UNI-T UT366A for Exhaust and Dust Collection Pressure Testing Malaysia
An industrial exhaust or dust-collection system may continue running even when its extraction performance has deteriorated. A blocked filter, closed damper, leaking duct or fan problem can change the pressure throughout the system.
The UNI-T UT366A Digital Manometer can measure gauge pressure and differential pressure at suitable test points, helping factory-maintenance teams investigate changes in filters, fans and exhaust ducts.
Why Pressure Testing Matters
Dust collectors and exhaust systems depend on pressure differences to move contaminated air from the collection point through the duct and filtration equipment.
Pressure measurement can support investigations involving:
-
Weak extraction at the hood
-
Dust escaping into the work area
-
Rapid filter blockage
-
Fan-performance changes
-
Closed or incorrectly adjusted dampers
-
Blocked duct sections
-
Air leakage
-
Uneven extraction between branches
-
Unexpected energy consumption
-
Changes after maintenance work
Pressure readings should be compared with the equipment specification or an established operating baseline.
Checking Filter Differential Pressure
As dust accumulates on a filter, resistance to airflow normally increases. Measuring pressure before and after the filter helps maintenance teams track this change.
A typical measurement procedure is:
-
Identify the approved upstream pressure point.
-
Identify the downstream pressure point.
-
Connect one pressure hose to each point.
-
Set the UT366A to differential-pressure mode.
-
Confirm the required pressure unit.
-
Operate the system under normal conditions.
-
Allow the reading to stabilise.
-
Record the pressure difference.
-
Compare the result with the manufacturer’s recommended limit.
Do not replace or clean filters based only on a general pressure value. Different filter designs have different operating limits.
What Does High Differential Pressure Mean?
A higher-than-normal pressure drop across the filter may indicate:
-
Filter loading
-
Blocked filter media
-
Moisture inside the filter
-
Incorrect filter type
-
Failed cleaning cycle
-
Compressed-air cleaning problem
-
Hopper or dust-discharge problem
-
Excessive airflow
-
Blocked pressure line
-
Incorrect P1 and P2 connection
Inspect both the filtration system and the measurement setup before deciding on corrective action.
What Does Low Differential Pressure Mean?
A very low filter-pressure drop does not always mean the filter is clean.
Possible causes include:
-
Torn filter media
-
Missing filter element
-
Air bypass around the filter
-
Reduced fan speed
-
Open bypass damper
-
Duct leakage
-
Low process airflow
-
Blocked pressure-test point
-
Leaking measurement hose
-
Incorrect pressure connection
A physical filter inspection may be necessary.
Checking Fan Inlet and Outlet Pressure
The UT366A can also compare pressure at the fan inlet and outlet.
This may help identify changes caused by:
-
Dirty filters
-
Obstructed ducts
-
Fan-speed reduction
-
Incorrect fan rotation
-
Damaged impeller
-
Loose belt
-
Closed damper
-
Air leakage
-
System modification
A pressure reading alone cannot confirm the fan condition. Also inspect airflow, motor current, speed, noise and vibration.
Checking Exhaust Hood Suction
Weak suction at an extraction hood may allow dust, fumes or process emissions to escape into the surrounding area.
Pressure checks can help determine whether the problem is located near:
-
The extraction hood
-
A branch duct
-
A damper
-
The main duct
-
The filter
-
The fan
-
The discharge section
Use approved static-pressure test points. Do not place pressure hoses where they can be drawn into moving machinery.
Air-velocity measurement at the hood may also be required to assess capture performance.
Using the Optional Pitot Tube
With the optional UNI-T Pitot tube, the UT366A can measure air velocity inside a suitable duct.
The compatible Pitot tube is:
-
350 mm long
-
8 mm in diameter
-
Made from 304 stainless steel
-
Connected using separate black and white silicone hoses
Take measurements at several positions across the duct because air velocity is not normally uniform.
Average velocity can be combined with the internal duct area to estimate air volume.
Dust Can Block the Pressure Line
Fine particles may enter an unprotected pressure hose or test point.
A blocked pressure line can cause:
-
Slow response
-
No pressure response
-
A reading that remains after disconnection
-
Unstable measurement
-
Lower-than-expected pressure
-
Different results between test points
Inspect and clean the system’s pressure-test fittings according to the equipment procedure. Prevent dust from entering the UT366A pressure ports.
Protect the Instrument
The UT366A should measure pressure through a suitable clean and dry connection.
Do not allow:
-
Dust
-
Liquid
-
Condensation
-
Oil
-
Hot gas
-
Corrosive gas
-
Process chemicals
to enter the pressure ports.
Depending on the application, a suitable filter, trap, isolation arrangement or other protective accessory may be required.
Common Reasons for Unstable Readings
Pressure readings may fluctuate because of:
-
Pulse-jet filter cleaning
-
Variable fan speed
-
Damper movement
-
Changing process load
-
Air leakage
-
Turbulence
-
Loose hoses
-
Blocked pressure points
-
Dust inside the hose
-
Incorrect test-point location
The MAX, MIN and AVG functions can help document pressure variation, but large fluctuations should still be investigated.
Establish a System Baseline
Record pressure values when the exhaust system is known to be operating normally.
A useful baseline can include:
-
Equipment identification
-
Fan speed
-
Damper position
-
Filter differential pressure
-
Fan inlet pressure
-
Fan outlet pressure
-
Hood or branch pressure
-
Duct air velocity
-
Motor current
-
Filter condition
-
Process operating condition
Repeat future measurements at the same locations and under similar load conditions.
UT366A Pressure Range and Functions
The UT366A provides:
-
Pressure range of ±15.00 kPa
-
Specified accuracy of ±0.5% full scale at 25°C
-
Independent P1 and P2 measurement
-
Differential-pressure mode
-
Positive and negative pressure LED indicators
-
MAX, MIN, AVG and HOLD
-
Backlit display
-
Unit memory
-
Magnetic hook
Selectable units include kPa, mbar, psi, mmHβO, inHβO and hPa.
Suitable Industrial Applications
The UT366A can support pressure checks in:
-
Dust-collection systems
-
Welding-fume extraction
-
Woodworking exhaust systems
-
Powder-handling areas
-
Factory ventilation
-
Process exhaust
-
Laboratory extraction
-
Bag-filter systems
-
Cartridge-filter systems
-
General HVAC exhaust systems
It is suitable for factories and maintenance contractors across Selangor, Kuala Lumpur, Johor, Penang and Malaysia.
Enquire About Exhaust Pressure Measurement
For assistance selecting the UNI-T UT366A for filter-pressure drop, fan-pressure or exhaust-duct testing, WhatsApp MTM Precision with the expected pressure range and photos of the available test points.