How to Check HVAC Airflow Before and After Coil Cleaning Malaysia

How to Check HVAC Airflow Before and After Coil Cleaning Malaysia

 

Cleaning an HVAC coil is a common maintenance task, but how do you know whether airflow actually changed after the work?

 

Visual inspection alone may not provide the answer.

 

A practical approach is to measure air velocity or airflow before and after coil cleaning under comparable operating conditions.

 

A digital anemometer such as the TASI TA642C High Accuracy Digital Anemometer can help HVAC technicians and facility maintenance teams record these measurements and create a more objective maintenance record.

 

Why Can a Dirty Coil Affect Airflow?

 

Air needs to pass through the HVAC system before reaching the supply duct and room outlets.

 

When contamination accumulates on system components, airflow performance may be affected.

 

However, low airflow should not automatically be blamed on the coil.

 

Other possible factors include:

 

Dirty filters

 

Fan condition

 

Fan speed

 

Damper position

 

Duct restrictions

 

Blocked grilles

 

Return air restrictions

 

System controls

 

This is why measurement before and after maintenance is useful.

 

Measure Before Cleaning

 

Whenever practical, take measurements before carrying out the maintenance.

 

This creates a baseline.

 

Possible measurement locations include:

 

Supply air duct

 

Main supply outlet

 

Selected room outlets

 

AHU discharge

 

FCU outlet

 

Other repeatable ventilation points

 

Record the measurement location clearly so the same point can be checked again later.

 

Keep the HVAC Operating Condition Consistent

 

A before-and-after comparison is only useful if the operating conditions are reasonably similar.

 

For example, avoid:

 

Before cleaning: Low fan speed

 

After cleaning: High fan speed

 

A higher reading after cleaning could simply be caused by the different fan setting.

 

Where possible, maintain consistent:

 

Fan speed

 

Operating mode

 

Damper position

 

Measurement location

 

Probe orientation

 

Measurement method

 

Measure Air Velocity

 

Air velocity can be useful for quick comparison.

 

For example:

 

Before coil cleaning: Lower average air velocity

 

After coil cleaning: Higher average air velocity

 

If the measurement method and operating conditions are consistent, this can provide useful evidence that the airflow condition changed.

 

However, do not draw conclusions from one isolated reading.

 

Take More Than One Reading

 

Airflow is often uneven.

 

At an outlet, the centre may have a different velocity from the edges.

 

Inside a duct, velocity can also vary across the cross-section.

 

Taking several readings can provide a more representative picture than measuring only one point.

 

For more formal airflow testing, use the measurement procedure required by the project or organisation.

 

When Should You Use CFM?

 

Air velocity tells you how fast the air is moving at a measurement point.

 

If you want to evaluate airflow volume, you may need to consider the measurement area.

 

The basic relationship is:

 

Airflow = Air Velocity × Area

 

Depending on the reporting requirement, airflow may be expressed in:

 

CFM

 

CMM

 

CMS

 

The TASI TA642C supports airflow measurement functions suitable for this type of HVAC application.

 

Example: FCU Before and After Cleaning

 

Imagine an FCU serving an office.

 

Before servicing, occupants report weak airflow.

 

The technician measures selected supply outlets and records the results.

 

The FCU is then serviced and the coil is cleaned.

 

After servicing, the technician returns to the same outlets and repeats the measurements under comparable operating conditions.

 

If airflow improves, the technician now has measurement data supporting the observation.

 

If airflow remains low, further troubleshooting may be required.

 

What If Airflow Does Not Improve?

 

This is important.

 

Coil cleaning does not guarantee that every airflow problem will disappear.

 

If measurements remain low, investigate other possible causes.

 

Check the Filter

 

A restricted or unsuitable filter can affect airflow.

 

Check the Fan

 

Confirm that the fan is operating as required.

 

Check Dampers

 

A partially closed damper may restrict airflow.

 

Inspect Ductwork

 

Look for restrictions, damaged flexible ducts or other installation issues.

 

Check Return Air

 

Poor return airflow may also affect system performance.

 

The measurement helps show that further investigation is necessary.

 

What If Airflow Becomes Worse?

 

If airflow is unexpectedly lower after maintenance, do not immediately assume the instrument is wrong.

 

First verify:

 

Same measurement location?

 

Same fan speed?

 

Same operating mode?

 

Same probe orientation?

 

Same damper condition?

 

Same measurement units?

 

Then check whether anything changed during servicing.

 

A consistent measurement procedure is essential for meaningful comparison.

 

Use the Same Measurement Point

 

For preventive maintenance, it can be useful to define permanent or repeatable measurement points.

 

For example:

 

FCU-05 – Supply Outlet 1 – Centre

 

or

 

AHU-02 – Main Supply Duct – Measurement Point A

 

Future technicians can then return to approximately the same location.

 

This makes historical comparisons much more useful.

 

Record the Maintenance Activity

 

Do not record only the airflow number.

 

A better maintenance record may include:

 

Equipment: FCU-05

Location: Office Level 2

Date: Inspection date

Condition: Before cleaning

Air Velocity / Airflow: Recorded value

Maintenance: Coil cleaning

After Maintenance: New measurement

Remarks: Technician observations

 

This creates a more complete service history.

 

Why Data Storage Can Be Useful

 

When multiple AHUs, FCUs or outlets need to be checked, manual recording can become inconvenient.

 

The TA642C provides measurement storage capability that can support users who need to collect multiple readings.

 

USB/PC connectivity can also be useful when measurement data needs to be reviewed or organised later.

 

Useful for Preventive Maintenance

 

Airflow measurements should not only be taken after a complaint.

 

Facility teams can establish baseline readings when the HVAC system is operating normally.

 

Later measurements can then be compared against these baseline conditions.

 

This can help identify gradual changes in:

 

AHU performance

 

FCU airflow

 

Exhaust ventilation

 

Fresh air systems

 

Supply air distribution

 

A trend may provide an early indication that further maintenance is required.

 

Coil Cleaning and Energy Efficiency

 

A clean HVAC system is generally desirable for proper system operation, but an anemometer alone cannot determine total HVAC energy efficiency.

 

Airflow measurement is one part of the maintenance picture.

 

Other factors such as temperatures, pressures, electrical consumption, equipment condition and control strategy may also need to be considered.

 

Suitable Applications

 

Before-and-after airflow testing can be useful for:

 

AHU servicing

 

FCU maintenance

 

Commercial air-conditioning

 

Office HVAC systems

 

Shopping centres

 

Hotels

 

Factories

 

Hospitals

 

Schools

 

Data centres

 

Facility management

 

It can also help service contractors provide customers with more objective maintenance documentation.

 

From “Already Cleaned” to Measured Results

 

A service report that simply says:

 

“Coil cleaned.”

 

confirms that work was performed.

 

A report containing before-and-after measurements provides additional information about the system condition.

 

This does not replace professional HVAC diagnosis, but it makes maintenance records more informative.

 

TASI TA642C for HVAC Preventive Maintenance Malaysia

 

The TASI TA642C High Accuracy Digital Anemometer can support HVAC contractors and facility maintenance teams who want to measure air velocity and airflow before and after servicing.

 

By using consistent measurement points and operating conditions, technicians can build more meaningful maintenance records and identify systems that may require further investigation.

 

For product availability and technical enquiries:

 

MTM Precision Sdn Bhd

Showroom & Service Centre: Puchong, Selangor, Malaysia

 

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com

Website: www.mtmpre.com.my

 

Contact MTM Precision for more information about the TASI TA642C Digital Anemometer for HVAC servicing, coil cleaning airflow checks and preventive maintenance in Malaysia.


 

26 Sep 2026