What Does %LEL Mean on Smart Sensor ST8904 Gas Detector Malaysia
What Does %LEL Mean on Smart Sensor ST8904 Gas Detector Malaysia
The Smart Sensor ST8904 measures oxygen, carbon monoxide, hydrogen sulphide and combustible gas.
Its combustible-gas reading is displayed as %LEL. This is frequently misunderstood as the percentage of gas in the air.
However:
10% LEL does not normally mean that the atmosphere contains 10% gas by volume.
It means the detected concentration has reached 10% of the level at which the relevant combustible gas could begin forming an ignitable mixture under specified conditions.
What Does LEL Stand For?
LEL means Lower Explosive Limit, also called the Lower Flammable Limit in some references.
It represents the lowest concentration of a combustible gas or vapour in air that can support ignition under defined test conditions.
Below the LEL, the mixture may be too lean to burn.
At or above the LEL, the atmosphere may become ignitable if an appropriate ignition source is present.
The exact LEL is different for every gas.
What Does 100% LEL Mean?
A reading of 100% LEL represents the lower explosive limit of the gas according to the detector’s calibration and response basis.
It does not mean that the surrounding atmosphere is 100% combustible gas.
For example:
0% LEL indicates no detectable combustible-gas response relative to the instrument’s scale
10% LEL means the response has reached 10% of the lower explosive limit
50% LEL means the response has reached half of the lower explosive limit
100% LEL represents the lower explosive limit
Any increasing LEL reading should be treated seriously according to the site’s safety procedure.
%LEL vs %VOL
These two units are not interchangeable.
UnitMeaning%LELPercentage of the gas’s lower explosive limit%VOLPercentage by volume in the atmosphereppmParts per million
The relationship between %LEL and %VOL depends on the specific gas.
A reading should never be converted without knowing:
The gas involved
Its published LEL
The detector’s calibration gas
The sensor’s response characteristics
Environmental and application conditions
Can the ST8904 Identify Which Combustible Gas Is Present?
No.
The ST8904’s LEL channel can respond to combustible gas, but it does not normally identify the exact gas.
A rising reading may be caused by substances such as:
Methane
LPG components
Natural gas
Fuel vapour
Solvent vapour
Other combustible gases or vapours
The response can differ between gases.
If the work requires gas identification or accurate measurement of a particular compound, a gas-specific instrument may be necessary.
Why Does Calibration Gas Matter?
A combustible-gas sensor is calibrated using a specified reference gas.
Its response to another combustible gas may be different. Therefore, two gases at similar concentrations may not produce the same displayed %LEL reading.
Before using the ST8904 for a specific gas, confirm:
Expected combustible gas
Calibration basis
Sensor suitability
Required correction factor, if applicable
Project or site requirements
Do not assume the detector responds equally to every combustible gas.
Is 0% LEL Always Safe?
Not necessarily.
A 0% LEL reading means the detector is not showing a measurable response on its combustible-gas channel at that moment.
It does not prove that the atmosphere is free from:
Toxic gas
Oxygen deficiency
A gas the sensor cannot detect
Combustible gas below the detector’s response level
Gas located elsewhere in the space
Vapour that does not produce the expected sensor response
Always check all relevant gas channels and follow the complete risk assessment.
Why Can Oxygen Affect LEL Detection?
Some combustible-gas sensing methods require sufficient oxygen to operate correctly.
In a severely oxygen-deficient atmosphere, the combustible-gas response may not behave as expected.
Therefore, the oxygen and LEL readings should not be considered separately when assessing a confined space.
A specialised detector may be required for applications involving inert atmospheres or very low oxygen.
What Can Damage or Reduce the LEL Sensor Response?
Possible causes include:
Silicone vapours
Strong solvents
Corrosive chemicals
Oil mist
Excessive gas exposure
Water or condensation
Blocked sensor openings
Sensor ageing
Incorrect calibration
Inappropriate test gas
Some contaminants can inhibit or poison the combustible-gas sensor, causing reduced sensitivity.
The detector may still switch on and display 0% LEL even when the sensor does not respond correctly. This is why bump testing is important.
Why Does the LEL Reading Increase in a Manhole?
A manhole or sewer can accumulate combustible gas because of:
Organic decomposition
Methane generation
Fuel or chemical discharge
Leakage from connected pipelines
Limited ventilation
Gas migration from another chamber
The gas concentration may also differ between the top, middle and bottom of the space.
Testing only near the opening may not represent the entire manhole.
Why Does the LEL Reading Increase in a Factory?
Possible industrial causes include:
Fuel-gas leakage
Solvent vapour
Tank or pipeline leakage
Incomplete purging
Chemical spills
Poor ventilation
Process-gas release
Maintenance work that opens a contained system
Stop work and follow the site’s emergency procedure when the detector activates an alarm.
Do not continue searching for the source unless the equipment, training and work procedure allow it.
ST8904 vs Combustible-Gas Leak Detector
The ST8904 and a probe-type leak detector serve different purposes.
Smart Sensor ST8904
Monitors the general atmosphere
Displays combustible gas as %LEL
Also measures O₂, CO and H₂S
Provides personal safety alarms
Suitable for multi-hazard monitoring
Combustible-gas leak detector
Helps locate leaks around joints, pipes and valves
Often uses an extended or flexible probe
May provide relative concentration indication
Usually focuses on one gas category
Use the ST8904 to help protect personnel from a hazardous atmosphere. Use a suitable leak detector when the objective is locating a leakage point.
What Should You Do When the LEL Alarm Activates?
Follow the organisation’s emergency procedure, which may include:
Stop the work.
Avoid introducing an ignition source.
Leave the affected area.
Warn nearby personnel.
Report the alarm to the responsible supervisor.
Investigate only from a safe location.
Ventilate where the approved procedure allows.
Retest before returning.
Never silence the alarm and continue working simply because no gas can be smelled.
Why Is Bump Testing Important?
A bump test exposes the LEL sensor to an appropriate test gas to confirm:
Sensor response
Display response
Audible alarm
Warning light
Vibration alarm
A detector showing 0% LEL in fresh air has not proven that the sensor will respond to combustible gas.
If the detector fails a bump test, it should not be relied upon for safety-critical monitoring.
Smart Sensor ST8904 LEL Measuring Range
The ST8904 combustible-gas channel measures:
0–100% LEL
Its complete standard gas combination is:
O₂: 0–30% VOL
CO: 0–999 ppm
H₂S: 0–500 ppm
Combustible gas: 0–100% LEL
This combination is commonly considered for confined-space, wastewater, manhole and general industrial-maintenance applications.
Need Help Selecting a Combustible-Gas Detector?
MTM Precision supplies the Smart Sensor ST8904 four-in-one gas detector and other gas-detection options in Malaysia.
Before requesting a quotation, provide:
Expected combustible gas
Work application
Personal monitoring or leak detection
Required measuring range
Diffusion or pump requirement
Required certification
Quantity
Calibration or documentation requirements
This helps determine whether the ST8904, a probe-type leak detector or another multi-gas instrument is the appropriate option.
Contact MTM Precision
MTM Precision Sdn. Bhd.
Office: +603-8080 7172
Desmond: +6019-220 7346
Fifi Ng: +6016-660 7346
WhatsApp: +6019-220 7346
Email: enquiry@mtmpre.com.my
Showroom & Service Centre
No. 29-1 & 29-2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia.
Serving customers throughout Selangor, Kuala Lumpur, Johor, Penang, Perak, Melaka, Negeri Sembilan, Pahang, Kedah, Perlis, Terengganu, Sabah and Sarawak.
16 Sep 2026