Where Should Temperature and Humidity Data Loggers Be Placed in a Data Centre? Malaysia
A data logger placed in the wrong location may record a stable temperature while critical server racks experience overheating.
Installing one logger in the centre of a server room is usually not enough to represent the conditions at equipment air intakes, rack tops, hot aisles, UPS batteries and cooling-system problem areas.
Correct data centre temperature and humidity logger placement helps Malaysian facility teams detect hotspots, cooling imbalance, high humidity, condensation risk and recurring environmental changes.
Why Does Logger Placement Matter?
Environmental conditions can vary significantly within the same room.
Differences may occur between:
-
Top and bottom of a server rack
-
Front and rear of a rack
-
Cold aisle and hot aisle
-
Racks near and far from cooling units
-
High-load and low-load racks
-
Open and enclosed areas
-
Server room and UPS battery room
-
Raised floor and occupied space
A poorly positioned logger may be influenced by direct cold air, hot exhaust, sunlight, a nearby wall or another local condition.
Its reading may be accurate for that exact point but not representative of the equipment being protected.
What Should Be Monitored?
Depending on the site and equipment, monitoring may include:
-
Air temperature
-
Relative humidity
-
Temperature trend
-
Humidity trend
-
Rate of temperature change
-
Duration outside site limits
-
High and low values
-
Time of each event
-
Differences between rack locations
-
Cooling-system operating condition
The site’s approved environmental limits should be based on equipment requirements, operating policy and relevant standards.
Temperature Logger or Temperature-and-Humidity Logger?
Temperature Data Logger
A temperature-only logger is suitable when the main concern is:
-
Rack inlet temperature
-
Cooling performance
-
Overnight temperature changes
-
Hotspot verification
-
Temperature comparison between locations
The Elitech RC-5 can support reusable temperature recording and report generation.
Temperature-and-Humidity Data Logger
This is preferable when the investigation includes:
-
High humidity
-
Condensation
-
Low humidity
-
Battery-room conditions
-
Water leakage
-
Door-opening effects
-
Cooling-coil or humidification problems
The Elitech GSP-6 Pro can support temperature and relative-humidity recording.
Priority Logger Locations
Important monitoring points may include:
-
Front-top of critical racks
-
Front-middle of critical racks
-
Front-bottom of critical racks
-
Racks farthest from cooling supply
-
High-load racks
-
Racks with previous temperature alarms
-
Hot-aisle locations
-
Cooling-unit return-air area
-
UPS battery room
-
Network and telecommunications rooms
-
Raised-floor problem areas
-
Areas near doors or wall penetrations
The final number and position of loggers should reflect the room layout and equipment risk.
1. Rack Front or Air-Inlet Side
For server equipment, the most useful reading is often the temperature of the air entering the equipment.
Position the logger:
-
At the rack front
-
Near the equipment air intake
-
Without blocking ventilation
-
Away from direct contact with the rack surface
-
Where it will not be moved accidentally
A logger at the rear mainly records warmer exhaust air and should not be interpreted as the inlet condition.
2. Rack Front-Top
The front-top of a rack is a priority location because it may be affected by:
-
Hot-air recirculation
-
Insufficient upper-rack airflow
-
Missing blanking panels
-
Containment leakage
-
High-load upper equipment
-
Warm air entering from above the rack
If only one location per critical rack is possible, the front-top is often more revealing than the room centre.
3. Rack Front-Middle
The middle position helps show whether the entire rack is warm or whether the problem is concentrated at the top or bottom.
Use it with top and bottom loggers during detailed investigation.
4. Rack Front-Bottom
The bottom position helps evaluate:
-
Cooling-air supply
-
Raised-floor outlet performance
-
Vertical temperature difference
-
Overcooling near floor level
-
Uneven distribution
A cool bottom and warm top may indicate that supplied air is not reaching the entire rack.
Three-Height Monitoring
For a critical rack, position loggers at:
-
Bottom
-
Middle
-
Top
This shows the vertical temperature profile.
Record the height of each logger so that future measurements can be repeated consistently.
5. Rack Rear or Exhaust Side
A rear logger can help evaluate:
-
Equipment heat output
-
Exhaust-air temperature
-
Cooling load
-
Fan or airflow changes
-
Hot-aisle condition
Do not compare a rear exhaust reading directly with a front inlet limit.
Clearly label every logger as front or rear.
6. Cold Aisle
Cold-aisle monitoring can help confirm whether cooling air is reaching the equipment area.
Avoid positioning the logger:
-
Directly above a perforated tile
-
Inside a strong cold-air jet
-
Against a cold surface
-
Too far from equipment intakes
A logger directly in cooling discharge may show an artificially low reading.
7. Hot Aisle
Hot-aisle monitoring helps assess:
-
Exhaust-air condition
-
Containment performance
-
Cooling return path
-
Changes in equipment load
-
Hot-air leakage
Hot-aisle readings should be identified separately from rack-inlet readings.
8. Racks Farthest From Cooling Units
Racks far from the cooling source may receive:
-
Lower airflow
-
Warmer air
-
Less stable cooling
-
Greater temperature variation
Monitor these racks even when central-room temperature appears normal.
9. High-Load Racks
Racks containing high-power servers, storage equipment, PoE switches or dense network equipment may require additional monitoring.
Review:
-
Rack electrical load
-
Equipment arrangement
-
Fan speed
-
Temperature alarms
-
Cooling airflow
-
Previous incidents
10. Racks With Previous Hotspots
A rack with a history of overheating should receive more frequent or continuous monitoring.
Do not remove the logger immediately after corrective work.
Continue recording long enough to verify that the improvement remains stable under different loads and times of day.
11. Cooling-Unit Supply-Air Area
A logger near the supply-air path can help show:
-
Cooling discharge temperature
-
Cooling-unit cycling
-
Loss of cooling
-
Difference between units
-
Recovery after maintenance
Position it consistently and avoid contact with the cooling-unit casing.
12. Cooling-Unit Return-Air Area
Return-air monitoring can show the warmer air returning from the data-centre space.
Comparing supply and return conditions may help identify changes in cooling load or airflow.
This comparison should be interpreted together with equipment and cooling-system information.
13. UPS Battery Room
The UPS battery area may have different environmental conditions from the main server room.
Place a separate logger near the battery installation without:
-
Touching battery terminals
-
Obstructing access
-
Placing it directly against a battery
-
Exposing it to unsafe electrical areas
-
Interfering with ventilation
Monitor temperature and humidity according to the battery manufacturer’s requirements and facility procedure.
14. Network and Telecommunications Room
Smaller network rooms are sometimes overlooked.
Monitor rooms containing:
-
Core switches
-
Distribution switches
-
Patch panels
-
CCTV equipment
-
Access-control equipment
-
Network recorders
-
Telecommunications systems
These rooms may have limited cooling redundancy.
15. Raised-Floor Area
Where authorised and safe, temporary monitoring under a raised floor can support investigation of:
-
Cooling-air distribution
-
Underfloor temperature
-
Moisture risk
-
Air leakage
-
Obstructed airflow
-
Cooling changes
Do not leave unsecured equipment under the floor where it may interfere with cables or airflow.
16. Near Doors
A logger near a frequently opened door may show:
-
Warm-air entry
-
Humidity changes
-
Cooling loss
-
Traffic patterns
-
Influence from adjacent rooms
Avoid treating this reading as representative of the entire room.
It should be used as a specific diagnostic point.
17. Areas Near Water or Condensation Risk
Install temperature-and-humidity monitoring near:
-
Chilled-water pipes
-
Cooling units
-
Previous leakage points
-
Cold surfaces
-
Wall penetrations
-
Areas with condensation history
Do not place the logger where it can become wet unless it is designed for that environment.
18. Reference Location
Maintain at least one stable reference location for comparison.
The reference should be:
-
Away from direct cooling discharge
-
Away from equipment exhaust
-
Away from doors
-
Away from direct sunlight
-
Clearly identified
-
Consistently positioned
A reference logger helps determine whether a change affects the whole room or only one local area.
Temporary Investigation Versus Permanent Monitoring
Temporary Investigation
Use temporary logger placement to investigate:
-
One hot rack
-
Nighttime temperature rise
-
Cooling-unit cycling
-
Door-opening effects
-
Humidity excursions
-
Conditions before and after corrective work
Permanent Monitoring
Permanent monitoring is more suitable for:
-
Critical racks
-
High-load areas
-
UPS battery rooms
-
Locations with repeated alarms
-
Areas far from cooling supply
-
Unmanned network rooms
-
Sites requiring continuous records
Portable loggers can supplement a fixed building-management or environmental-monitoring system.
How Many Data Loggers Are Needed?
There is no single number suitable for every data centre.
The required quantity depends on:
-
Room size
-
Number of racks
-
Rack density
-
Cooling design
-
Containment arrangement
-
Equipment criticality
-
Previous hotspots
-
Environmental risk
-
Monitoring objective
-
Available fixed sensors
A small server room may need several carefully selected points rather than one central logger.
A larger or high-density facility may require monitoring at many rack inlets and supporting areas.
How to Choose the Logging Interval
Possible logging intervals include:
-
One minute for short troubleshooting
-
Five minutes for detailed investigation
-
Ten to fifteen minutes for routine monitoring
-
Longer intervals for slow-changing storage conditions
The correct interval depends on:
-
Speed of expected change
-
Required investigation detail
-
Logger memory
-
Monitoring duration
-
Reporting requirement
-
Battery life
A long interval may miss a brief overheating event.
A very short interval may generate more data than necessary.
How Long Should Monitoring Continue?
Suggested monitoring periods depend on the problem:
| Investigation | Possible monitoring period |
|---|---|
| Immediate cooling check | Several hours |
| Day-and-night comparison | At least 24–72 hours |
| Weekly operating pattern | At least seven days |
| Before-and-after correction | Comparable periods |
| Intermittent unexplained alarm | Until the event is captured |
| Routine environmental monitoring | Continuous or scheduled |
The monitoring period should include the condition that normally produces the complaint.
Record the Operating Condition
Environmental readings are more useful when recorded with:
-
Rack load
-
Server activity
-
Cooling units operating
-
Standby unit status
-
Door condition
-
Maintenance activity
-
Weather condition
-
Power event
-
Alarm time
-
Equipment changes
A temperature increase may be caused by higher IT load rather than a cooling fault.
Avoid Direct Cold-Air Discharge
A logger positioned directly in a cold-air stream may report a low temperature while nearby equipment receives warmer mixed air.
Avoid placing it:
-
Directly over a perforated floor tile
-
Immediately in front of a cooling grille
-
Against an air-conditioning outlet
-
Inside the cooling unit
-
Where airflow is unrepresentative
The objective is usually to measure equipment intake conditions.
Avoid Direct Contact With Surfaces
Do not attach the sensor directly to:
-
Hot server casing
-
Cold pipe
-
Rack metal
-
Wall exposed to sunlight
-
Cooling-unit surface
-
Electrical panel
Surface temperature may differ from surrounding air temperature.
If surface temperature is required, use a suitable surface-temperature method.
Avoid Human and Maintenance Interference
Position loggers where they will not be:
-
Knocked down
-
Covered
-
Moved during cleaning
-
Blocked by boxes
-
Exposed to accidental water
-
Removed without documentation
-
Placed in a walkway
-
Interfering with cables or ventilation
Use clear identification and secure mounting.
Label Every Logger
Each logger should have:
-
Logger identification number
-
Room name
-
Rack number
-
Front or rear designation
-
Top, middle or bottom position
-
Installation date
-
Responsible person
Do not rely on memory when collecting multiple loggers.
Synchronise the Time
Before deployment, confirm:
-
Logger date
-
Logger time
-
Computer time
-
Time zone
-
Daylight or clock settings where relevant
Incorrect timestamps make it difficult to compare temperature changes with alarms, cooling operation and power events.
Check the Logger Before Deployment
Verify:
-
Battery condition
-
Available memory
-
Logging interval
-
Start mode
-
Alarm limits
-
Sensor response
-
Correct date and time
-
Required software
-
Report format
A logger that stops recording halfway through the investigation may leave the main event undocumented.
Download and Review the Data
Do not review only the maximum and minimum readings.
Examine:
-
Full trend
-
Time of each excursion
-
Duration outside limits
-
Rate of change
-
Differences between locations
-
Repeated daily pattern
-
Relationship to cooling cycles
-
Conditions before an alarm
-
Recovery after corrective work
The Elitech RC-5 can provide temperature records, while the Elitech GSP-6 Pro adds relative-humidity information.
Compare Multiple Locations
Useful comparisons include:
-
Rack top versus rack bottom
-
Rack front versus rack rear
-
Problem rack versus normal rack
-
Cold aisle versus hot aisle
-
Cooling supply versus return
-
Server room versus battery room
-
Before correction versus after correction
Use the same logging interval and time reference wherever possible.
Confirm Findings With Other Instruments
Data-logger trends should be supported where necessary by:
-
Handheld temperature and humidity meter
-
Thermal imaging camera
-
Airflow meter
-
Differential pressure meter
-
Clamp meter
-
Cooling-system records
-
Rack power information
A temperature rise shows that a condition changed but may not identify its cause.
Example: Rack Top Is Warm but Bottom Is Cool
Possible causes include:
-
Hot-air recirculation
-
Insufficient upper-rack airflow
-
Missing blanking panels
-
Cable obstruction
-
Poor containment
-
High-load equipment at the top
Confirm using airflow measurement and thermal imaging.
Example: All Loggers Rise at the Same Time
Possible causes include:
-
Cooling-unit shutdown
-
Cooling-control change
-
Power event
-
Higher overall IT load
-
Building HVAC change
-
Door left open
-
Loss of chilled-water supply
Review cooling and facility logs.
Example: Humidity Rises Overnight
Possible causes include:
-
Reduced cooling operation
-
Door opening
-
Outdoor-air entry
-
Humidifier condition
-
Condensation
-
Building HVAC schedule
-
Water leakage
Use a temperature-and-humidity logger rather than a temperature-only model.
Example: One Rack Records Repeated Short Temperature Spikes
Check:
-
Equipment load changes
-
Fan operation
-
Airflow obstruction
-
Containment leakage
-
Logger movement
-
Nearby exhaust air
-
Rack door position
Confirm that the logger is not directly exposed to a temporary hot exhaust stream.
Common Data Logger Placement Mistakes
Avoid:
-
Using only one logger for the entire room
-
Placing the logger in the room centre only
-
Monitoring rack rear instead of equipment inlet
-
Positioning directly in cold-air discharge
-
Attaching the logger to a hot or cold surface
-
Failing to label locations
-
Using different logging intervals without reason
-
Forgetting to synchronise time
-
Ignoring the UPS battery room
-
Monitoring only during office hours
-
Removing loggers before the fault occurs
-
Reviewing maximum and minimum values without the trend
-
Comparing measurements taken under different loads
-
Failing to monitor after corrective work
Recommended Monitoring Kit
A practical environmental investigation kit may include:
-
Elitech RC-5 Temperature Data Logger
-
Elitech GSP-6 Pro Temperature and Humidity Data Logger
-
Handheld temperature and humidity meter
-
Airflow meter
-
Differential pressure meter
-
Noyafa NF-522 Thermal Camera
-
Suitable mounting accessories
-
Location labels
-
Monitoring record sheet
A Better Logger Placement Plan
Use this process:
-
Define the environmental problem.
-
Identify critical and high-load equipment.
-
Review room and cooling layout.
-
Select problem and reference locations.
-
Position loggers at equipment air intakes.
-
Include top, middle and bottom where required.
-
Set the same time and logging interval.
-
Record exact logger positions.
-
Monitor through the relevant operating cycle.
-
Compare trends between locations.
-
Confirm possible causes using other instruments.
-
Repeat monitoring after corrective action.
Measure the Conditions Experienced by the Equipment
The best data-logger location is not necessarily the easiest place to reach.
It should represent the environmental condition experienced by the equipment or area being investigated.
By monitoring rack inlets, different rack heights, critical locations, battery areas and reference points, data-centre teams can detect problems that a single central room sensor may miss.
Correct logger placement turns temperature and humidity records into useful maintenance evidence rather than a collection of isolated readings.