Elitech RC-5 vs GSP-6 Pro for Data Centre Monitoring Malaysia
The Elitech RC-5 and Elitech GSP-6 Pro can both support environmental monitoring, but they are intended for different measurement requirements.
The RC-5 is the simpler choice when a data-centre technician needs to record temperature only.
The GSP-6 Pro is more suitable when both temperature and relative humidity must be monitored, especially during condensation, water-leakage, battery-room or indoor environmental investigations.
This comparison helps Malaysian data-centre teams select the correct logger without paying for unnecessary functions or collecting incomplete information.
Quick Selection
Choose the Elitech RC-5 when you need:
-
Temperature recording
-
Rack-temperature trending
-
Cooling-cycle monitoring
-
Overnight temperature checks
-
Transportable and reusable logging
-
A straightforward temperature report
-
Multiple low-cost measurement points
Choose the Elitech GSP-6 Pro when you need:
-
Temperature and relative-humidity recording
-
Condensation investigation
-
High-humidity troubleshooting
-
UPS battery-room monitoring
-
Cooling and humidity comparison
-
Water-leakage follow-up
-
A more complete environmental record
Main Difference
The most important distinction is simple:
| Model | Temperature | Relative humidity |
|---|---|---|
| Elitech RC-5 | Yes | No |
| Elitech GSP-6 Pro | Yes | Yes |
If humidity can materially affect the investigation, choose the GSP-6 Pro.
If temperature is the only required parameter, the RC-5 may provide a more economical and straightforward solution.
Why Use a Data Logger in a Data Centre?
A handheld meter provides the condition at the moment of inspection.
A data logger records changes over time.
This is useful for detecting:
-
Overnight temperature rise
-
Cooling-unit cycling
-
Rack hotspots
-
Temperature increase after a power event
-
Door-opening effects
-
Weekend HVAC changes
-
Intermittent cooling failure
-
High humidity
-
Condensation risk
-
Differences between rack locations
-
Conditions before and after corrective work
A logger can reveal a problem that is no longer present when the technician arrives.
Elitech RC-5: Best for Temperature Monitoring
The Elitech RC-5 Temperature Data Logger is suitable for applications where temperature is the main concern.
Possible data-centre uses include:
-
Server rack inlet monitoring
-
Rack top-to-bottom comparison
-
Cold-aisle temperature checks
-
Hot-aisle trend monitoring
-
Cooling-unit supply and return comparison
-
Network-room temperature recording
-
Temperature monitoring after power restoration
-
Verifying cooling improvements
-
Monitoring equipment-storage areas
It is especially useful when several temperature points must be monitored economically.
Elitech GSP-6 Pro: Best for Temperature and Humidity
The Elitech GSP-6 Pro Temperature and Humidity Data Logger is more appropriate when moisture-related conditions must also be evaluated.
Possible applications include:
-
Server-room humidity monitoring
-
UPS battery-room monitoring
-
Condensation investigation
-
Chilled-water pipe problem areas
-
Water-leakage follow-up
-
Cooling-system humidity analysis
-
Door and outdoor-air influence
-
Environmental monitoring in network rooms
-
Comparing server room and corridor conditions
It provides more complete evidence when temperature and humidity interact.
Application Comparison
| Data-centre application | RC-5 | GSP-6 Pro |
|---|---|---|
| Rack inlet temperature | Recommended | Suitable |
| Rack top versus bottom | Recommended | Suitable |
| Cold-aisle monitoring | Recommended | Suitable |
| Hot-aisle monitoring | Recommended | Suitable |
| Cooling-cycle investigation | Recommended | Recommended |
| High-humidity investigation | Not sufficient alone | Recommended |
| Condensation investigation | Limited | Recommended |
| UPS battery-room monitoring | Temperature only | Better overall choice |
| Water-leakage follow-up | Limited | Recommended |
| Multiple temperature points | Economical choice | Possible |
| Temperature and humidity report | No | Yes |
Choose RC-5 for Rack Temperature Mapping
When the objective is to map temperature at many rack positions, the RC-5 can be practical.
For example, loggers may be placed at:
-
Rack A01 front-top
-
Rack A01 front-bottom
-
Rack A05 front-top
-
Rack B03 front-top
-
Cold-aisle reference point
-
Cooling-unit return area
Using several temperature loggers provides more useful information than placing one advanced logger in the room centre.
Choose GSP-6 Pro for Condensation Investigation
Condensation depends on more than temperature.
An investigation may require:
-
Air temperature
-
Relative humidity
-
Dew-point assessment
-
Cold-surface temperature
-
Duration of exposure
-
Airflow condition
The GSP-6 Pro provides temperature and relative-humidity trends that can support this assessment.
A thermal camera or surface-temperature probe may still be required to inspect cold surfaces.
Choose GSP-6 Pro for UPS Battery Rooms
Battery performance and service life can be affected by environmental conditions.
A battery-room monitoring plan may include:
-
Air temperature
-
Relative humidity
-
Individual battery temperature
-
Terminal temperature
-
Cooling operation
-
Ventilation condition
-
Battery alarms
The GSP-6 Pro is generally the stronger choice when both temperature and humidity records are required.
Follow the battery manufacturer’s environmental recommendations.
Choose RC-5 for Cooling Failure Investigation
The RC-5 can support temperature trending during:
-
Cooling-unit shutdown
-
Standby cooling activation
-
Power failure
-
Generator transfer
-
Cooling restart
-
Rack-temperature recovery
-
Preventive maintenance
Place loggers at critical rack inlets rather than only in the centre of the room.
Choose GSP-6 Pro After Water Leakage
Following a water-leakage event, humidity monitoring may help confirm whether the area is returning to stable environmental conditions.
It may be placed near:
-
Previous leakage point
-
Cooling unit
-
Affected rack
-
Raised-floor area where appropriate
-
Nearby reference location
The logger does not directly confirm that a wall, cable or piece of equipment is dry.
Use suitable moisture and electrical testing where required.
Spot Measurement Versus Continuous Logging
| Requirement | Handheld meter | RC-5 | GSP-6 Pro |
|---|---|---|---|
| Immediate temperature reading | Yes | Possible | Possible |
| Immediate humidity reading | Selected models | No | Yes |
| Overnight temperature trend | No | Yes | Yes |
| Overnight humidity trend | No | No | Yes |
| Capture an intermittent event | No | Yes | Yes |
| Compare many locations quickly | Yes | Limited | Limited |
| Produce a recorded trend | No | Yes | Yes |
A handheld meter and data logger serve different purposes and often work best together.
Suggested Logger Placement
For rack monitoring, consider:
-
Front-top
-
Front-middle
-
Front-bottom
-
Nearby reference rack
-
Cooling-unit supply or return area
For environmental investigation, consider:
-
Problem area
-
General room reference
-
Near door
-
Near cooling unit
-
Battery room
-
Adjacent room
-
Previous condensation or leakage area
Avoid placing a logger directly in cold-air discharge unless that specific air stream is being investigated.
How Many Loggers Are Required?
The required number depends on:
-
Room size
-
Number of racks
-
Rack density
-
Cooling arrangement
-
Equipment criticality
-
Previous alarm history
-
Monitoring objective
-
Available fixed sensors
A practical approach is to use:
-
Several RC-5 loggers for broad temperature mapping
-
One or more GSP-6 Pro units at humidity-sensitive locations
This combination can balance coverage and measurement capability.
Example Monitoring Combination
A server room investigation might use:
-
RC-5 at rack front-top
-
RC-5 at rack front-bottom
-
RC-5 at a normal reference rack
-
GSP-6 Pro near the cooling unit
-
GSP-6 Pro near the room entrance
This arrangement shows both temperature distribution and humidity behaviour.
Logging Interval
Possible settings include:
-
One minute for fast troubleshooting events
-
Five minutes for detailed investigation
-
Ten to fifteen minutes for routine trending
-
Longer intervals for extended stable monitoring
Select the interval according to:
-
Expected event duration
-
Required detail
-
Memory capacity
-
Monitoring period
-
Reporting requirement
Use the same interval when comparing several locations.
Monitoring Duration
| Objective | Possible duration |
|---|---|
| Immediate cooling check | Several hours |
| Day-and-night comparison | 24–72 hours |
| Weekly operating pattern | At least seven days |
| Intermittent alarm | Until the event is captured |
| Corrective-action verification | Before and after comparable periods |
| Routine monitoring | Continuous or scheduled |
The logger should remain installed long enough to capture the operating condition that creates the complaint.
What Should Be Recorded Before Deployment?
Record:
-
Logger model
-
Logger identification number
-
Exact location
-
Rack number
-
Front or rear
-
Top, middle or bottom
-
Start date and time
-
Logging interval
-
Alarm settings
-
Battery condition
-
Responsible technician
Photograph the logger position where site security permits.
Review More Than Maximum and Minimum Values
A complete review should consider:
-
Full temperature trend
-
Full humidity trend
-
Time of each excursion
-
Duration outside limits
-
Rate of change
-
Repeated daily pattern
-
Difference between locations
-
Cooling-unit status
-
Equipment load
-
Door activity
-
Power events
A short peak may have a different cause and impact from a condition lasting several hours.
Example: Rack Top Overheats at Night
Recommended approach:
-
Place RC-5 at rack front-top
-
Place another RC-5 at rack front-bottom
-
Monitor a nearby reference rack
-
Review cooling schedule
-
Compare temperatures over several nights
-
Measure airflow during the affected period
The RC-5 is sufficient if humidity is not part of the complaint.
Example: Humidity Rises When the Door Opens
Recommended approach:
-
Place GSP-6 Pro near the door
-
Place another logger at the room reference point
-
Monitor adjacent-area conditions
-
Review door-access times
-
Check differential pressure
-
Inspect door seals
Temperature-only records would provide incomplete evidence.
Example: Condensation Appears on a Chilled-Water Pipe
Recommended approach:
-
Use GSP-6 Pro for air temperature and humidity
-
Check dew point
-
Measure the pipe-surface temperature
-
Inspect insulation
-
Use thermal imaging for temperature patterns
-
Check for humid-air entry
The GSP-6 Pro supports the investigation but should not be used as the only instrument.
Example: Checking Cooling Improvement
Install the same logger:
-
At the same location
-
At the same height
-
Using the same logging interval
-
During a similar operating load
-
For a comparable period
This makes the before-and-after comparison more reliable.
RC-5 Advantages
For suitable applications, the RC-5 offers:
-
Straightforward temperature monitoring
-
Reusable logging
-
Practical deployment at multiple locations
-
Useful temperature reports
-
Lower complexity when humidity is unnecessary
-
Suitable rack-temperature mapping
Its main limitation for this comparison is that it does not record relative humidity.
GSP-6 Pro Advantages
For suitable applications, the GSP-6 Pro offers:
-
Temperature recording
-
Relative-humidity recording
-
Better support for condensation investigation
-
Better support for battery-room monitoring
-
More complete environmental information
-
Useful high-humidity troubleshooting data
It may be unnecessary when the requirement is strictly temperature only.
When RC-5 Is Not Enough
Do not rely on the RC-5 alone when investigating:
-
High humidity
-
Low humidity
-
Condensation
-
Water leakage
-
Damp room conditions
-
Humid-air entry
-
Moisture-related equipment problems
Use a temperature-and-humidity logger such as the GSP-6 Pro.
When GSP-6 Pro May Be More Than Necessary
The GSP-6 Pro may provide more information than required when:
-
Only rack temperature matters
-
Many temperature points are needed
-
Humidity is already monitored by a reliable fixed system
-
The investigation is limited to cooling-temperature recovery
-
A simple temperature report is sufficient
In these situations, the RC-5 may be the more efficient choice.
Data Logger and Thermal Camera
A data logger shows when conditions change.
A thermal camera shows where unusual surface temperatures appear.
Use them together when investigating:
-
Rack hotspots
-
Cooling imbalance
-
Electrical heating
-
Condensation-prone surfaces
-
Failed equipment fans
-
Hot PDU connections
The Noyafa NF-522 Thermal Camera can support temperature-pattern inspection, while the logger provides the time-based record.
Data Logger and Airflow Meter
A logger may show a temperature increase but not explain why it occurred.
An airflow meter can help check whether:
-
Rack inlet airflow is weak
-
Cooling discharge has changed
-
Upper-rack airflow is insufficient
-
A grille is blocked
-
Containment leakage is present
The combination provides stronger evidence than either reading alone.
Common Selection Mistakes
Avoid:
-
Buying RC-5 for a humidity investigation
-
Buying GSP-6 Pro when only simple temperature mapping is required
-
Using one logger for the entire server room
-
Placing the logger at the rack rear when inlet temperature is required
-
Installing it directly in cooling discharge
-
Forgetting to synchronise logger time
-
Using different intervals for comparison points
-
Reviewing only maximum and minimum readings
-
Removing the logger before the event occurs
-
Failing to repeat monitoring after corrective work
Which Model Should You Buy?
Choose Elitech RC-5 if your main requirement is:
“I need to record server rack or room temperature over time.”
Choose Elitech GSP-6 Pro if your requirement is:
“I need to record both temperature and humidity or investigate condensation.”
For a more complete data-centre monitoring kit, use both:
-
RC-5 units for multiple rack-temperature points
-
GSP-6 Pro units for humidity-sensitive and reference locations
Recommended Supporting Instruments
Depending on the investigation, combine the logger with:
-
Handheld temperature and humidity meter
-
Noyafa NF-522 Thermal Camera
-
Airflow meter
-
Differential pressure meter
-
AC/DC clamp meter
-
Moisture meter
-
Power quality analyzer
Select the Logger According to the Question
The RC-5 and GSP-6 Pro are not direct substitutes in every application.
The correct choice depends on what the maintenance team needs to prove.
Use the RC-5 for practical temperature trending and multi-point rack monitoring.
Use the GSP-6 Pro when relative humidity affects the diagnosis, particularly in condensation, leakage and battery-room applications.
Selecting the logger according to the measurement objective produces clearer evidence and avoids repeating the entire monitoring exercise with a different instrument.