How to Measure Airflow CFM with TASI TA642C Digital Anemometer Malaysia

How to Measure Airflow CFM with TASI TA642C Digital Anemometer Malaysia

 

When checking an HVAC or ventilation system, measuring air velocity alone does not always tell the complete story.

 

Technicians may also need to determine airflow volume, commonly expressed as CFM – Cubic Feet per Minute.

 

The TASI TA642C High Accuracy Digital Anemometer can be used for air velocity and airflow measurement, making it useful for HVAC servicing, ventilation inspection, duct testing and building maintenance in Malaysia.

 

What Is CFM?

 

CFM means Cubic Feet per Minute.

 

It describes the volume of air passing through an opening or duct every minute.

 

In simple terms:

 

Air Velocity × Area = Airflow

 

This is why the dimensions of the duct, grille or measurement area matter when calculating airflow.

 

A high air velocity through a small opening does not necessarily mean the system is moving more total air than a lower velocity through a much larger opening.

 

Why Is CFM Important in HVAC?

 

An HVAC system must move an appropriate amount of air to distribute cooling, heating or ventilation effectively.

 

CFM measurements can help technicians investigate problems such as:

 

Weak air-conditioning performance

 

Insufficient supply airflow

 

Poor room ventilation

 

Uneven cooling

 

Exhaust system problems

 

AHU or FCU airflow issues

 

Incorrect damper settings

 

Restricted filters or ducts

 

Rather than describing airflow as simply “strong” or “weak”, CFM provides a measurable value.

 

Step 1: Identify the Measurement Area

 

First, determine where the airflow measurement will be taken.

 

Typical locations include:

 

Supply air grille

 

Return air grille

 

HVAC duct

 

Fresh air intake

 

Exhaust outlet

 

Ventilation opening

 

The dimensions of the measurement area are important because airflow calculation depends on both air velocity and area.

 

Step 2: Measure the Opening or Duct

 

Measure the dimensions of the duct or opening carefully.

 

For a rectangular opening, this generally involves determining its width and height.

 

For a circular duct, the diameter is required.

 

Incorrect dimensions can produce an incorrect airflow calculation even when the air velocity reading itself is accurate.

 

Step 3: Measure Air Velocity

 

Position the TASI TA642C probe correctly in the airflow.

 

Allow the reading to stabilise.

 

Because air velocity may vary across an outlet or duct, avoid assuming that one measurement point represents the entire cross-section.

 

For better assessment, take readings at several locations.

 

Step 4: Use Multiple Measurement Points

 

Air near the centre of a duct may move at a different velocity from air near the edges.

 

Airflow can also be affected by bends, dampers, filters, grilles and other components.

 

Taking several readings across the measurement area can provide a more representative result.

 

This becomes particularly important when troubleshooting HVAC systems or comparing airflow before and after maintenance.

 

Step 5: Determine the Airflow

 

Once the measurement area and representative air velocity are known, airflow can be determined.

 

The TA642C supports airflow measurement functions including:

 

CFM – Cubic Feet per Minute

 

CMM – Cubic Metres per Minute

 

CMS – Cubic Metres per Second

 

The appropriate unit depends on the project, specification and reporting requirements.

 

Practical Example

 

Consider an office where one room is consistently warmer than surrounding rooms.

 

The air-conditioning system is operating, and cool air can be felt from the diffuser.

 

However, this does not confirm that sufficient air volume is reaching the room.

 

A technician can measure airflow at several supply outlets.

 

If surrounding outlets provide substantially higher airflow while the problematic room shows a lower value, further investigation can focus on that branch of the HVAC system.

 

Possible issues may include:

 

Partially closed damper

 

Duct obstruction

 

Dirty filter

 

Air leakage

 

Flexible duct problem

 

Fan performance issue

 

Incorrect balancing

 

Measurement helps narrow down the investigation.

 

CFM Measurement Before and After Maintenance

 

One useful application is comparing readings before and after HVAC servicing.

 

For example:

 

Before filter replacement: Record airflow.

 

After filter replacement: Measure the same location again under comparable operating conditions.

 

If airflow improves significantly, the measurement provides useful evidence of the change in system performance.

 

The same approach can be used after duct cleaning, damper adjustment or other maintenance work.

 

TASI TA642C for AHU and FCU Checking

 

The TA642C can also support airflow investigation around Air Handling Units (AHU) and Fan Coil Units (FCU).

 

Technicians may use measurements to compare:

 

Different supply branches

 

Different rooms

 

Supply and return locations

 

Before and after maintenance

 

Current and historical readings

 

Trend and comparison data can be more useful than an isolated measurement.

 

Common CFM Measurement Mistakes

 

Several mistakes can affect airflow measurement results.

 

Measuring at Only One Point

 

Air velocity is rarely uniform across an entire duct or grille.

 

Incorrect Area Setting

 

If the measurement area is wrong, the calculated airflow will also be wrong.

 

Poor Probe Position

 

Incorrect probe orientation can affect air velocity measurements.

 

Measuring Near Severe Turbulence

 

Bends, dampers and obstructions can create unstable airflow.

 

Comparing Different Operating Conditions

 

Comparisons should be made under similar HVAC operating conditions whenever possible.

 

Who Can Use the TASI TA642C?

 

The TA642C can be useful for:

 

HVAC contractors

 

Air-conditioning technicians

 

M&E contractors

 

Facility management teams

 

Building maintenance departments

 

Factory maintenance teams

 

Ventilation contractors

 

Indoor environmental inspection

 

Preventive maintenance teams

 

Typical applications include offices, factories, shopping centres, hotels, warehouses, hospitals, laboratories, commercial buildings and data centres.

 

TASI TA642C Digital Anemometer Malaysia

 

For users who need more than basic wind-speed measurement, the TASI TA642C High Accuracy Digital Anemometer provides air velocity, temperature and airflow measurement functions for HVAC and ventilation applications.

 

Its airflow functions make it particularly useful when technicians need to move from a subjective description such as “low airflow” to actual measurement data.

 

For product availability and technical enquiries, contact:

 

MTM Precision Sdn Bhd

Showroom & Service Centre: Puchong, Selangor, Malaysia

 

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com

Website: www.mtmpre.com.my

 

Contact MTM Precision for the TASI TA642C Digital Anemometer for CFM, HVAC airflow and ventilation measurement in Malaysia.


 

26 Sep 2026