How to Check HVAC Airflow Before and After Coil Cleaning Malaysia
How to Check HVAC Airflow Before and After Coil Cleaning Malaysia
Cleaning an HVAC coil is a common maintenance task, but how do you know whether airflow actually changed after the work?
Visual inspection alone may not provide the answer.
A practical approach is to measure air velocity or airflow before and after coil cleaning under comparable operating conditions.
A digital anemometer such as the TASI TA642C High Accuracy Digital Anemometer can help HVAC technicians and facility maintenance teams record these measurements and create a more objective maintenance record.
Why Can a Dirty Coil Affect Airflow?
Air needs to pass through the HVAC system before reaching the supply duct and room outlets.
When contamination accumulates on system components, airflow performance may be affected.
However, low airflow should not automatically be blamed on the coil.
Other possible factors include:
Dirty filters
Fan condition
Fan speed
Damper position
Duct restrictions
Blocked grilles
Return air restrictions
System controls
This is why measurement before and after maintenance is useful.
Measure Before Cleaning
Whenever practical, take measurements before carrying out the maintenance.
This creates a baseline.
Possible measurement locations include:
Supply air duct
Main supply outlet
Selected room outlets
AHU discharge
FCU outlet
Other repeatable ventilation points
Record the measurement location clearly so the same point can be checked again later.
Keep the HVAC Operating Condition Consistent
A before-and-after comparison is only useful if the operating conditions are reasonably similar.
For example, avoid:
Before cleaning: Low fan speed
After cleaning: High fan speed
A higher reading after cleaning could simply be caused by the different fan setting.
Where possible, maintain consistent:
Fan speed
Operating mode
Damper position
Measurement location
Probe orientation
Measurement method
Measure Air Velocity
Air velocity can be useful for quick comparison.
For example:
Before coil cleaning: Lower average air velocity
After coil cleaning: Higher average air velocity
If the measurement method and operating conditions are consistent, this can provide useful evidence that the airflow condition changed.
However, do not draw conclusions from one isolated reading.
Take More Than One Reading
Airflow is often uneven.
At an outlet, the centre may have a different velocity from the edges.
Inside a duct, velocity can also vary across the cross-section.
Taking several readings can provide a more representative picture than measuring only one point.
For more formal airflow testing, use the measurement procedure required by the project or organisation.
When Should You Use CFM?
Air velocity tells you how fast the air is moving at a measurement point.
If you want to evaluate airflow volume, you may need to consider the measurement area.
The basic relationship is:
Airflow = Air Velocity × Area
Depending on the reporting requirement, airflow may be expressed in:
CFM
CMM
CMS
The TASI TA642C supports airflow measurement functions suitable for this type of HVAC application.
Example: FCU Before and After Cleaning
Imagine an FCU serving an office.
Before servicing, occupants report weak airflow.
The technician measures selected supply outlets and records the results.
The FCU is then serviced and the coil is cleaned.
After servicing, the technician returns to the same outlets and repeats the measurements under comparable operating conditions.
If airflow improves, the technician now has measurement data supporting the observation.
If airflow remains low, further troubleshooting may be required.
What If Airflow Does Not Improve?
This is important.
Coil cleaning does not guarantee that every airflow problem will disappear.
If measurements remain low, investigate other possible causes.
Check the Filter
A restricted or unsuitable filter can affect airflow.
Check the Fan
Confirm that the fan is operating as required.
Check Dampers
A partially closed damper may restrict airflow.
Inspect Ductwork
Look for restrictions, damaged flexible ducts or other installation issues.
Check Return Air
Poor return airflow may also affect system performance.
The measurement helps show that further investigation is necessary.
What If Airflow Becomes Worse?
If airflow is unexpectedly lower after maintenance, do not immediately assume the instrument is wrong.
First verify:
Same measurement location?
Same fan speed?
Same operating mode?
Same probe orientation?
Same damper condition?
Same measurement units?
Then check whether anything changed during servicing.
A consistent measurement procedure is essential for meaningful comparison.
Use the Same Measurement Point
For preventive maintenance, it can be useful to define permanent or repeatable measurement points.
For example:
FCU-05 – Supply Outlet 1 – Centre
or
AHU-02 – Main Supply Duct – Measurement Point A
Future technicians can then return to approximately the same location.
This makes historical comparisons much more useful.
Record the Maintenance Activity
Do not record only the airflow number.
A better maintenance record may include:
Equipment: FCU-05
Location: Office Level 2
Date: Inspection date
Condition: Before cleaning
Air Velocity / Airflow: Recorded value
Maintenance: Coil cleaning
After Maintenance: New measurement
Remarks: Technician observations
This creates a more complete service history.
Why Data Storage Can Be Useful
When multiple AHUs, FCUs or outlets need to be checked, manual recording can become inconvenient.
The TA642C provides measurement storage capability that can support users who need to collect multiple readings.
USB/PC connectivity can also be useful when measurement data needs to be reviewed or organised later.
Useful for Preventive Maintenance
Airflow measurements should not only be taken after a complaint.
Facility teams can establish baseline readings when the HVAC system is operating normally.
Later measurements can then be compared against these baseline conditions.
This can help identify gradual changes in:
AHU performance
FCU airflow
Exhaust ventilation
Fresh air systems
Supply air distribution
A trend may provide an early indication that further maintenance is required.
Coil Cleaning and Energy Efficiency
A clean HVAC system is generally desirable for proper system operation, but an anemometer alone cannot determine total HVAC energy efficiency.
Airflow measurement is one part of the maintenance picture.
Other factors such as temperatures, pressures, electrical consumption, equipment condition and control strategy may also need to be considered.
Suitable Applications
Before-and-after airflow testing can be useful for:
AHU servicing
FCU maintenance
Commercial air-conditioning
Office HVAC systems
Shopping centres
Hotels
Factories
Hospitals
Schools
Data centres
Facility management
It can also help service contractors provide customers with more objective maintenance documentation.
From “Already Cleaned” to Measured Results
A service report that simply says:
“Coil cleaned.”
confirms that work was performed.
A report containing before-and-after measurements provides additional information about the system condition.
This does not replace professional HVAC diagnosis, but it makes maintenance records more informative.
TASI TA642C for HVAC Preventive Maintenance Malaysia
The TASI TA642C High Accuracy Digital Anemometer can support HVAC contractors and facility maintenance teams who want to measure air velocity and airflow before and after servicing.
By using consistent measurement points and operating conditions, technicians can build more meaningful maintenance records and identify systems that may require further investigation.
For product availability and technical enquiries:
MTM Precision Sdn Bhd
Showroom & Service Centre: Puchong, Selangor, Malaysia
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
Contact MTM Precision for more information about the TASI TA642C Digital Anemometer for HVAC servicing, coil cleaning airflow checks and preventive maintenance in Malaysia.
26 Sep 2026