How to Simulate 4-20mA Signals for Pressure Transmitter Testing Using FNIRSI SG-004A Malaysia

How to Simulate 4-20mA Signals for Pressure Transmitter Testing Using FNIRSI SG-004A Malaysia

Pressure transmitters are widely used in factories, water treatment plants, industrial machinery and process control systems to monitor pressure and transmit measurement signals to PLC and DCS controllers.

When a pressure reading becomes incorrect, technicians need to determine whether the problem comes from the pressure transmitter, signal wiring, PLC analog input or control system configuration.

The FNIRSI SG-004A Multifunction Signal Generator can simulate 4-20mA current signals to help technicians troubleshoot pressure measurement systems.

How Does a 4-20mA Pressure Transmitter Work?

A pressure transmitter converts measured pressure into an electrical signal.

For example, a pressure transmitter with a measurement range of 0-10 bar may produce the following outputs.

Pressure Current Output
0 bar 4mA
2.5 bar 8mA
5 bar 12mA
7.5 bar 16mA
10 bar 20mA

The PLC converts the received current into a pressure reading using its configured scaling parameters.

If the signal or scaling is incorrect, the displayed pressure may not match the actual process pressure.

Why Simulate a 4-20mA Pressure Signal?

4-20mA signal simulation allows technicians to test the control system without depending on the actual pressure transmitter output.

This is useful when:

  • The PLC displays incorrect pressure readings.

  • The pressure transmitter is suspected to be faulty.

  • A new control panel is being commissioned.

  • The analog input module needs functional testing.

  • The transmitter is temporarily disconnected for maintenance.

  • The PLC scaling needs verification.

By injecting a known current signal, technicians can check whether the control system responds correctly.

How to Simulate a Pressure Transmitter Using FNIRSI SG-004A

Step 1: Identify the Pressure Transmitter Range

Check the transmitter nameplate or datasheet.

For example:

Pressure Range: 0-10 bar

Output Signal: 4-20mA

Step 2: Check the PLC Analog Input

Confirm that the PLC input is configured to receive a 4-20mA current signal.

Identify whether the circuit requires an active current source or passive current simulation.

Step 3: Safely Isolate the Transmitter

Follow the equipment manufacturer's instructions and site safety procedures before disconnecting the transmitter signal wiring.

Ensure that the test will not unintentionally operate pumps, valves, alarms or other machinery.

Step 4: Connect the FNIRSI SG-004A

Select the appropriate current output mode.

Connect the signal generator according to the PLC analog input wiring diagram and SG-004A operating instructions.

Step 5: Generate Test Signals

Apply known current signals and compare them with the expected PLC pressure readings.

SG-004A Output Expected PLC Pressure
4mA 0 bar
8mA 2.5 bar
12mA 5 bar
16mA 7.5 bar
20mA 10 bar

Step 6: Check the PLC Display

Observe whether the PLC or HMI displays the expected pressure values.

If the readings match, the analog input and scaling are likely functioning correctly at the tested points.

If the readings are incorrect, further troubleshooting may be required.

Common Pressure Transmitter Signal Problems

1. PLC Displays Zero Pressure

Check the transmitter output, wiring, loop power and PLC configuration.

2. Pressure Reading Is Unstable

Inspect loose terminals, electrical interference, grounding and transmitter power supply stability.

3. Pressure Reading Is Too High or Too Low

Verify the transmitter measuring range and PLC scaling parameters.

4. PLC Reading Does Not Change

Check the analog input module, signal connections and controller configuration.

5. Simulated Signal Works but Actual Transmitter Does Not

Investigate the transmitter, field wiring, power supply and actual process conditions.

Can the SG-004A Calibrate a Pressure Transmitter?

The FNIRSI SG-004A can assist with electrical signal simulation and functional troubleshooting.

However, generating a 4-20mA signal does not verify the pressure-sensing accuracy of the transmitter itself.

Actual pressure calibration requires an appropriate pressure reference instrument and pressure source, together with a suitable calibration procedure.

The SG-004A is therefore useful for testing the electrical signal path, but should not be considered a complete pressure calibration system.

Where Is Pressure Transmitter Signal Testing Used?

Manufacturing Factories

Troubleshooting pressure monitoring systems in production machinery.

Water Treatment Plants

Checking pressure signals used in pumping and filtration systems.

HVAC Systems

Testing pressure-related control inputs in compatible building automation systems.

Industrial Process Plants

Verifying analog signals used for process monitoring and control.

Control Panel Manufacturing

Checking PLC analog input response before equipment installation.

Who Should Use the FNIRSI SG-004A?

The instrument is relevant for:

  • Instrumentation Technicians

  • Factory Maintenance Engineers

  • PLC Programmers

  • Automation Contractors

  • Process Control Technicians

  • Control Panel Manufacturers

  • Industrial Maintenance Teams

For technicians regularly working with 4-20mA transmitters, a portable signal generator can help identify faults and reduce unnecessary component replacement.

FNIRSI SG-004A Signal Generator Supplier Malaysia

MTM Precision Sdn Bhd supplies industrial testing and measuring instruments for factories, engineering companies and maintenance contractors throughout Malaysia.

For customers working with pressure transmitters, PLC analog inputs, 4-20mA signals and industrial automation, the FNIRSI SG-004A provides a practical solution for signal simulation and troubleshooting.

Customers may WhatsApp us a photo of their pressure transmitter, PLC analog input module or existing testing instrument for product selection assistance.

MTM Precision Sdn Bhd

Showroom & Service Centre

No. 29-1 & 2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia.

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com

Website: www.mtmpre.com.my

We serve customers throughout Kuala Lumpur, Selangor, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kedah, Kelantan, Terengganu, Perlis, Sabah and Sarawak.

08 Oct 2026