FNIRSI SG-004A 4-20mA Loop Troubleshooting Guide Malaysia

FNIRSI SG-004A 4-20mA Loop Troubleshooting Guide Malaysia

4-20mA loop troubleshooting is one of the most common tasks performed by industrial instrumentation technicians, PLC engineers and factory maintenance teams.

Many industrial systems use 4-20mA current signals to transmit measurement information from pressure, temperature, flow and level transmitters to PLC or DCS controllers.

When a current loop stops working correctly, the controller may display an incorrect measurement, zero reading or instrument fault alarm.

The FNIRSI SG-004A Multifunction Signal Generator can assist with troubleshooting compatible 4-20mA circuits by generating known current signals and supporting selected electrical signal testing functions.

This guide explains common 4-20mA loop problems, their possible causes and practical troubleshooting procedures.

What Is a 4-20mA Current Loop?

A 4-20mA current loop is a standard industrial method for transmitting analog measurement signals.

The current represents a value within the configured measurement range.

For example, a pressure transmitter with a 0-10 bar measurement range may produce:

Current Signal Pressure Reading
4mA 0 bar
8mA 2.5 bar
12mA 5 bar
16mA 7.5 bar
20mA 10 bar

4mA represents the lower measurement limit, while 20mA represents the upper measurement limit for this example.

This is called a live-zero signal because the minimum normal measurement is represented by 4mA rather than 0mA.

A current significantly below the normal operating range may indicate a fault, depending on the transmitter configuration.

Problem 1: No 4-20mA Signal

A missing current signal is a common industrial instrumentation problem.

Possible Causes:

  • Missing loop power supply

  • Broken signal cable

  • Loose terminal connection

  • Incorrect wiring polarity

  • Faulty transmitter

  • Incorrect controller input configuration

  • Open current loop

How to Troubleshoot

Step 1: Check the transmitter power supply and loop wiring.

Step 2: Inspect terminals and cable connections.

Step 3: Confirm the PLC input is configured for the correct current signal.

Step 4: Following approved isolation procedures, disconnect the transmitter from the receiving circuit where appropriate.

Step 5: Connect the SG-004A in the correct current output or simulation mode, according to the loop configuration.

Step 6: Apply a known signal such as 12mA.

If the PLC displays the expected measurement, the receiving input is likely functioning at that test point.

Further investigation can then focus on the original transmitter, power supply and field wiring.

Problem 2: Open 4-20mA Current Loop

An open loop occurs when the current path is interrupted.

Common causes include:

  • Disconnected signal wire

  • Broken cable

  • Loose terminal

  • Damaged connector

  • Incorrect terminal connection

In a series current loop, an open circuit prevents normal loop current from flowing.

How to Identify an Open Loop

Step 1: Follow electrical isolation and lockout procedures where required.

Step 2: Inspect the loop wiring diagram.

Step 3: Check the cable and terminal connections.

Step 4: Use an appropriate multimeter to perform continuity testing on a safely de-energized circuit.

Step 5: Repair the wiring fault before reconnecting the equipment.

The SG-004A can then be used to apply a known current signal to a compatible receiving input.

Important: Do not use continuity mode on an energized circuit.

Problem 3: Incorrect 4-20mA Current Reading

Sometimes the PLC receives a current signal but displays the wrong engineering value.

For example, the actual current may be 12mA while the PLC displays 7.5 bar instead of 5 bar.

Possible Causes:

  • Incorrect PLC scaling

  • Wrong transmitter measurement range

  • Incorrect analog input configuration

  • Transmitter configuration error

  • Faulty input module

How to Troubleshoot

Use the SG-004A to apply known current values to the compatible PLC input.

For a 0-10 bar measurement range:

Test Current Expected Reading
4mA 0 bar
12mA 5 bar
20mA 10 bar

If the controller displays incorrect values at these points, investigate the PLC scaling and analog input settings.

If the controller responds correctly, check the transmitter configuration and field circuit.

Problem 4: 24V Loop Power Supply Problem

Many industrial 4-20mA transmitters use a nominal 24V DC power supply.

A two-wire loop-powered transmitter normally requires a suitable external supply to operate.

If the loop supply is missing or insufficient, the transmitter may not function correctly.

What Should Technicians Check?

  • Power supply output voltage

  • Transmitter operating voltage requirements

  • Wiring polarity

  • Total loop resistance

  • PLC input burden

  • Cable condition

Active and Passive Current Loop Testing

It is important to understand the difference between an active current source and a passive current simulation arrangement.

Active Current Output

The signal generator provides the current-driving function for a compatible receiving circuit.

Passive Current Simulation

The signal generator operates in a suitable externally powered current loop, where supported by the selected instrument mode.

Using the wrong mode can result in incorrect operation or equipment damage.

Always confirm the SG-004A mode, wiring and power limits before connecting it to a powered loop.

Problem 5: PLC Analog Input Not Responding

A PLC analog input may fail to respond even when the transmitter appears to be operating normally.

Possible Causes:

  • Incorrect analog input configuration

  • Faulty input module

  • Wrong wiring terminals

  • Incorrect active or passive circuit arrangement

  • Controller software problem

Testing Procedure

Step 1: Review the PLC analog input wiring diagram.

Step 2: Confirm the input is configured for 4-20mA operation.

Step 3: Safely isolate the original transmitter signal.

Step 4: Connect the SG-004A using the appropriate current mode.

Step 5: Apply 4mA, 12mA and 20mA.

Step 6: Observe the PLC or HMI reading.

If the controller does not respond to the simulated current, investigate the input module, wiring and configuration.

Problem 6: Unstable 4-20mA Signal

An unstable current signal may cause the displayed process measurement to fluctuate.

Common causes include:

  • Loose wiring terminals

  • Electrical interference

  • Poor cable shielding

  • Grounding problems

  • Unstable power supply

  • Transmitter faults

  • Actual process fluctuations

Troubleshooting Tips

First, inspect the physical connections and power supply.

Then compare the actual transmitter signal with a stable simulated signal under an approved test arrangement.

If the PLC reading becomes stable when receiving a known signal, the problem may be related to the original field circuit or transmitter.

If the reading remains unstable, investigate the receiving input and associated wiring.

4-20mA Troubleshooting Summary

Problem Possible Cause Recommended Check
No current signal Missing power or open loop Check supply and wiring
Current below expected range Transmitter fault or loop problem Check configuration and circuit
Incorrect PLC reading Scaling error Inject known current
Unstable signal Interference or loose wiring Inspect wiring and grounding
PLC input not responding Input module or configuration fault Test with known current
Transmitter works intermittently Power or connection problem Check supply and terminals

How to Use FNIRSI SG-004A for Basic 4-20mA Loop Testing

Step 1: Identify the Circuit

Confirm the transmitter type, power supply arrangement and PLC input specifications.

Step 2: Review the Wiring Diagram

Identify the correct signal terminals and required active or passive current mode.

Step 3: Prepare the Equipment

Follow the factory's approved maintenance procedures.

Ensure that testing will not unintentionally operate pumps, valves, motors or other equipment.

Step 4: Connect the SG-004A

Use the appropriate terminals and operating mode specified by the manufacturer.

Step 5: Apply Test Signals

Start with a suitable known current value, then test additional points within the permitted range.

Step 6: Compare the Results

Check whether the PLC or controller displays the expected engineering value.

Step 7: Document the Findings

Record the test current, displayed reading and any identified faults.

FNIRSI SG-004A vs Digital Multimeter for 4-20mA Testing

A digital multimeter and a signal generator perform different functions.

Testing Function Digital Multimeter FNIRSI SG-004A
Measure Loop Voltage Yes, depending on model Depends on supported mode
Measure Loop Current Yes, depending on model Depends on supported mode
Generate Known 4-20mA Signal Generally No Yes
Simulate Compatible Transmitter Output Generally No Yes
Check PLC Response to Known Current Requires a Separate Source Yes

For industrial troubleshooting, a multimeter is useful for measuring existing electrical conditions.

A signal generator is useful for applying a controlled electrical signal to the receiving equipment.

Using both instruments can provide a more complete troubleshooting approach.

Who Should Use the FNIRSI SG-004A?

The instrument is relevant for:

  • Factory Maintenance Engineers

  • Instrumentation Technicians

  • PLC Automation Engineers

  • Process Control Technicians

  • Control Panel Builders

  • System Integrators

  • Industrial Maintenance Contractors

It is especially useful for technicians who frequently work with 4-20mA transmitters, PLC analog inputs and industrial control systems.

Important Safety Precautions

Before performing 4-20mA loop troubleshooting:

  • Confirm the correct electrical signal type.

  • Check the loop power supply and input specifications.

  • Verify the active or passive current configuration.

  • Follow the manufacturer's wiring instructions.

  • Do not connect incompatible active outputs together.

  • Do not disconnect critical instrumentation without authorization.

  • Prevent unintended equipment operation during testing.

  • Follow the site's electrical safety procedures.

Safety Note: Never bypass emergency shutdown systems, safety instrumented systems or critical process protection without an approved procedure and authorization.

The SG-004A is useful for electrical signal troubleshooting but does not replace physical sensor calibration equipment or traceable calibration standards.

FNIRSI SG-004A Signal Generator Supplier Malaysia

MTM Precision Sdn Bhd supplies industrial testing and measuring instruments for factories, engineering companies, automation contractors and maintenance teams throughout Malaysia.

For customers working with 4-20mA loop troubleshooting, PLC analog input testing, industrial transmitters and control panel maintenance, the FNIRSI SG-004A provides a practical multifunction signal testing solution.

Customers may WhatsApp us a photo of their 4-20mA transmitter, PLC input module, wiring diagram or existing testing equipment for product selection assistance.

MTM Precision Sdn Bhd

Showroom & Service Centre

No. 29-1 & 2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia.

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com

Website: www.mtmpre.com.my

We serve customers throughout Kuala Lumpur, Selangor, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kedah, Kelantan, Terengganu, Perlis, Sabah and Sarawak.

08 Oct 2026