How to Compare Lighting Before and After LED Upgrade with UNI-T UT383S Malaysia
The **UNI-T UT383S Digital Light Meter** can be used to record illumination before and after an LED upgrade at the same measurement points. This gives contractors and facility teams clearer evidence of how the lighting has changed.
## Why Measure Before Replacing the Lights?
Without baseline measurements, it is difficult to determine whether the new installation has improved the actual working areas.
Before-upgrade readings can help document:
- Existing dark areas
- Uneven fixture spacing
- Failed or deteriorating lamps
- Lighting at desks and workbenches
- Illumination between fixtures
- Areas affected by shelves or machinery
- Daylight contribution
- Current operating conditions
These readings provide a reference for the post-installation inspection.
## Why Use the UNI-T UT383S?
The UT383S measures from **0 to 199,900 Lux** and uses a separate light sensor.
The split-sensor design allows the user to:
- Place the sensor directly on a desk or workbench
- Keep the display visible
- Move away to reduce shadows
- Repeat readings at marked positions
- Measure under shelves or fixed equipment
- Compare multiple working heights
The meter also provides automatic range selection, MAX/MIN readings, Data Hold and Lux/Fc selection.
## Step 1: Define the Lighting Objectives
Before collecting readings, determine what the LED upgrade is intended to achieve.
Possible objectives include:
- Improve visibility at workstations
- Reduce dark areas
- Replace ageing fluorescent lamps
- Improve aisle lighting
- Support detailed inspection work
- Reduce maintenance frequency
- Change fixture layout
- Improve lighting consistency
- Reduce unnecessary over-lighting
Lux readings can support these objectives, but they do not directly measure energy consumption, glare or colour quality.
## Step 2: Create a Measurement Grid
Divide the room or work area into repeatable measurement points.
For an office:
- Each desk
- Room centre
- Window side
- Wall side
- Meeting table
- Reception counter
For a factory:
- Workbenches
- Assembly stations
- Inspection tables
- Machine operating points
- Aisle intersections
- Packing areas
For a warehouse:
- Aisle entrances
- Aisle centres
- Picking heights
- Packing stations
- Loading areas
Label every point so that it can be measured again after installation.
## Step 3: Keep the Sensor Height Consistent
The sensor must be placed at the actual working height.
Examples include:
- Desk surface
- Inspection table
- Factory workbench
- Warehouse floor
- Product-picking level
- Vertical display or whiteboard
Do not take the before reading at desk level and the after reading while holding the sensor in the air.
## Step 4: Record the Existing Conditions
For every before-upgrade measurement, record:
- Lux value
- Measurement point
- Sensor height
- Date and time
- Daylight condition
- Curtains or blinds position
- Lights operating
- Failed lamps
- Furniture or machinery position
- Room operating condition
Photographs of the sensor position can make the after-upgrade test easier to reproduce.
## Step 5: Measure After the LED Installation
Allow the new lights to operate normally before collecting the after-upgrade readings.
Repeat the test using:
- The same UT383S meter
- The same measurement points
- The same sensor height
- The same sensor orientation
- Similar daylight conditions
- The same furniture or machinery arrangement
- The same number of operating fixtures
Avoid changing several conditions at once without documenting them.
## Step 6: Compare Distribution, Not Only the Average
An improved average Lux value can hide dark or excessively bright locations.
Compare:
- Lowest reading
- Highest reading
- Difference between points
- Dark areas between fixtures
- Light levels at actual workstations
- Window-side and wall-side results
- Centre and corner measurements
- Task areas with local lighting
The objective should be suitable and reasonably consistent illumination for the actual work—not simply the highest possible reading.
## Example Before-and-After Record
| Point | Location | Before Upgrade | After Upgrade | Observation |
|---|---|---:|---:|---|
| A1 | Front desk | Record Lux | Record Lux | Check distribution |
| A2 | Centre desk | Record Lux | Record Lux | Compare same position |
| A3 | Rear desk | Record Lux | Record Lux | Check dark area |
| B1 | Inspection bench | Record Lux | Record Lux | Verify task lighting |
| B2 | Walkway | Record Lux | Record Lux | Check floor-level lighting |
State the measurement unit clearly in the actual report.
## Check for New Lighting Problems
An LED upgrade may increase measured illumination but introduce other issues.
Inspect for:
- Glare
- Reflections on screens
- Bright hotspots
- Dark gaps between fixtures
- Visible flicker
- Shadows from equipment
- Unsuitable colour appearance
- Different light levels between identical workstations
The UT383S measures illumination. Additional instruments or visual assessment may be required for other lighting characteristics.
## Do Not Compare Different Units
Confirm whether the UT383S is displaying **Lux or Foot-Candle**.
If the before measurements are recorded in Lux and the after measurements in Fc, the numerical results cannot be compared directly without conversion.
Use one unit consistently throughout the project.
## Common Before-and-After Measurement Mistakes
Avoid:
- Measuring only after the upgrade
- Changing the measurement points
- Using different sensor heights
- Comparing day and night conditions
- Measuring with different numbers of lights operating
- Standing over the sensor
- Recording values without units
- Comparing two different meters without considering their condition
- Measuring an empty area before and a fully occupied area after
- Reporting only the highest Lux reading
A controlled comparison produces more useful information.
## Does the Meter Need Calibration?
For internal comparison and general maintenance, the same meter used consistently before and after may provide useful trend information.
For contractual acceptance, compliance reporting or quality-system documentation, confirm:
- Calibration requirements
- Instrument traceability
- Required measurement method
- Acceptance criteria
- Measurement uncertainty
- Reporting format
These requirements should be agreed upon before the LED project begins.
## Suitable Users
The UNI-T UT383S is suitable for:
- Electrical contractors
- Lighting installers
- Facility-management teams
- Factory maintenance departments
- Schools and commercial buildings
- Warehouse operators
- Interior renovation contractors
- Energy-improvement projects
- Property-management companies
For UNI-T UT383S enquiries and assistance selecting a Lux meter for LED upgrades, workplace lighting or building inspections in Malaysia, contact MTM Precision.
**MTM Precision Sdn Bhd**
**Showroom & Service Centre:** No. 29-1 & 29-2, Jalan Bandar 18, Pusat Bandar Puchong, 47160 Puchong, Selangor, Malaysia
**Tel:** 03-8080 7172
**WhatsApp:** +6016-660 7346
**Email:** mtmpre@yahoo.com
**Website:** www.mtmpre.com.my
25 Sep 2026