How to Detect Gas Leaks During Factory Maintenance Malaysia

Gas leaks in a factory may occur around pipes, valves, regulators, storage areas, process equipment and utility systems. Some leaks produce a noticeable smell, but others may be invisible, odourless or difficult to recognise before they become dangerous.

 

A portable gas detector helps maintenance teams identify hazardous atmospheres and investigate possible leak sources. However, the detector must match the target gas and the way the inspection will be performed.

 

Where Can Gas Leaks Occur in a Factory?

 

Common inspection points include:

 

Pipe joints and flanges

 

Valves and valve stems

 

Pressure regulators

 

Flexible hoses

 

Gas-cylinder connections

 

Storage tanks

 

Boiler and burner systems

 

Refrigeration equipment

 

Compressors

 

Chemical-processing equipment

 

Wastewater areas

 

Battery-charging rooms

 

Confined spaces

 

Gas cabinets and manifolds

 

Leaks may develop due to worn seals, corrosion, vibration, loose fittings, physical damage or incorrect installation.

 

Identify the Target Gas First

 

There is no universal portable detector that is suitable for every gas.

 

Before selecting an instrument, determine:

 

Which gas may be leaking

 

Whether it is combustible, toxic or asphyxiating

 

Expected concentration

 

Required measuring range

 

Possible cross-sensitivities

 

Whether the work area is classified as hazardous

 

Whether remote sampling is required

 

Examples of gases that may be encountered during factory maintenance include:

 

Methane

 

LPG

 

Hydrogen

 

Carbon monoxide

 

Hydrogen sulphide

 

Ammonia

 

Carbon dioxide

 

Oxygen deficiency

 

Refrigerant gases

 

Volatile organic compounds

 

A standard four-gas detector usually measures O₂, LEL, CO and H₂S. It should not be assumed to detect ammonia, carbon dioxide, refrigerants or every combustible gas without confirming its sensor configuration.

 

Gas Leak Detector vs Multi-Gas Detector

 

These instruments may be used for different purposes.

 

Gas Leak Detector

 

A gas leak detector is generally used to investigate and locate a suspected leak around a particular component.

 

Typical applications include:

 

Checking pipe connections

 

Scanning valves and regulators

 

Inspecting gas appliances

 

Testing cylinder connections

 

Tracing leakage around machinery

 

Checking natural-gas installations

 

A probe-equipped pump detector can help the technician compare readings at different points and move closer to the suspected source.

 

Multi-Gas Detector

 

A multi-gas detector is mainly used to warn workers when the surrounding atmosphere becomes hazardous.

 

It is suitable for:

 

Confined-space entry

 

Factory shutdown work

 

Wastewater maintenance

 

Tank cleaning

 

Boiler-room inspection

 

Chemical-process areas

 

Personal gas monitoring

 

Some pump-type multi-gas detectors can also perform remote sampling before workers enter an area.

 

Pump-Type or Diffusion-Type for Leak Detection?

 

For locating a leak, a pump-type detector is generally more practical because it actively draws gas through a probe or tube.

 

It allows the user to:

 

Sample from a safer distance

 

Reach difficult locations

 

Check inside enclosures

 

Compare concentrations at multiple points

 

Test an area before approaching it

 

A diffusion detector is better suited to personal protection and continuous monitoring around the worker.

 

For higher-risk maintenance, teams may use a pump-type detector to investigate the area while workers also wear diffusion-type personal detectors.

 

Practical Gas-Leak Inspection Sequence

 

Gas-leak work should be carried out by trained personnel under the factory’s safety procedure. A general inspection sequence includes:

 

1. Review the Process

 

Identify the gas, equipment, pressure, operating condition and previous leak history.

 

2. Control the Work Area

 

Restrict access where necessary. Remove ignition sources when a combustible atmosphere may be present and follow the appropriate emergency or permit procedure.

 

3. Confirm the Detector Configuration

 

Check that the installed sensor is designed for the suspected gas and required concentration range.

 

4. Inspect the Detector

 

Check:

 

Sensor openings

 

Filter

 

Sampling probe

 

Tubing

 

Pump operation

 

Battery level

 

Calibration status

 

5. Perform a Bump Test

 

Expose the detector to suitable test gas and confirm that the sensors and alarms respond before relying on it.

 

6. Check the General Atmosphere

 

Before moving directly toward the suspected source, check whether the surrounding area is already hazardous.

 

7. Approach Gradually

 

Move the probe slowly around potential leakage points. Observe changes in readings instead of immediately placing the detector against the equipment.

 

8. Monitor Continuously

 

Gas concentration may change with ventilation, equipment operation and maintenance activities. Continue monitoring until the work is completed and the area has been confirmed safe under the site procedure.

 

Why Does the Reading Increase but Not Identify the Exact Leak?

 

A gas detector measures the gas reaching its sensor. Air movement can carry gas away from the actual leak point.

 

Readings may be affected by:

 

Ventilation fans

 

Open doors

 

Wind

 

Hot surfaces

 

Equipment movement

 

Gas density

 

Probe position

 

Sampling-tube length

 

Pump-flow rate

 

The highest reading does not always sit directly over the damaged component. Technicians may need to approach from different directions and compare multiple points.

 

Should You Use Soap Solution?

 

A suitable leak-detection solution may help confirm leakage at certain pressurised pipe joints by producing bubbles. However, it is not appropriate for every gas, surface, pressure or electrical installation.

 

A gas detector provides atmospheric information and may help locate the general leak area. A leak-detection solution can sometimes help confirm the exact joint.

 

Users should follow the equipment manufacturer’s instructions and site procedures. Do not apply unsuitable liquid to hot, energised, reactive or sensitive equipment.

 

Common Gas-Leak Detection Mistakes

 

Avoid these common mistakes:

 

Depending only on smell

 

Using a detector with the wrong sensor

 

Skipping the bump test

 

Ignoring an overdue calibration

 

Blocking the detector’s gas inlet

 

Moving the probe too quickly

 

Testing only one side of the equipment

 

Ignoring ventilation direction

 

Using a diffusion detector for inaccessible remote points

 

Entering an enclosed area before atmospheric testing

 

Continuing work after a gas alarm without following site procedure

 

Assuming that a zero reading proves there is no hazard

 

A zero reading may also result from an expired sensor, blocked inlet, unsuitable measuring range or incorrect detector.

 

What Should You Do When the Detector Alarms?

 

Treat every alarm according to the factory’s established safety procedure.

 

Depending on the site and gas involved, necessary actions may include:

 

Stop work

 

Warn nearby personnel

 

Leave the affected area

 

Prevent unauthorised entry

 

Eliminate ignition sources where safe and applicable

 

Isolate the gas supply using approved procedures

 

Improve ventilation

 

Inform the safety or emergency-response team

 

Continue remote monitoring from a safe location

 

Do not silence the alarm and continue working without identifying the reason for the reading.

 

Gas Detection for Planned Factory Maintenance

 

Gas detection should be prepared before shutdown or maintenance work begins.

 

Planning may include:

 

Listing the gases used in each production area

 

Identifying confined spaces

 

Selecting suitable sensors

 

Confirming the number of detectors needed

 

Assigning pump and personal monitors

 

Scheduling calibration

 

Preparing bump-test gas and regulators

 

Charging detector batteries

 

Inspecting sampling tubes and filters

 

Recording detector assignments

 

Preparing spare instruments

 

Last-minute detector selection increases the risk of receiving an instrument with the wrong gas configuration.

 

Gas Detector Options from MTM Precision

 

MTM Precision supplies portable gas detectors for gas-leak investigation, confined-space entry and factory-maintenance applications in Malaysia.

 

Selected solutions include:

 

OTYWELL OT131 – pump-type detector for selected gas-leak applications

 

OTYWELL G40S – portable multi-gas monitoring

 

OTYWELL G60 – industrial multi-gas configurations

 

OTYWELL OT135S – pump-type multi-gas configurations

 

Eranntex MS104K series – professional multi-gas monitoring options

 

Smart Sensor ST8904 – four-gas detector

 

Wintact WT8812 – portable multi-gas detector

 

The exact detector should be selected according to the target gas, measuring range, pump requirement and working environment.

 

Information Required for a Recommendation

 

When requesting a quotation, provide:

 

Target gas

 

Factory process or equipment

 

Expected concentration

 

Leak location or personal-monitoring requirement

 

Indoor, outdoor or confined-space use

 

Pump or diffusion preference

 

Required measuring range

 

Number of users

 

Data-recording requirement

 

Calibration or test-report requirement

 

Photos of the equipment and a description of the work process may also help identify a suitable detector.

 

Contact MTM Precision

 

Contact MTM Precision for gas-leak detectors and multi-gas detectors for factory maintenance, confined spaces and industrial-safety applications in Malaysia.

 

MTM Precision Sdn Bhd

Website: www.mtmpre.com

Email: mtmpre@yahoo.com

WhatsApp: 016-660 7346

 

Showroom & Service Centre

No. 29-1 & 29-2, Jalan Bandar 18,

Pusat Bandar Puchong,

47160 Puchong, Selangor, Malaysia.


 

14 Sep 2026