How to Measure Magnetic Fields Around Transformers and Electrical Rooms with TENMARS TM-290 Malaysia

How to Measure Magnetic Fields Around Transformers and Electrical Rooms with TENMARS TM-290 Malaysia

 

Transformers, electrical panels, distribution equipment and power cables can produce low-frequency electromagnetic fields during operation.

 

For facility maintenance teams, electrical contractors and industrial users, a common question is:

 

How can we perform a basic magnetic-field check around an electrical room or transformer area?

 

The TENMARS TM-290 Multi-Field EMF Meter provides 50/60 Hz three-axis magnetic-field measurement, making it suitable for general investigation around mains-frequency electrical installations.

 

Why Measure Magnetic Fields Around Electrical Equipment?

 

Magnetic-field measurements can be useful when investigating how field levels vary around:

 

Transformers

 

Main switchboards

 

Distribution boards

 

Electrical panels

 

Busbar systems

 

Power cables

 

UPS systems

 

Motors

 

Generators

 

Other electrical equipment

 

The purpose should be clearly defined before measurements begin.

 

A general field survey, equipment comparison and formal occupational exposure assessment are different tasks and may require different procedures.

 

TENMARS TM-290 Magnetic-Field Measurement

 

The TM-290 measures low-frequency magnetic fields at:

 

50/60 Hz

 

Available ranges include:

 

20 / 200 / 2000 mG

 

or:

 

2 / 20 / 200 uT

 

The instrument also provides:

 

X, Y and Z three-axis magnetic-field measurement

 

This is particularly useful for general investigation because magnetic fields have direction.

 

Why 50/60 Hz Matters

 

Electrical power systems operate at mains frequency.

 

In Malaysia, the mains electricity frequency is 50 Hz.

 

Therefore, a meter designed for low-frequency 50/60 Hz magnetic-field measurement is relevant when investigating many common mains-powered electrical installations.

 

This measurement should not be confused with RF measurement in MHz or GHz.

 

Step 1: Identify the Equipment

 

Before measuring, identify the electrical equipment being investigated.

 

For example:

 

Transformer T1

 

Main Switchboard MSB-1

 

Distribution Board DB-2

 

UPS Room A

 

Avoid simply recording:

 

Electrical Room

 

A specific equipment reference makes future comparison easier.

 

Step 2: Establish Measurement Points

 

Do not take only one reading.

 

Create several measurement points around the equipment.

 

For example:

 

Point A: Near equipment

 

Point B: 0.5 m away

 

Point C: 1 m away

 

Point D: 2 m away

 

Point E: Normal working position

 

This can help show how the measured field varies with location.

 

Step 3: Keep the Measurement Height Consistent

 

If you want to compare several locations, try to maintain a consistent measurement height.

 

For example, do not measure one point near floor level and another point at chest height unless the survey specifically requires this.

 

Record the measurement position whenever it is important.

 

Consistency improves the usefulness of repeated measurements.

 

Step 4: Record the Distance

 

Distance can significantly affect the reading around electrical equipment.

 

Instead of recording:

 

Transformer: 12 uT

 

record:

 

Equipment: Transformer T1

 

Distance: 1 m

 

Measurement: Magnetic Field

 

Reading: 12 uT

 

This provides much better context.

 

Step 5: Record the Equipment Operating Condition

 

Electrical equipment may operate under different load conditions.

 

When possible, record whether the equipment is:

 

Operating normally

 

Under load

 

Lightly loaded

 

Idle

 

Switched off

 

If measurements are repeated in the future, try to compare readings under similar operating conditions.

 

Why Does the Magnetic-Field Reading Change Around a Transformer?

 

A changing reading does not automatically indicate an instrument problem.

 

The field can vary according to:

 

Distance

 

Position

 

Direction

 

Electrical load

 

Nearby conductors

 

Nearby electrical equipment

 

Measurement height

 

Moving only a short distance may produce a different reading, especially close to electrical equipment.

 

Why 3-Axis Measurement Is Useful

 

Magnetic fields have direction.

 

A single-axis meter measures the component along one sensing direction, so rotating the instrument may change the displayed reading.

 

The TM-290 measures:

 

X Axis

 

Y Axis

 

Z Axis

 

and can provide an aggregated magnetic-field result.

 

This makes general magnetic-field investigation more convenient when the field direction is not known in advance.

 

Example: Transformer Measurement

 

A simple transformer-area survey could use the following locations:

 

T1-A: Front, 0.5 m

 

T1-B: Front, 1 m

 

T1-C: Front, 2 m

 

T1-D: Side, 1 m

 

T1-E: Normal technician working position

 

Record the magnetic-field reading at each point.

 

If the survey is repeated later, use the same locations where practical.

 

This creates a useful comparison rather than a collection of random readings.

 

Example: Electrical Room Survey

 

An electrical room may contain several sources.

 

Possible measurement locations include:

 

Main Switchboard

 

Measure at selected distances and normal working positions.

 

Distribution Panels

 

Record readings individually rather than combining all panels under one location.

 

UPS Equipment

 

Check defined positions around the equipment.

 

Cable Routes

 

Measurements may also be taken at relevant positions near major power cable routes.

 

Normal Working Area

 

Include positions where technicians normally stand or perform maintenance.

 

Do Not Measure Only at the Highest Point

 

Walking around an electrical room searching only for the largest displayed number may not provide a repeatable survey.

 

A better approach is to define measurement locations before recording results.

 

For example:

 

Location 1: Main Switchboard - Front

 

Location 2: Main Switchboard - 1 m

 

Location 3: UPS - Front

 

Location 4: Technician Working Position

 

Location 5: Electrical Room Entrance

 

This allows future measurements to be compared with the same positions.

 

Magnetic Field vs Electric Field

 

The TM-290 can also measure 50/60 Hz electric fields.

 

However, magnetic-field and electric-field measurements are different.

 

Magnetic-field readings may be displayed in:

 

mG

 

or:

 

uT

 

Electric-field readings are displayed in:

 

V/m

 

Do not directly compare a uT reading with a V/m reading as though they represent the same parameter.

 

What About RF Inside an Electrical Room?

 

The TM-290 also includes RF measurement from:

 

50 MHz to 10 GHz

 

However, this is a separate measurement function.

 

If wireless or communication equipment is present, the RF function may be used where the source frequency falls within the specified range.

 

Do not confuse the RF reading with the 50/60 Hz magnetic-field measurement from electrical power equipment.

 

Can Magnetic-Field Measurement Detect a Faulty Transformer?

 

A magnetic-field reading by itself should not be used to diagnose whether a transformer is faulty.

 

Transformer condition assessment may require other inspection methods depending on the equipment and application.

 

These may include:

 

Electrical testing

 

Thermal inspection

 

Insulation testing

 

Oil analysis

 

Vibration monitoring

 

Other condition-monitoring methods

 

The TM-290 should be used according to its intended EMF measurement function.

 

Simple Electrical Room EMF Record

 

A basic record may look like this:

 

Date: __________

 

Equipment: Transformer T1

 

Location: Front

 

Distance: 1 m

 

Measurement Mode: Magnetic Field

 

Reading: __________ uT

 

Equipment Condition: Normal Operation

 

Remarks: __________

 

For repeated surveys, using the same format makes comparison easier.

 

Basic Survey vs Occupational Exposure Assessment

 

A basic magnetic-field survey does not automatically constitute a formal occupational exposure assessment.

 

Formal assessment may require:

 

Applicable exposure limits

 

Defined measurement procedures

 

Appropriate instrument selection

 

Calibration requirements

 

Measurement uncertainty

 

Exposure duration

 

Formal documentation

 

Where regulatory or occupational compliance is required, follow the applicable standard and measurement procedure.

 

TENMARS TM-290 for Electrical Room and Transformer EMF Measurement Malaysia

 

The TENMARS TM-290 provides:

 

Magnetic Field Frequency: 50/60 Hz

 

Magnetic Ranges: 20 / 200 / 2000 mG or 2 / 20 / 200 uT

 

Magnetic Measurement: X/Y/Z three-axis

 

Electric Field: 50/60 Hz

 

RF Field: 50 MHz to 10 GHz

 

This makes the TM-290 useful for general EMF investigation around transformers, electrical panels, UPS systems, electrical rooms and other mixed electrical environments.

 

For TENMARS TM-290 quotation, stock availability or technical enquiries in Malaysia, contact:

 

MTM Precision Sdn Bhd

 

Puchong Showroom & Service Centre

 

Tel: 03-8080 7172

 

WhatsApp: +6016-660 7346

 

Email: mtmpre@yahoo.com

 

Website: www.mtmpre.com.my

 

Serving customers throughout Malaysia, including Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.


 

20 Sep 2026