4-20 mA Signal Problems - How to Troubleshoot with FNIRSI SG-003A Malaysia
4-20 mA Signal Problems - How to Troubleshoot with FNIRSI SG-003A Malaysia
A 4-20 mA signal problem can cause incorrect readings, unstable values or complete loss of measurement in an industrial control system.
When this happens, the transmitter is often blamed first.
However, the actual problem may be somewhere else in the loop.
Possible causes include field wiring, loop power, loose terminals, incorrect PLC configuration, analog input problems or incorrect scaling.
The FNIRSI SG-003A Signal Generator can help technicians troubleshoot suitable 4-20 mA systems by providing a known electrical signal and checking how the receiving equipment responds.
For factory maintenance, instrumentation and automation teams in Malaysia, this can make troubleshooting more systematic.
What Is a 4-20 mA Signal?
The 4-20 mA current loop is commonly used to transmit process measurements in industrial systems.
Typical measurements include:
Pressure
Temperature
Flow
Level
Humidity
Position
Process variables
A typical system may look like:
Sensor > Transmitter > 4-20 mA > PLC/DCS > HMI
The transmitter converts the measured process value into an electrical current.
The PLC then converts that current back into an engineering value.
Why 4 mA and 20 mA?
In a standard linear 4-20 mA measurement range:
4 mA = 0%
8 mA = 25%
12 mA = 50%
16 mA = 75%
20 mA = 100%
For example, consider a pressure transmitter configured for:
0-10 bar = 4-20 mA
The expected relationship would be:
4 mA = 0 bar
8 mA = 2.5 bar
12 mA = 5 bar
16 mA = 7.5 bar
20 mA = 10 bar
If the PLC does not display the expected value, further troubleshooting is required.
Problem 1: PLC Shows 0 Even Though the Process Is Running
Suppose a flow transmitter is installed on an operating process, but the PLC displays zero.
Possible causes may include:
No transmitter power
Open circuit
Broken signal wire
Loose terminal
Incorrect PLC input channel
Wrong analog input configuration
Transmitter problem
Before replacing the transmitter, technicians should check the signal path systematically.
A known test signal can help determine whether the receiving side is working.
Problem 2: PLC Reading Is Too High or Too Low
Another common problem is that the PLC displays a value, but the value is clearly incorrect.
For example:
Actual pressure appears to be approximately 5 bar.
The HMI displays 8 bar.
Possible causes include:
Incorrect transmitter range
Incorrect PLC scaling
Wrong engineering-unit configuration
Transmitter output problem
Signal wiring problem
Applying known signals to the appropriate PLC input can help determine whether the PLC scaling is correct.
Problem 3: Reading Is Unstable
A process reading that continuously moves up and down may indicate several possible issues.
These may include:
Loose wiring
Poor terminal connection
Electrical interference
Power-supply problems
Transmitter problems
Actual process fluctuations
A signal generator can help separate the control-system side from the field side.
If the PLC displays a stable value when receiving a stable known signal, the technician can investigate the transmitter, wiring and process conditions more closely.
Problem 4: 4 mA Does Not Show 0%
Suppose the system is configured for:
4-20 mA = 0-100%
You apply 4 mA, but the HMI displays 10%.
This may indicate a scaling or configuration problem.
Check:
PLC analog input range
Raw input scaling
Engineering-unit conversion
HMI scaling
Configured lower range
The lower endpoint should be checked together with other points across the range.
Problem 5: 20 mA Does Not Show 100%
The same principle applies at the upper end.
If:
20 mA should represent 100%
but the HMI displays only 80%, possible causes may include incorrect scaling or configuration.
Do not check only one point.
A useful functional test may include:
4 mA
8 mA
12 mA
16 mA
20 mA
This helps show whether the error exists across the entire range or only at certain points.
Problem 6: 12 mA Does Not Show 50%
The midpoint is particularly useful when checking linear scaling.
For:
4-20 mA = 0-100%
the expected midpoint is:
12 mA = 50%
If 4 mA and 20 mA appear correct but 12 mA gives an unexpected result, the PLC programming or scaling logic should be investigated carefully.
How Can the FNIRSI SG-003A Help?
The FNIRSI SG-003A provides a known test signal for suitable industrial troubleshooting applications.
Instead of relying entirely on the signal produced by the existing transmitter, technicians can introduce a known value and observe the system response.
For example:
Generate 4 mA > Check PLC reading
Generate 8 mA > Check PLC reading
Generate 12 mA > Check PLC reading
Generate 16 mA > Check PLC reading
Generate 20 mA > Check PLC reading
If the PLC responds correctly, attention can move towards the field side.
If the PLC responds incorrectly, the technician can investigate the receiving side.
How to Separate a Transmitter Problem from a PLC Problem
Consider this system:
Pressure Transmitter > 4-20 mA > PLC > HMI
The HMI reading is incorrect.
A technician needs to determine which section is causing the problem.
If the PLC correctly interprets known test signals, investigate:
Transmitter
Field wiring
Loop power
Connections
Transmitter configuration
If the PLC incorrectly interprets known signals, investigate:
PLC analog input
Input configuration
PLC scaling
HMI configuration
This approach can reduce unnecessary replacement of working equipment.
Example: 0-100掳C Temperature Transmitter
Suppose a temperature transmitter is configured for:
0-100掳C = 4-20 mA
Expected values are:
4 mA = 0掳C
8 mA = 25掳C
12 mA = 50掳C
16 mA = 75掳C
20 mA = 100掳C
If the SG-003A generates 12 mA and the PLC displays approximately 50掳C, the scaling is responding correctly at the midpoint.
If the PLC displays 75掳C, the configuration should be investigated.
Example: 0-16 Bar Pressure Transmitter
For a pressure transmitter configured as:
0-16 bar = 4-20 mA
the expected relationship is:
4 mA = 0 bar
8 mA = 4 bar
12 mA = 8 bar
16 mA = 12 bar
20 mA = 16 bar
Known signals make it easier to compare the expected result with the actual PLC display.
What If the Current Is Below 4 mA?
A current below the expected operating range may indicate a fault condition, wiring issue or transmitter-related problem depending on the equipment and system configuration.
Do not automatically assume that every value below 4 mA has the same meaning.
Check the transmitter manual, PLC configuration and system design before interpreting an abnormal current.
What If the Current Is Above 20 mA?
Similarly, a current above the normal measurement range may indicate an over-range condition, fault behaviour or another system-specific condition.
Different transmitters and control systems may handle these conditions differently.
Always refer to the manufacturer's specifications.
Multimeter or Signal Generator?
Both instruments can be useful during 4-20 mA troubleshooting.
A multimeter helps technicians measure what the existing circuit is producing.
A signal generator provides a known test signal to check how another device responds.
A practical troubleshooting process may therefore involve:
Measure the existing signal
Compare it with the expected value
Generate a known signal where appropriate
Check the PLC response
Narrow down the problem
The two instruments complement each other.
Important Before Injecting a 4-20 mA Signal
Do not connect a signal generator to an industrial control loop without first understanding the circuit.
Before testing:
Check the wiring diagram
Identify the correct terminals
Confirm the PLC input type
Confirm polarity
Understand the loop power arrangement
Check the permitted input range
Determine what equipment may respond to the simulated signal
Follow site safety and isolation procedures
A simulated process signal may cause pumps, valves, alarms or other equipment to respond.
This is especially important in operating plants.
Troubleshooting Is Not the Same as Calibration
The FNIRSI SG-003A can be useful for signal troubleshooting, functional checking and suitable commissioning work.
Formal calibration may require additional requirements for:
Accuracy
Traceability
Measurement uncertainty
Reference equipment
Calibration procedures
Documentation
Choose the test equipment according to the actual purpose of the job.
Looking for a 4-20 mA Signal Generator in Malaysia?
MTM Precision Sdn Bhd supplies the FNIRSI SG-003A Signal Generator in Malaysia for PLC troubleshooting, industrial automation, process instrumentation and factory maintenance applications.
If you have a 4-20 mA signal problem and are unsure whether the SG-003A is suitable, send us a photo of your transmitter, PLC analog input, equipment nameplate or wiring diagram through WhatsApp.
We can help evaluate the application before you purchase.
MTM Precision Sdn Bhd
Showroom & Service Centre
No 29-1 & 2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
Serving customers across Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.
04 Oct 2026