How to Measure Magnetic Fields Around Transformers and Electrical Rooms with TENMARS TM-290 Malaysia
How to Measure Magnetic Fields Around Transformers and Electrical Rooms with TENMARS TM-290 Malaysia
Transformers, electrical panels, distribution equipment and power cables can produce low-frequency electromagnetic fields during operation.
For facility maintenance teams, electrical contractors and industrial users, a common question is:
How can we perform a basic magnetic-field check around an electrical room or transformer area?
The TENMARS TM-290 Multi-Field EMF Meter provides 50/60 Hz three-axis magnetic-field measurement, making it suitable for general investigation around mains-frequency electrical installations.
Why Measure Magnetic Fields Around Electrical Equipment?
Magnetic-field measurements can be useful when investigating how field levels vary around:
Transformers
Main switchboards
Distribution boards
Electrical panels
Busbar systems
Power cables
UPS systems
Motors
Generators
Other electrical equipment
The purpose should be clearly defined before measurements begin.
A general field survey, equipment comparison and formal occupational exposure assessment are different tasks and may require different procedures.
TENMARS TM-290 Magnetic-Field Measurement
The TM-290 measures low-frequency magnetic fields at:
50/60 Hz
Available ranges include:
or:
2 / 20 / 200 uT
The instrument also provides:
X, Y and Z three-axis magnetic-field measurement
This is particularly useful for general investigation because magnetic fields have direction.
Why 50/60 Hz Matters
Electrical power systems operate at mains frequency.
In Malaysia, the mains electricity frequency is 50 Hz.
Therefore, a meter designed for low-frequency 50/60 Hz magnetic-field measurement is relevant when investigating many common mains-powered electrical installations.
This measurement should not be confused with RF measurement in MHz or GHz.
Step 1: Identify the Equipment
Before measuring, identify the electrical equipment being investigated.
For example:
Transformer T1
Main Switchboard MSB-1
Distribution Board DB-2
UPS Room A
Avoid simply recording:
Electrical Room
A specific equipment reference makes future comparison easier.
Step 2: Establish Measurement Points
Do not take only one reading.
Create several measurement points around the equipment.
For example:
Point A: Near equipment
Point B: 0.5 m away
Point C: 1 m away
Point D: 2 m away
Point E: Normal working position
This can help show how the measured field varies with location.
Step 3: Keep the Measurement Height Consistent
If you want to compare several locations, try to maintain a consistent measurement height.
For example, do not measure one point near floor level and another point at chest height unless the survey specifically requires this.
Record the measurement position whenever it is important.
Consistency improves the usefulness of repeated measurements.
Step 4: Record the Distance
Distance can significantly affect the reading around electrical equipment.
Instead of recording:
Transformer: 12 uT
record:
Equipment: Transformer T1
Distance: 1 m
Measurement: Magnetic Field
Reading: 12 uT
This provides much better context.
Step 5: Record the Equipment Operating Condition
Electrical equipment may operate under different load conditions.
When possible, record whether the equipment is:
Operating normally
Under load
Lightly loaded
Idle
Switched off
If measurements are repeated in the future, try to compare readings under similar operating conditions.
Why Does the Magnetic-Field Reading Change Around a Transformer?
A changing reading does not automatically indicate an instrument problem.
The field can vary according to:
Distance
Position
Direction
Electrical load
Nearby conductors
Nearby electrical equipment
Measurement height
Moving only a short distance may produce a different reading, especially close to electrical equipment.
Why 3-Axis Measurement Is Useful
Magnetic fields have direction.
A single-axis meter measures the component along one sensing direction, so rotating the instrument may change the displayed reading.
The TM-290 measures:
X Axis
Y Axis
Z Axis
and can provide an aggregated magnetic-field result.
This makes general magnetic-field investigation more convenient when the field direction is not known in advance.
Example: Transformer Measurement
A simple transformer-area survey could use the following locations:
T1-A: Front, 0.5 m
T1-B: Front, 1 m
T1-C: Front, 2 m
T1-D: Side, 1 m
T1-E: Normal technician working position
Record the magnetic-field reading at each point.
If the survey is repeated later, use the same locations where practical.
This creates a useful comparison rather than a collection of random readings.
Example: Electrical Room Survey
An electrical room may contain several sources.
Possible measurement locations include:
Main Switchboard
Measure at selected distances and normal working positions.
Distribution Panels
Record readings individually rather than combining all panels under one location.
UPS Equipment
Check defined positions around the equipment.
Cable Routes
Measurements may also be taken at relevant positions near major power cable routes.
Normal Working Area
Include positions where technicians normally stand or perform maintenance.
Do Not Measure Only at the Highest Point
Walking around an electrical room searching only for the largest displayed number may not provide a repeatable survey.
A better approach is to define measurement locations before recording results.
For example:
Location 1: Main Switchboard - Front
Location 2: Main Switchboard - 1 m
Location 3: UPS - Front
Location 4: Technician Working Position
Location 5: Electrical Room Entrance
This allows future measurements to be compared with the same positions.
Magnetic Field vs Electric Field
The TM-290 can also measure 50/60 Hz electric fields.
However, magnetic-field and electric-field measurements are different.
Magnetic-field readings may be displayed in:
mG
or:
uT
Electric-field readings are displayed in:
V/m
Do not directly compare a uT reading with a V/m reading as though they represent the same parameter.
What About RF Inside an Electrical Room?
The TM-290 also includes RF measurement from:
50 MHz to 10 GHz
However, this is a separate measurement function.
If wireless or communication equipment is present, the RF function may be used where the source frequency falls within the specified range.
Do not confuse the RF reading with the 50/60 Hz magnetic-field measurement from electrical power equipment.
Can Magnetic-Field Measurement Detect a Faulty Transformer?
A magnetic-field reading by itself should not be used to diagnose whether a transformer is faulty.
Transformer condition assessment may require other inspection methods depending on the equipment and application.
These may include:
Electrical testing
Thermal inspection
Insulation testing
Oil analysis
Vibration monitoring
Other condition-monitoring methods
The TM-290 should be used according to its intended EMF measurement function.
Simple Electrical Room EMF Record
A basic record may look like this:
Date: __________
Equipment: Transformer T1
Location: Front
Distance: 1 m
Measurement Mode: Magnetic Field
Reading: __________ uT
Equipment Condition: Normal Operation
Remarks: __________
For repeated surveys, using the same format makes comparison easier.
Basic Survey vs Occupational Exposure Assessment
A basic magnetic-field survey does not automatically constitute a formal occupational exposure assessment.
Formal assessment may require:
Applicable exposure limits
Defined measurement procedures
Appropriate instrument selection
Calibration requirements
Measurement uncertainty
Exposure duration
Formal documentation
Where regulatory or occupational compliance is required, follow the applicable standard and measurement procedure.
TENMARS TM-290 for Electrical Room and Transformer EMF Measurement Malaysia
The TENMARS TM-290 provides:
Magnetic Field Frequency: 50/60 Hz
Magnetic Ranges: 20 / 200 / 2000 mG or 2 / 20 / 200 uT
Magnetic Measurement: X/Y/Z three-axis
Electric Field: 50/60 Hz
RF Field: 50 MHz to 10 GHz
This makes the TM-290 useful for general EMF investigation around transformers, electrical panels, UPS systems, electrical rooms and other mixed electrical environments.
For TENMARS TM-290 quotation, stock availability or technical enquiries in Malaysia, contact:
MTM Precision Sdn Bhd
Puchong Showroom & Service Centre
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
Serving customers throughout Malaysia, including Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.
20 Sep 2026