IT equipment

 

Cooling equipment

 

Pumps and fans

 

UPS and electrical losses

 

Lighting

 

Controls

 

Other supporting infrastructure

 

A theoretical PUE of 1.0 would mean that all incoming energy is used by IT equipment with no supporting-energy consumption.

 

Real facilities require cooling, power distribution and other systems, so their PUE is higher than 1.0.

 

Simple PUE Example

 

Assume a data centre uses:

 

Total facility power: 1,500 kW

 

IT equipment power: 1,000 kW

 

The PUE is:

 

1,500 ÷ 1,000 = 1.50

 

Now assume the IT load falls to 500 kW, but cooling and supporting systems continue consuming 500 kW.

 

The total power becomes 1,000 kW:

 

1,000 ÷ 500 = 2.00

 

The facility may not have developed a technical fault. The supporting load simply represents a larger proportion of the reduced IT load.

 

Why Supporting Equipment Does Not Fall Proportionally

 

Some data-centre systems have a minimum operating demand.

 

These may include:

 

Chillers

 

Cooling towers

 

Computer-room air conditioners

 

Computer-room air handlers

 

Pumps

 

Fans

 

UPS systems

 

Transformers

 

Controls

 

Lighting

 

Security and fire systems

 

When IT load decreases by 50%, these supporting systems may not reduce their consumption by the same percentage.

 

This creates poor part-load efficiency and increases PUE.

 

1. Cooling Equipment May Be Oversized for the Current Load

 

A data centre may be designed for future capacity but initially operate with only a small amount of installed IT equipment.

 

The cooling system may still require:

 

Minimum water flow

 

Minimum fan speed

 

Standby equipment

 

Pump circulation

 

Humidity control

 

Pressurisation

 

Control-system operation

 

As a result, cooling energy may remain relatively high while the IT denominator remains low.

 

2. Commissioning Loads Do Not Represent Full Operation

 

During commissioning, sections of the cooling and electrical infrastructure may operate before the associated server capacity is installed.

 

Examples include:

 

Cooling a partially occupied data hall

 

Operating pumps for testing

 

Running redundant equipment

 

Energising UPS systems at low load

 

Maintaining temperature and humidity in empty white space

 

Testing alarms and backup systems

 

PUE calculated during this phase should not be compared directly with a mature, fully occupied facility without explaining the operating condition.

 

3. UPS Efficiency May Decline at Low Load

 

UPS efficiency varies with load.

 

A UPS system designed for a high-capacity data hall may operate less efficiently when only lightly loaded.

 

Losses may include:

 

Conversion losses

 

Transformer losses

 

Battery-charging demand

 

Control-system consumption

 

Redundant UPS modules operating unnecessarily

 

Modular UPS architecture and load management may improve part-load performance, depending on the design and redundancy requirements.

 

4. Pumps and Fans May Run at Fixed Speed

 

A fixed-speed pump or fan may consume unnecessary energy when cooling demand is low.

 

Variable-speed control can reduce consumption, but only when:

 

Sensors are accurate

 

Control logic is correct

 

Minimum flow is respected

 

Valves and dampers operate properly

 

The system is commissioned correctly

 

A variable-speed drive does not guarantee efficient operation if the control setpoint is unsuitable.

 

5. Redundancy Carries an Energy Cost

 

Data centres require high availability.

 

Redundant systems may include:

 

N+1 chillers

 

Redundant pumps

 

Multiple UPS modules

 

Standby generators

 

Duplicate cooling paths

 

Additional fans

 

Some standby equipment consumes little energy, while other equipment may be operated continuously to maintain readiness or share load.

 

PUE improvement must not compromise the redundancy and reliability required by the facility.

 

6. Humidity Control May Continue at Low IT Load

 

When server heat output is low, temperature and humidity control may become more difficult rather than easier.

 

The system may use energy for:

 

Dehumidification

 

Reheating

 

Humidification

 

Preventing condensation

 

Maintaining room setpoints

 

This is especially relevant in Malaysia’s warm and humid climate.

 

Humidity problems can increase when outdoor air enters the building or when control sequences are not coordinated.

 

7. Airflow May Not Match Actual Rack Occupancy

 

Partially populated data halls may experience:

 

Empty rack positions

 

Missing blanking panels

 

Unsealed cable openings

 

Unbalanced supply airflow

 

Air recirculation

 

Bypass air

 

Excessive fan speed

 

Cooling equipment may move large quantities of air without effectively cooling active IT equipment.

 

Simple airflow-management improvements can sometimes reduce supporting energy without changing the main cooling equipment.

 

8. Poor Sensor Placement Can Increase Cooling Demand

 

Cooling controls depend on measurements such as:

 

Rack inlet temperature

 

Return-air temperature

 

Relative humidity

 

Differential pressure

 

Chilled-water temperature

 

Flow

 

Equipment status

 

A sensor placed in an unrepresentative location may cause overcooling.

 

Examples include:

 

Temperature sensor in a local hot spot

 

Humidity sensor near an outdoor-air leak

 

Differential-pressure sensor with incorrect tubing

 

Return-air sensor affected by bypass airflow

 

Uncalibrated or drifting sensor

 

Instrumentation should be checked before adjusting major control settings.

 

9. Metering Boundaries May Be Incorrect

 

PUE is only meaningful when the total facility and IT energy boundaries are clearly defined.

 

Possible errors include:

 

Missing cooling equipment

 

Including unrelated building loads

 

Incorrect current-transformer ratio

 

Double-counting meters

 

Estimating IT load instead of measuring it

 

Different time intervals

 

Meter drift

 

Communication errors

 

Incorrect aggregation

 

A worsening PUE may sometimes be caused by improved data reconciliation that reveals loads previously excluded.

 

10. Leakage Can Increase Water and Energy Use

 

Cooling-system leakage may increase:

 

Pump operation

 

Water consumption

 

Treatment-chemical usage

 

Makeup-water demand

 

Cooling instability

 

Small leaks and meter inconsistencies can remain unnoticed without regular trend review.

 

PUE should be assessed together with:

 

Water Usage Effectiveness

 

Makeup-water volume

 

Cooling load

 

IT load

 

Temperature

 

Flow and pressure

 

Equipment runtime

 

PUE Should Not Be Read Alone

 

A lower PUE does not automatically mean that every operating condition is better.

 

Facilities should also consider:

 

Reliability

 

Water use

 

Carbon intensity

 

Cooling resilience

 

IT utilisation

 

Rack density

 

Climate

 

Maintenance condition

 

Redundancy

 

Service availability

 

For example, reducing fan speed may improve energy use but create unacceptable rack-inlet temperatures if airflow is already poorly distributed.

 

How to Investigate High PUE at Low Load

 

Step 1: Confirm the Calculation

 

Check:

 

Total facility meter

 

IT power meter

 

Measurement interval

 

Meter calibration

 

Included and excluded loads

 

Data completeness

 

Step 2: Record IT Occupancy

 

Document:

 

Installed rack capacity

 

Active IT load

 

Average rack density

 

Data-hall occupancy

 

Planned future load

 

This helps distinguish a lightly occupied facility from a genuine efficiency decline.

 

Step 3: Separate Major Supporting Loads

 

Measure or estimate:

 

Chillers

 

Cooling towers

 

Pumps

 

CRAH or CRAC units

 

UPS losses

 

Lighting

 

Other facility loads

 

Identify which load is not reducing with IT demand.

 

Step 4: Review Part-Load Operation

 

Check whether:

 

Too many chillers are operating

 

Redundant pumps are sharing a very low load

 

Fans remain at fixed speed

 

UPS modules are lightly loaded

 

Empty halls are fully conditioned

 

Minimum-flow bypass is excessive

 

Step 5: Inspect Airflow

 

Check:

 

Hot- and cold-aisle separation

 

Blanking panels

 

Cable openings

 

Rack inlet temperature

 

Return-air path

 

Differential pressure

 

Fan speed

 

Empty rack spaces

 

Step 6: Verify Sensors

 

Compare installed sensors with portable instruments.

 

Check:

 

Temperature

 

Relative humidity

 

Differential pressure

 

Air velocity

 

Water temperature

 

Electrical current

 

A control change should not be based on an unverified sensor.

 

Useful Data Centre Measurements

 

Thermal Imaging

 

A thermal camera can help identify:

 

Hot electrical connections

 

Uneven rack temperatures

 

Cooling-distribution problems

 

Overheated cables

 

Abnormal UPS or panel conditions

 

Pump and motor heating

 

Thermal imaging shows surface-temperature patterns and should be combined with direct environmental and electrical measurements.

 

Temperature and Humidity Logging

 

A data logger can reveal:

 

Daily variation

 

Short-duration excursions

 

Differences between rack locations

 

Overcooling

 

Humidity instability

 

Changes after control adjustment

 

Differential Pressure

 

Differential-pressure measurement helps assess:

 

Raised-floor pressure

 

Hot- and cold-aisle containment

 

Filter restriction

 

Room pressurisation

 

Airflow imbalance

 

Air Velocity

 

Anemometers can support checks of:

 

Floor-tile airflow

 

Cooling-unit discharge

 

Return-air paths

 

Local airflow problems

 

Air velocity alone does not provide total airflow unless the outlet area and measurement method are considered.

 

Electrical Measurement

 

Clamp meters and electrical instruments help verify:

 

Current

 

Voltage

 

Load balance

 

UPS loading

 

Pump and fan demand

 

Circuit utilisation

 

Energy-efficiency analysis should use suitable power or energy measurement where required, rather than current alone.

 

When High PUE Is Expected

 

A temporarily high PUE may be understandable during:

 

Initial commissioning

 

Low occupancy

 

Phased server installation

 

Maintenance

 

System testing

 

Redundancy testing

 

Temporary cooling configuration

 

Equipment startup

 

The facility should document the reason and expected improvement as IT load increases or control optimisation is completed.

 

When High PUE Requires Investigation

 

Investigate when:

 

PUE continues rising at a stable IT load

 

Cooling power increases without a clear reason

 

Rack temperatures remain low while cooling demand rises

 

Water usage increases

 

Pumps or fans operate continuously at high speed

 

Sensors disagree

 

Humidity control becomes unstable

 

Leakage or meter anomalies are suspected

 

Efficiency does not improve after occupancy increases

 

Data Centre Testing Instruments from MTM Precision

 

MTM Precision supplies instruments for data-centre commissioning, inspection and preventive maintenance in Malaysia.

 

Relevant products include:

 

NOYAFA NF-522 thermal imaging camera

 

Temperature and humidity meters

 

Temperature and humidity data loggers

 

Differential-pressure meters

 

Airflow and anemometer instruments

 

Clamp meters and electrical testers

 

Water-quality meters for cooling systems

 

Leak-detection equipment

 

Vibration meters for pumps and cooling machinery

 

NOYAFA NF-8209 Pro and NF-8506 network cable testers

 

NOYAFA NF-IPC728HSO CCTV and network tester

 

These instruments can support investigation of thermal, airflow, electrical and cooling-system conditions. Formal PUE assessment also requires correctly installed energy metering and a clearly defined measurement boundary.

 

Contact MTM Precision

 

MTM Precision Sdn. Bhd. (744811-A)

 

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com / enquiry@mtmpre.com.my

Website: www.mtmpre.com.my

 

Visit our Puchong Showroom & Service Centre for data-centre testing instrument selection, product demonstration and technical support.

 

Operating hours: Monday to Friday, 9:00 AM–6:00 PM.


 

20 Sep 2026