How to Check AHU Filter Pressure Drop with UNI-T UT366A Malaysia
A dirty air filter can reduce airflow, increase fan workload and affect the performance of an air-conditioning system. Instead of replacing filters based only on appearance or a fixed schedule, HVAC technicians can measure the pressure drop across the filter using the UNI-T UT366A Digital Manometer.
What Is Filter Pressure Drop?
Air pressure is normally higher before the filter and lower after the air passes through it. The difference between these two pressure points is known as the filter pressure drop or differential pressure.
As dust accumulates inside the filter, airflow resistance increases. A higher pressure difference may indicate that the filter is becoming restricted.
However, the measured value must always be compared with:
-
The filter manufacturer’s recommended limit
-
The AHU operating specification
-
The system’s normal baseline reading
-
The current fan speed and airflow condition
There is no single pressure-drop limit that applies to every filter or HVAC system.
Why Use the UNI-T UT366A?
The UT366A is designed to measure both gauge pressure and differential pressure. It has separate P1 and P2 pressure ports, allowing technicians to compare pressure on both sides of an AHU filter.
Useful features include:
-
Pressure range up to ±15.00 kPa
-
Accuracy of ±0.5% full scale at 25°C
-
Independent P1 and P2 measurements
-
Differential-pressure measurement
-
MAX, MIN, AVG and HOLD functions
-
Positive and negative pressure LED indicators
-
Multiple pressure units, including Pa-related units, kPa, mbar, mmHβO and inHβO
-
Backlit display for plant-room inspections
-
Magnetic hook for convenient positioning
How to Connect the UT366A
Before starting, identify the pressure-test points located before and after the filter.
Connect the hoses as follows:
-
Connect one UT366A pressure port to the upstream side, before the filter.
-
Connect the other pressure port to the downstream side, after the filter.
-
Ensure both hoses are secure and not folded, blocked or leaking.
-
Place the instrument in a stable position using the magnetic hook if suitable.
-
Switch on the HVAC system and allow it to operate under its normal condition.
-
Select the required pressure unit.
-
Observe and record the differential-pressure reading.
If the reading shows the opposite direction from what is expected, check whether the two hoses have been connected to the correct ports.
What Does a High Reading Mean?
A higher-than-normal differential-pressure reading can indicate:
-
A dirty or clogged filter
-
An incorrect filter grade
-
A filter that is too restrictive for the system
-
Obstruction inside the air path
-
Incorrectly installed filter media
-
Reduced effective filter area
-
A change in fan operating conditions
Do not conclude that the filter is dirty from one reading alone. Compare the result with an earlier baseline or the filter manufacturer’s recommended final pressure drop.
What Does a Low Reading Mean?
A very low pressure-drop reading does not always mean the filter is clean.
Possible causes include:
-
The filter is missing
-
The filter is damaged
-
Air is bypassing the filter frame
-
The fan is operating at a lower speed
-
Airflow is lower than normal
-
The pressure hose is leaking
-
The test point is blocked
-
The pressure connections are incorrect
Technicians should inspect both the filter condition and the complete airflow system before making a replacement decision.
Establish a Baseline Reading
After installing a new filter, record the initial differential pressure while the AHU is operating normally. This becomes the clean-filter baseline.
During scheduled maintenance, repeat the measurement under similar operating conditions. Comparing new readings with the baseline provides more useful information than relying only on visual inspection.
A simple maintenance record can include:
-
Inspection date
-
AHU identification
-
Filter type
-
Fan operating condition
-
Pressure-drop reading
-
Filter condition
-
Action taken
This creates a practical history for maintenance planning.
Common Measurement Mistakes
Pressure-drop readings may be unreliable when:
-
A hose is loose or leaking
-
The hose is kinked
-
The wrong pressure ports are used
-
The instrument is not zeroed correctly
-
The fan speed changes between inspections
-
Doors or access panels are left open
-
Pressure points are placed in turbulent airflow
-
Readings are compared using different pressure units
For consistent results, use the same test points, operating condition and pressure unit for every inspection.
Suitable Applications in Malaysia
The UNI-T UT366A can support filter inspection and HVAC maintenance in:
-
Commercial buildings
-
Factories
-
Hospitals
-
Laboratories
-
Shopping centres
-
Hotels
-
Data centres
-
Cleanrooms
-
Office buildings
-
Industrial ventilation systems
It is suitable for HVAC contractors, facility-management teams and maintenance departments working in Selangor, Kuala Lumpur and throughout Malaysia.
Enquire About the UNI-T UT366A
For assistance selecting a digital manometer for AHU filter pressure-drop measurement, duct-pressure checking or HVAC maintenance, contact MTM Precision with details of your application.
MTM Precision Sdn Bhd
Showroom & Service Centre:
No. 29-1 & 29-2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
30 Sep 2026