Why Does a Four-Gas Detector Show 20.9% Oxygen Malaysia

Why Does a Four-Gas Detector Show 20.9% Oxygen Malaysia

 

When the Smart Sensor ST8904 or another four-gas detector is switched on in fresh air, its oxygen channel will normally display approximately 20.9% VOL.

 

Many first-time users ask whether this means the detector has found an oxygen leak or whether the reading should be zero.

 

The answer is simple:

 

Unlike toxic-gas channels, the oxygen channel is expected to show the percentage of oxygen naturally present in the surrounding air.

 

Why Is the Normal Oxygen Reading About 20.9%?

 

Normal dry air at sea level contains approximately:

 

78% nitrogen

 

20.9% oxygen

 

Small amounts of argon, carbon dioxide and other gases

 

Therefore, a correctly functioning portable gas detector will generally show an oxygen reading near 20.9% in suitable fresh air.

 

The other ST8904 channels may normally display approximately:

 

CO: 0 ppm

 

H₂S: 0 ppm

 

LEL: 0%

 

O₂: Approximately 20.9% VOL

 

Oxygen is different because it is naturally present in the atmosphere.

 

Is 20.9% an Oxygen Leak?

 

No. A reading around 20.9% in normal fresh air is expected.

 

An oxygen leak or oxygen-enriched atmosphere would cause the reading to increase above the normal atmospheric level.

 

Oxygen enrichment can increase fire and combustion risks. It should not be treated as harmless simply because oxygen is necessary for breathing.

 

What Does a Low Oxygen Reading Mean?

 

A lower-than-expected oxygen reading may indicate that oxygen has been:

 

Displaced by another gas

 

Consumed by combustion

 

Consumed by biological activity

 

Reduced by oxidation or corrosion

 

Affected by a chemical reaction

 

Diluted inside an enclosed space

 

Potential locations include:

 

Storage tanks

 

Manholes

 

Sewers

 

Underground chambers

 

Process vessels

 

Silos

 

Wastewater facilities

 

Poorly ventilated rooms

 

A low oxygen reading can also result from sensor drift, incorrect zeroing or sensor deterioration. Always investigate before assuming the reading is safe or incorrect.

 

Can a Normal Oxygen Reading Prove the Area Is Safe?

 

No.

 

A reading near 20.9% oxygen does not prove that the atmosphere is free from every hazard.

 

For example:

 

Carbon monoxide may still be present

 

Hydrogen sulphide may still be present

 

A combustible gas may still be present

 

A specialised toxic gas may be present

 

The atmosphere may change after work starts

 

This is why the Smart Sensor ST8904 monitors O₂ together with CO, H₂S and LEL.

 

The detector must also be suitable for the gases expected at the site.

 

Why Does the ST8904 Show 20.8% or 21.0% Instead?

 

A small difference from 20.9% does not automatically indicate a fault.

 

The displayed value can be influenced by:

 

Sensor tolerance

 

Calibration condition

 

Temperature

 

Humidity

 

Atmospheric pressure

 

Altitude

 

Sensor age

 

Display resolution

 

Actual environmental conditions

 

However, a reading that is significantly different, unstable or unable to return to its expected fresh-air value should be investigated.

 

Why Does the Oxygen Reading Drop When Another Gas Is Present?

 

When another gas displaces normal air, the percentage of oxygen may decrease.

 

Possible examples include:

 

Nitrogen entering a space

 

Carbon dioxide accumulation

 

Fuel gas leakage

 

Process-gas release

 

Decomposition gas inside a tank or sewer

 

The oxygen sensor may show that oxygen has been displaced, but it does not identify the gas responsible.

 

A normal-looking reading on the CO, H₂S and LEL channels does not exclude a different gas that the detector cannot measure.

 

Should the Oxygen Channel Be Zeroed to 0%?

 

No. Do not attempt to make the oxygen channel display zero in fresh air.

 

The fresh-air reference for oxygen is normally around the atmospheric oxygen concentration, while the toxic and combustible channels generally use a zero baseline in verified clean air.

 

Incorrect zeroing can produce misleading readings and unsafe decisions.

 

Follow the operating procedure for the specific detector.

 

Where Should Fresh-Air Zeroing Be Performed?

 

Perform fresh-air zeroing only in an area known to contain clean, uncontaminated air.

 

Do not zero the detector:

 

Inside the space being tested

 

Near vehicle exhaust

 

Beside an open chemical container

 

Near fuel or solvent vapour

 

Inside a poorly ventilated room

 

Where the atmosphere is already uncertain

 

Zeroing in contaminated air may cause the detector to treat a hazardous concentration as its baseline.

 

What If the ST8904 Shows 19% Oxygen in Open Air?

 

Move the detector to a location independently confirmed to contain suitable fresh air and allow the reading to stabilise.

 

Then check:

 

Was the detector switched on in contaminated air?

 

Was it zeroed incorrectly?

 

Is the sensor opening blocked?

 

Has the detector been exposed to water or condensation?

 

Is the oxygen sensor ageing?

 

Has the detector passed its bump test?

 

Is calibration overdue?

 

Does another detector show the same result?

 

Do not use the detector for safety-critical work if the oxygen channel cannot be verified.

 

Why Does the Reading Change Inside a Manhole or Tank?

 

A confined space may have different atmospheric conditions at different depths.

 

The oxygen concentration near the opening may differ from the concentration at the middle or bottom of the space.

 

Possible reasons include:

 

Gas density

 

Inadequate ventilation

 

Connected pipelines

 

Decomposition

 

Chemical reactions

 

Sludge disturbance

 

Process-gas entry

 

Testing only at the opening may not represent the complete atmosphere.

 

Does Ventilation Immediately Make the Space Safe?

 

Not necessarily.

 

Ventilation may improve the atmosphere, but the space should be retested according to the approved procedure.

 

The team must also consider:

 

Whether ventilation reaches the entire space

 

Whether gas continues entering

 

Whether work will create new hazards

 

Whether ventilation could fail

 

Whether continuous monitoring is required

 

A single acceptable reading before work begins does not guarantee that conditions will remain safe.

 

Bump Test and Calibration of the Oxygen Sensor

 

A bump test exposes the oxygen sensor to an appropriate test condition to confirm that it responds and activates the required alarm.

 

Calibration compares the detector with a known reference and adjusts the reading when necessary.

 

The oxygen channel may require further inspection when:

 

It fails a bump test

 

It cannot be calibrated

 

Response becomes slow

 

Reading fluctuates excessively

 

Fresh-air reading remains abnormal

 

A sensor fault appears

 

The detector has experienced impact, water or chemical exposure

 

The oxygen sensor is a consumable component and may eventually require replacement.

 

Smart Sensor ST8904 Oxygen Measuring Range

 

The ST8904 oxygen channel measures:

 

0–30% VOL O₂

 

The instrument also monitors:

 

CO: 0–999 ppm

 

H₂S: 0–500 ppm

 

Combustible gas: 0–100% LEL

 

This combination is commonly used for confined-space, wastewater, manhole and factory-maintenance applications.

 

Need Help with an Abnormal Oxygen Reading?

 

MTM Precision supplies the Smart Sensor ST8904 four-in-one gas detector in Malaysia.

 

When requesting assistance, provide:

 

Actual oxygen reading

 

Location of the test

 

Fresh-air reading

 

Last bump-test result

 

Last calibration date

 

Sensor age, if known

 

Photos or video of the display

 

Whether the detector was exposed to water, impact or high gas concentration

 

Do not rely on an instrument for confined-space entry when its oxygen reading cannot be verified.

 

Contact MTM Precision

 

MTM Precision Sdn. Bhd.

 

Office: +603-8080 7172

Desmond: +6019-220 7346

Fifi Ng: +6016-660 7346

WhatsApp: +6019-220 7346

Email: enquiry@mtmpre.com.my

 

Showroom & Service Centre

No. 29-1 & 29-2, Jalan Bandar 18,

Pusat Bandar Puchong,

47160 Puchong, Selangor, Malaysia.

 

Serving customers throughout Selangor, Kuala Lumpur, Johor, Penang, Perak, Melaka, Negeri Sembilan, Pahang, Kedah, Perlis, Terengganu, Sabah and Sarawak.


 

16 Sep 2026