How to Check Server Room Temperature and Humidity with TASI TA622C Malaysia
Server rooms and data centres depend on controlled environmental conditions to support reliable IT equipment operation.
However, checking only the temperature shown on a wall-mounted air-conditioning controller may not tell you what is actually happening around the server racks.
Temperature and humidity can vary between:
Rack inlet and exhaust
Upper and lower rack positions
Hot aisle and cold aisle
Areas near cooling outlets
Different parts of the server room
For portable environmental inspection, the TASI TA622C Digital Thermo-Hygrometer can be used to measure temperature and relative humidity at specific locations while also providing dew point and wet bulb temperature.
Its separate probe is particularly useful when technicians need to investigate conditions around individual server racks.
Why Measure Server Room Temperature at the Rack?
A room thermostat measures conditions only at or around its sensor location.
The environmental conditions experienced by IT equipment may be different.
For example, a room may appear to have an acceptable average temperature while one particular rack receives warmer inlet air.
This can happen because of:
Airflow distribution
Equipment load
Rack arrangement
Cooling layout
Obstructions
Local recirculation
Hot and cold air mixing
Portable measurements can help identify these local differences.
Why Measure Humidity in a Server Room?
Temperature is only one part of the environmental condition.
Relative humidity is also relevant.
The TA622C provides:
Relative Humidity Range:
0 to 100%RH
with specified accuracy of:
±3%RH within 10–90%RH
It also measures temperature from:
-40°C to 80°C
with specified temperature accuracy of:
±0.5°C.
For professional facility management, temperature and RH should be considered together rather than relying only on one parameter.
Step 1: Start with General Room Conditions
Begin by measuring temperature and humidity in a representative area of the server room.
Avoid positioning the sensor:
Directly against your body
Directly in front of your face
Against equipment
Against a wall
Allow the probe to stabilise before recording the measurement.
This gives you a baseline for comparison.
Step 2: Measure the Rack Inlet
The rack inlet is particularly important because this is where cooling air enters the IT equipment.
Depending on the rack design, technicians may take measurements at several heights, such as:
Lower rack
Middle rack
Upper rack
This can reveal whether the cooling conditions are consistent throughout the rack.
Why Measure at Different Rack Heights?
Warm air tends to rise, but actual server room airflow is influenced by cooling system design and equipment operation.
Conditions at the top of a rack may therefore differ from conditions at the bottom.
Measuring only one location could miss a local hot area.
The TA622C's separate probe makes multi-height measurements easier.
Step 3: Measure the Rack Exhaust
Next, compare conditions around the rack exhaust.
The exhaust air is expected to be warmer after passing through operating IT equipment.
The objective is not simply to find a high temperature.
The comparison can help technicians understand how heat is being transferred through the rack and whether hot exhaust air may be recirculating toward equipment inlets.
Step 4: Compare Hot Aisle and Cold Aisle
Where a server room uses hot-aisle/cold-aisle arrangements, portable measurements can be taken in both areas.
Useful comparisons include:
Cold aisle temperature
Cold aisle RH
Hot aisle temperature
Hot aisle RH
Rack inlet temperature
Rack exhaust temperature
These measurements can help facility personnel understand local environmental differences.
What Is a Hot Aisle?
In a typical arrangement, the hot aisle is the area receiving heated exhaust air from server equipment.
Temperatures here may naturally be higher than at rack inlets.
A high hot-aisle temperature does not automatically indicate a fault.
The more important question is whether hot air is reaching areas where cooling air should be supplied.
What Is a Cold Aisle?
The cold aisle is generally the area where cooler supply air is available to server equipment inlets.
Portable measurement can help identify whether:
One area is warmer than another
Upper rack positions receive warmer air
Cooling is distributed unevenly
The correct environmental limits should follow the facility's design and applicable equipment or industry requirements.
Step 5: Check Near Cooling Outlets
Measure conditions around relevant cooling outlets.
However, remember that a reading directly at the outlet represents the outlet environment, not necessarily the server inlet environment.
This is why measurements should be taken at several locations.
Step 6: Check for Hot Air Recirculation
Hot air discharged from equipment can sometimes return toward the inlet side.
Possible signs include:
Higher inlet temperature at upper rack positions
One rack consistently warmer than adjacent racks
Significant temperature differences between measurement points
Portable measurements can help identify these patterns for further investigation.
Why Is the TA622C Separate Probe Useful in Server Rooms?
The TASI TA622C uses a separate temperature and humidity probe.
This allows technicians to position the sensor near:
Rack inlet
Rack exhaust
Upper rack
Lower rack
Cooling outlet
Network cabinet
while keeping the meter display accessible.
This can be more convenient than positioning the complete instrument at each measurement point.
Dew Point in Server Rooms
The TA622C also provides dew point temperature.
Dew point is useful because it provides information about the moisture content of the air and condensation conditions.
Condensation around electrical and electronic equipment is undesirable.
If a cold surface falls below the surrounding air's dew point, condensation may become possible.
Does Dew Point Mean Condensation Is Happening?
Not automatically.
Dew point indicates the temperature at which condensation can begin under the existing environmental conditions.
To assess a specific surface, technicians may also need to know its actual temperature.
An appropriate surface temperature instrument may therefore be required for a complete condensation investigation.
Wet Bulb Temperature
The TA622C also provides wet bulb temperature.
Wet bulb information is particularly relevant to HVAC and environmental assessment.
For server room facility teams working with cooling systems, having temperature, RH, dew point and wet bulb available in one instrument can provide additional troubleshooting information.
Use MAX / MIN / AVG
Server room conditions may fluctuate.
The TA622C provides:
MAX
MIN
AVG
These functions can help technicians see the highest, lowest and average measurements observed during an inspection period.
This can be more informative than relying only on the current display.
Use Data Recording for Intermittent Problems
Some server room problems may occur only during:
Peak equipment load
Afternoon periods
HVAC cycling
Maintenance periods
Cooling system changes
A technician visiting during normal conditions may not see the problem.
The TASI TA622C provides data recording capability and supports USB PC communication.
This can help users investigate environmental changes over a measurement period.
Handheld Meter vs Permanent Server Room Monitoring
The TA622C is primarily a portable professional inspection instrument.
It should not be confused with a permanent network-connected environmental monitoring system.
For critical server rooms or data centres, permanent monitoring may be appropriate for:
24/7 monitoring
Remote alarms
Historical trends
Multiple fixed sensors
Centralised monitoring
The TA622C can complement such a system by helping technicians investigate individual locations.
Example: Permanent Sensor Shows High Temperature
Suppose a permanent environmental sensor sends a high-temperature alarm.
The alarm tells the facility team that there may be a problem.
But it may not explain:
Which rack is affected
Whether the problem is at the inlet or exhaust
Whether the upper rack is hotter
Whether hot air is recirculating
Whether adjacent racks have the same condition
A portable TA622C can then be used to investigate the area point by point.
Example: One Server Rack Is Running Hot
A practical investigation may include:
Rack A Lower Inlet
Temperature + RH
Rack A Middle Inlet
Temperature + RH
Rack A Upper Inlet
Temperature + RH
Then repeat the same measurements at adjacent racks.
This can reveal whether the problem is specific to one rack or part of a wider cooling distribution issue.
Example: Server Room Feels Cold but RH Is High
A low room temperature does not automatically mean moisture conditions are ideal.
Because relative humidity depends on temperature, a colder room can still show relatively high RH.
Check:
Temperature
RH
Dew point
together.
This provides a more useful environmental picture.
Common Server Room Measurement Mistakes
Avoid these common mistakes:
Measuring only at the wall thermostat
Checking only room temperature
Ignoring humidity
Measuring only one rack
Ignoring different rack heights
Holding the probe too close to your body
Reading before the sensor stabilises
Assuming a cooling outlet reading represents the rack inlet
Confusing portable inspection with permanent monitoring
A systematic measurement approach provides more useful information.
Practical Server Room Inspection Checklist
For a basic portable environmental survey:
Measure general room temperature and RH.
Measure rack inlet temperature and RH.
Check lower, middle and upper rack positions.
Compare rack exhaust.
Compare hot and cold aisles where applicable.
Check relevant cooling outlets.
Compare adjacent racks.
Review dew point where moisture or condensation is a concern.
Use MAX / MIN / AVG for fluctuating conditions.
Use data recording if the problem is intermittent.
Record the location together with every measurement.
What Temperature Should a Server Room Be?
There is no single number that should automatically be applied to every server room.
Suitable environmental conditions depend on factors such as:
IT equipment requirements
Facility design
Cooling system
Applicable standards or guidelines
Internal operating procedures
Users should follow the environmental requirements applicable to their equipment and facility.
The measurement instrument provides the data; the acceptable limits should come from the relevant technical requirements.
Can TA622C Replace a Data Centre Monitoring System?
No.
For facilities requiring continuous monitoring, alarms and remote access, a permanent monitoring solution should be considered.
The TA622C is better positioned as a portable troubleshooting and verification instrument.
The two approaches can work together.
Frequently Asked Questions
Can TASI TA622C measure server room temperature?
Yes. It is suitable for portable environmental temperature measurement.
Can TA622C measure server room humidity?
Yes. It measures relative humidity from 0 to 100%RH.
Can TA622C measure at different server rack heights?
Yes. Its separate probe makes it practical to check different measurement locations and heights.
Does TA622C measure dew point?
Yes.
Why is dew point useful in a server room?
It provides information about air moisture conditions and can support condensation-risk investigations.
Does TA622C provide wet bulb temperature?
Yes.
Can TA622C record server room conditions?
Yes. It provides data recording capability and USB PC communication.
Can TA622C send remote alarms?
It should be considered a portable professional meter rather than a permanent network-connected remote monitoring system.
Looking for a Server Room Temperature Humidity Meter in Malaysia?
MTM Precision supplies professional server room temperature humidity meters, thermo-hygrometers, data loggers and environmental monitoring instruments in Malaysia.
The TASI TA622C Digital Thermo-Hygrometer is suitable for portable inspection around server racks, hot aisles, cold aisles, cooling outlets and other specific measurement locations.
For facilities requiring continuous monitoring, MTM Precision can also help users identify the appropriate type of environmental monitoring solution according to the application.
Contact MTM Precision
MTM Precision Sdn Bhd
No. 29-1 & 29-2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia.
Website: www.mtmpre.com.my
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
26 Aug 2026