How to Measure Motor Inrush Current with TASI TA813B+ Clamp Meter Malaysia
How to Measure Motor Inrush Current with TASI TA813B+ Clamp Meter Malaysia
When an electric motor starts, it can draw a much higher current than during normal operation. This temporary surge is known as inrush current or starting current.
For maintenance technicians troubleshooting motors, pumps, compressors and HVAC equipment, measuring only the normal running current may not reveal what is happening during startup.
The TASI TA813B+ True RMS Digital Clamp Meter includes an Inrush Current measurement function, making it useful for investigating motor startup conditions in industrial and commercial applications.
What Is Motor Inrush Current?
When a motor is first energized, the rotor is stationary.
During this short startup period, the motor can draw substantially more current than its normal operating current. Once the motor accelerates toward its operating speed, the current normally decreases.
The basic sequence is:
Motor OFF → Motor Starts → High Inrush Current → Motor Accelerates → Normal Running Current
This behaviour is normal to a certain extent.
However, unusually high or prolonged starting current can be associated with electrical or mechanical problems that require further investigation.
Why Measure Inrush Current?
Consider a common factory maintenance complaint:
“The motor runs normally after starting, but sometimes the breaker trips when we switch it on.”
If a technician checks only the running current, the reading may appear normal.
The important event may have occurred during the first moments of startup.
Measuring inrush current gives technicians another piece of information when investigating issues such as:
Breaker trips during startup
Motor difficult to start
Compressor startup problems
Generator struggling when equipment starts
Excessive voltage drop during startup
Pump startup problems
HVAC compressor problems
Unexpected protection-device operation
Where Can TASI TA813B+ Be Used?
Typical equipment includes:
Electric motors
Water pumps
Air compressors
HVAC compressors
Blower motors
Exhaust fans
Cooling tower equipment
Industrial machinery
Production equipment
Building services equipment
This makes inrush measurement particularly relevant to factory maintenance, HVAC maintenance and electrical troubleshooting.
How to Measure Motor Inrush Current with TA813B+
Before measurement, technicians should understand the equipment, electrical system and applicable electrical safety requirements.
The general measurement concept is:
1. Identify the Correct Conductor
The clamp should be placed around the appropriate single current-carrying conductor.
Do not simply clamp around an entire multi-core cable containing both outgoing and returning conductors, as opposing magnetic fields can affect the measurement.
2. Select the Appropriate Current Measurement
Set the TA813B+ to the appropriate current measurement mode for the circuit being tested.
Confirm that the expected measurement is within the instrument's specified range.
3. Select Inrush Measurement
Use the meter's Inrush function before starting the equipment.
This allows the meter to capture the startup-current event rather than showing only the subsequent running current.
4. Start the Motor or Equipment
Start the equipment under its normal operating conditions.
The clamp meter captures the inrush event.
5. Record the Inrush Reading
Record the measured value for comparison with equipment information, previous measurements or other equivalent equipment.
6. Measure Normal Running Current
After the equipment reaches stable operation, check the normal operating current.
You now have two useful measurements:
Starting Current → Running Current
Both can help build a better picture of the equipment's electrical behaviour.
Example: Pump Motor Troubleshooting
Imagine a factory pump that occasionally trips its protective device during startup.
A technician measures the normal operating current and finds no obvious abnormality.
Instead of stopping there, the technician can investigate:
Power Supply → Protection → Motor Starter / Drive → Motor → Pump Load
Inrush-current measurement can help establish whether an unusually high startup-current event is occurring.
The result should not be interpreted alone. The technician may also need to investigate factors such as supply voltage, protection settings, motor condition and mechanical load.
Example: Air Compressor Startup
Compressors can place a substantial load on a motor during startup.
If an air compressor becomes difficult to start, possible areas requiring investigation can include:
Supply voltage
Starting current
Motor condition
Starting components
Protection devices
Mechanical loading
Compressor condition
Using the TA813B+ Inrush function provides a measured starting-current value that can be included in the troubleshooting process.
Inrush Current vs Running Current
These two measurements answer different questions.
Running Current
Shows the current consumed while the equipment is operating under relatively stable conditions.
Inrush Current
Captures the high-current event associated with startup.
A motor can therefore show an acceptable running current while still experiencing a startup-related problem.
This is why both measurements can be useful.
Build a Maintenance Record
Inrush measurement becomes even more useful when readings are recorded over time.
For example:
EquipmentInrush CurrentRunning CurrentDatePump Motor 1Record ReadingRecord ReadingInspection DatePump Motor 2Record ReadingRecord ReadingInspection DateCompressor 1Record ReadingRecord ReadingInspection Date
Rather than relying only on a single measurement, maintenance teams can compare readings against previous results and similar equipment.
A change in electrical behaviour can then be investigated together with other maintenance information.
Why True RMS Matters in Industrial Maintenance
Modern industrial electrical systems do not always produce ideal sinusoidal waveforms.
Factories increasingly use equipment such as:
Variable Frequency Drives
Electronic motor controls
Switching power supplies
Automation systems
Modern HVAC controls
The TA813B+ is a True RMS clamp meter, making it suitable for measurements in many modern electrical environments where waveform characteristics can differ from a simple sine wave.
Inrush Measurement Does Not Diagnose the Fault by Itself
An important point is that a high inrush reading does not automatically tell you which component has failed.
It is a diagnostic measurement.
Technicians should interpret the result together with other information such as:
Voltage + Current + Equipment Specification + Protection Setting + Mechanical Condition + Maintenance History
For example, a startup problem could involve the electrical supply, motor, driven load or another component in the system.
TA813B+ for Factory Preventive Maintenance
The TA813B+ can be used for more than emergency troubleshooting.
Maintenance teams can incorporate current measurements into routine inspections of important equipment such as:
Pumps → Fans → Motors → Compressors → HVAC → Production Machinery
Recording baseline measurements when equipment is operating normally gives technicians useful reference data for future troubleshooting.
TASI TA813B+ Clamp Meter Supplier Malaysia
For enquiries about the TASI TA813B+ True RMS Digital Clamp Meter for motor, compressor, HVAC and industrial electrical maintenance applications, contact:
MTM Precision Sdn Bhd
Showroom & Service Centre
No 29-1 & 2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia.
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
Supporting industrial and electrical customers across Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.
26 Sep 2026