How to Test Fibre Optic Cable Loss Using the NOVKER NK281 Stable Light Source Malaysia

A fibre optic cable may look physically undamaged but still suffer from excessive optical loss caused by dirty connectors, poor splicing, sharp bends or damaged components.

To check the total loss of a fibre link, technicians can use the NOVKER NK281 Stable Light Source together with a compatible optical power meter.

This guide explains the basic testing process and the common mistakes to avoid when measuring fibre optic cable loss in Malaysia.

What Equipment Is Required?

A basic fibre-loss test requires:

  • NOVKER NK281 Stable Light Source

  • Compatible optical power meter

  • Suitable reference patch cords

  • Correct SC, FC or ST adaptors

  • Fibre connector cleaning tools

  • Fibre under test

The light source and power meter must support the same wavelength. For example, when the NK281 transmits at 1310nm, the optical power meter must also be set to 1310nm.

Using different wavelength settings will produce an incorrect result.

What Does the NK281 Measure?

The NK281 does not directly display the cable loss. It supplies a stable optical signal into one end of the fibre.

The optical power meter measures the signal received at the other end. The technician compares this reading against a reference value to calculate the total insertion loss.

The basic relationship is:

Fibre Link Loss = Reference Power − Received Power

The result is normally shown in dB.

For example:

  • Reference reading: −5.00dBm

  • Received reading: −7.20dBm

  • Total link loss: 2.20dB

This result represents the combined loss from the fibre cable, connectors, adaptors and splices within the tested link.

Step 1: Confirm the Fibre Type

Before starting the test, determine whether the cable is:

  • Single-mode fibre

  • Multimode fibre

Common single-mode testing wavelengths include:

  • 1310nm

  • 1550nm

Common multimode testing wavelengths include:

  • 850nm

  • 1300nm

The NK281 is available in different wavelength configurations. Always check the actual model configuration instead of assuming that every unit supports every wavelength.

Step 2: Inspect and Clean the Connectors

Dirty fibre connectors are one of the most common causes of unstable or unusually high loss readings.

Before connecting the test equipment:

  • Inspect the connector if suitable inspection equipment is available.

  • Clean the ferrule using approved fibre-cleaning tools.

  • Do not touch the connector end face.

  • Check that the patch cord is not damaged.

  • Ensure that the adaptor matches the connector type.

A contaminated connector can affect the result even if the installed fibre link is in good condition.

Step 3: Switch On the Test Equipment

Turn on the NK281 and the optical power meter.

Allow the equipment to stabilise according to the manufacturer’s instructions. Confirm that both instruments have sufficient battery power before beginning a long site test.

Select the required wavelength on the NK281. Set the optical power meter to the same wavelength.

For a 1310nm test:

  • NK281 setting: 1310nm

  • Optical power meter setting: 1310nm

Repeat the same procedure at 1550nm when dual-wavelength testing is required.

Step 4: Establish the Reference Value

The reference measurement is essential. Without a proper reference, the final loss result may not be meaningful.

Connect the NK281 directly to the optical power meter using a clean reference patch cord and the correct adaptors.

Wait until the displayed value becomes stable. Depending on the power meter, the technician may:

  • Record the displayed dBm value manually, or

  • Press the reference or zero button to establish a 0dB reference

Do not disconnect or replace the reference patch cord unnecessarily after establishing the reference.

If the connection is disturbed, establish the reference again.

Step 5: Connect the Fibre Link Under Test

After the reference has been established:

  1. Keep the reference patch cords clean.

  2. Connect the NK281 to one end of the installed fibre.

  3. Connect the optical power meter to the opposite end.

  4. Confirm that the correct fibre core is being tested.

  5. Wait for the reading to stabilise.

  6. Record the measured loss.

For long-distance or building-to-building fibre links, two technicians may be needed—one at each end of the cable.

Clear fibre-core identification and communication between both technicians are important to prevent testing the wrong fibre.

Step 6: Test at More Than One Wavelength

Single-mode fibre links are commonly checked at both 1310nm and 1550nm.

Testing at two wavelengths can reveal different conditions:

  • 1310nm is commonly used for standard link-loss testing.

  • 1550nm is more sensitive to bending-related loss.

A link that performs normally at 1310nm but shows significantly higher loss at 1550nm may have excessive bending or cable-routing problems.

Record the result for each wavelength separately.

Step 7: Compare the Result with the Loss Budget

A measured loss value cannot be judged without considering the expected loss budget.

The acceptable total loss depends on:

  • Fibre length

  • Number of connectors

  • Number of splices

  • Fibre type

  • Testing wavelength

  • Project specifications

  • Network-equipment requirements

A simple estimated loss budget may include:

Total allowable loss = Fibre loss + Connector loss + Splice loss + Design margin

The actual acceptance limit should follow the project requirement or the applicable cabling standard.

Common Causes of High Fibre Loss

If the measured loss is higher than expected, check for:

  • Dirty fibre connectors

  • Damaged reference patch cords

  • Loose adaptors

  • Poor fusion splices

  • Mechanical-splice loss

  • Excessive cable bending

  • Crushed fibre cable

  • Incorrect connector mating

  • Wrong wavelength setting

  • Incorrect reference procedure

  • Testing the wrong fibre core

Clean and reconnect the test cords before concluding that the installed cable is defective.

Why Is the Reading Unstable?

An unstable result may be caused by:

  • Contaminated connectors

  • Loose optical connections

  • Damaged patch cords

  • Low instrument battery

  • Movement of the test cable

  • Incompatible adaptors

  • Incorrect light-source mode

For loss measurement, use a continuous and stable output mode unless the testing procedure requires a modulated signal.

Can the NK281 Locate a Fibre Break?

The NK281 can help determine whether optical power passes through the link, but it does not show the exact distance to a break.

Use the appropriate instrument for each task:

  • Stable light source and power meter: Measure total end-to-end loss.

  • Visual Fault Locator: Identify visible faults over shorter distances.

  • OTDR: Locate breaks, splices, connectors and loss events by distance.

  • Fibre identifier: Identify traffic or signal direction without disconnecting the fibre.

For complete fibre troubleshooting, technicians commonly use more than one type of tester.

Additional Network-Cable Functions

The NK281 is useful for technicians working on mixed network infrastructure because it also includes RJ45 testing functions.

Depending on its configuration, it can assist with:

  • RJ45 cable-sequence checking

  • Open and short-circuit identification

  • Network-cable length measurement

  • Routine structured-cabling troubleshooting

This makes it suitable for contractors handling fibre backbones together with copper Ethernet cabling inside offices, factories, commercial buildings and data centres.

Recommended Applications in Malaysia

The NOVKER NK281 is suitable for:

  • FTTH contractors

  • Fibre optic installation companies

  • CCTV and network installers

  • Data centre cabling teams

  • Telecom maintenance contractors

  • Factory network maintenance

  • Campus and commercial-building networks

  • Fibre patch-panel inspection

  • Structured-cabling projects

Important Testing Reminder

A stable light source must be used together with a compatible optical power meter. Buying the NK281 alone does not create a complete loss-measurement system.

Before ordering, confirm:

  • Required wavelength

  • Single-mode or multimode application

  • Optical connector type

  • Included adaptors

  • Suitable power-meter range

  • Patch-cord requirements

MTM Precision can assist customers in selecting the correct light source, optical power meter and accessories for their fibre network.

Contact MTM Precision

Contact us for the NOVKER NK281 Stable Light Source, optical power meters, VFLs, fibre identifiers, OTDRs and complete fibre optic testing equipment in Malaysia.

MTM Precision Sdn Bhd
No. 29-1 & 29-2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia.

Website: www.mtmpre.com.my
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com

04 Sep 2026