How to Perform a 4-20 mA Loop Check with FNIRSI SG-003A Malaysia

How to Perform a 4-20 mA Loop Check with FNIRSI SG-003A Malaysia

 

A 4-20 mA loop check is an important part of industrial instrumentation, commissioning and troubleshooting.

 

The objective is not simply to see whether there is current in the wire.

 

A proper functional loop check helps confirm that a signal can travel through the expected control-system path and produce the correct response.

 

For example:

 

Transmitter > Field Wiring > PLC > HMI

 

For suitable applications, the FNIRSI SG-003A Signal Generator can provide known test signals to help technicians check how the receiving side of a 4-20 mA loop responds.

 

For instrumentation technicians, automation engineers, system integrators and factory maintenance teams in Malaysia, this can be useful during commissioning and troubleshooting.

 

What Is a 4-20 mA Loop?

 

A 4-20 mA current loop is commonly used to transmit industrial process measurements.

 

Examples include:

 

Pressure

 

Temperature

 

Flow

 

Level

 

Position

 

Other process variables

 

A typical linear relationship is:

 

4 mA = 0%

 

8 mA = 25%

 

12 mA = 50%

 

16 mA = 75%

 

20 mA = 100%

 

The actual engineering values depend on the transmitter configuration.

 

Example: Pressure Loop

 

Suppose a pressure transmitter is configured as:

 

0-10 bar = 4-20 mA

 

The expected values are:

 

4 mA = 0 bar

 

8 mA = 2.5 bar

 

12 mA = 5 bar

 

16 mA = 7.5 bar

 

20 mA = 10 bar

 

During a functional loop check, the technician can determine whether known signals produce the expected values at the PLC and HMI.

 

Why Perform a Loop Check?

 

A system may be wired completely but still contain problems.

 

Examples include:

 

Wrong field cable

 

Wrong PLC channel

 

Reversed polarity

 

Incorrect terminal

 

Wrong PLC scaling

 

Incorrect HMI tag

 

Incorrect engineering range

 

Configuration errors

 

A loop check helps identify these problems before normal operation.

 

When Should You Perform a Loop Check?

 

Loop checks may be useful during:

 

New control-panel installation

 

PLC commissioning

 

New transmitter installation

 

Factory expansion

 

Control-system modification

 

Shutdown maintenance

 

Transmitter replacement

 

Troubleshooting

 

They may also form part of FAT or SAT activities depending on the project procedure.

 

Step 1: Understand the Loop

 

Before connecting test equipment, understand the complete signal path.

 

For example:

 

Pressure Transmitter > Junction Box > Control Panel > PLC AI03 > PLC Program > HMI Pressure Tag

 

Write down or verify each stage.

 

This is important because the purpose of a loop check is to confirm that the correct signal reaches the correct destination.

 

Step 2: Confirm the Signal Type

 

Do not assume every analog loop is 4-20 mA.

 

Check the instrument and PLC specifications.

 

The system may use:

 

4-20 mA

 

0-20 mA

 

0-10 V

 

or another signal type.

 

Confirm the exact signal before connecting the SG-003A or other test equipment.

 

Step 3: Confirm the Engineering Range

 

Suppose the transmitter is labelled:

 

0-16 bar = 4-20 mA

 

Then your expected values are:

 

4 mA = 0 bar

 

8 mA = 4 bar

 

12 mA = 8 bar

 

16 mA = 12 bar

 

20 mA = 16 bar

 

If the PLC is accidentally configured for 0-10 bar, the loop may electrically work while the displayed value remains incorrect.

 

Step 4: Identify the Correct PLC Channel

 

Confirm which analog input channel receives the signal.

 

For example:

 

AI01 - Flow

 

AI02 - Level

 

AI03 - Pressure

 

AI04 - Temperature

 

If you test AI03 but the HMI value associated with AI04 changes, there may be a channel assignment or tag problem.

 

This is exactly the type of issue that loop checking can reveal.

 

Step 5: Place the System in a Safe Test Condition

 

This step is critical.

 

A simulated analog signal can affect control logic.

 

Changing a signal may cause:

 

Pump startup

 

Motor operation

 

Valve movement

 

Alarm activation

 

Interlock activation

 

Automatic sequence changes

 

Shutdown functions

 

Before injecting any test signal, follow the site's approved isolation and commissioning procedure.

 

Step 6: Apply the Lower Test Point

 

For a standard 4-20 mA system, a useful starting point is:

 

4 mA

 

For a 0-100% range, the expected result is:

 

0%

 

For a 0-10 bar pressure range:

 

0 bar

 

Check the PLC and HMI.

 

Record the result if required by the commissioning procedure.

 

Step 7: Apply the Midpoint

 

Next, apply:

 

12 mA

 

For a standard linear 0-100% range:

 

12 mA = 50%

 

For:

 

0-10 bar

 

the expected value is:

 

5 bar

 

This midpoint is particularly useful because it can reveal scaling problems that are not obvious at the lower endpoint.

 

Step 8: Apply the Upper Test Point

 

Next, check:

 

20 mA

 

For a 0-100% range:

 

20 mA = 100%

 

For:

 

0-10 bar

 

the expected result is:

 

10 bar

 

If the HMI instead displays 16 bar, investigate the configured engineering range.

 

Should You Check 5 Points?

 

For troubleshooting and commissioning, additional test points can provide more information.

 

A common functional sequence is:

 

4 mA = 0%

 

8 mA = 25%

 

12 mA = 50%

 

16 mA = 75%

 

20 mA = 100%

 

This helps verify that the system responds across the range rather than only at the endpoints.

 

The exact number of test points should follow your project or maintenance procedure.

 

Example: Level Transmitter Loop Check

 

Suppose a tank level transmitter is configured as:

 

0-5 m = 4-20 mA

 

Expected results are:

 

4 mA = 0 m

 

8 mA = 1.25 m

 

12 mA = 2.5 m

 

16 mA = 3.75 m

 

20 mA = 5 m

 

If all values display correctly, the receiving side is responding as expected to the known signals.

 

If the HMI shows:

 

4 mA = 0 m

 

12 mA = 5 m

 

20 mA = 10 m

 

the PLC or HMI may be configured for the wrong range.

 

Example: Wrong HMI Tag

 

Imagine you are checking a pressure loop.

 

You apply a changing test signal to the expected pressure input.

 

But instead of the pressure display changing, the HMI flow reading changes.

 

This may indicate:

 

Incorrect PLC tag

 

Incorrect HMI tag

 

Wrong field cable

 

Wrong analog input channel

 

The electrical signal may be working perfectly.

 

The problem is that it is connected or mapped to the wrong place.

 

Example: PLC Raw Value Changes but HMI Does Not

 

During the loop check, the PLC programming software shows the raw analog value changing correctly.

 

However, the HMI remains fixed.

 

This suggests the issue may be downstream of the physical analog input.

 

Check:

 

PLC scaling

 

HMI tag

 

Communication

 

Display configuration

 

Program logic

 

This is why it is useful to observe both the PLC and HMI during a loop check.

 

Example: Nothing Changes

 

Suppose you apply appropriate known signals but the PLC raw value does not change.

 

Investigate:

 

Correct terminals

 

Correct channel

 

Input configuration

 

Current vs voltage mode

 

Wiring

 

Loop arrangement

 

PLC analog input module

 

Do not immediately conclude that the PLC module is damaged.

 

Check the configuration and connections first.

 

Loop Check vs Transmitter Calibration

 

These are not necessarily the same task.

 

A functional loop check asks:

 

Does the control system respond correctly to a known signal?

 

Transmitter calibration asks questions such as:

 

Does the transmitter accurately convert the physical process input into the expected output?

 

For example, fully calibrating a pressure transmitter may require an appropriate pressure reference and pressure source.

 

Generating 12 mA alone does not prove that a pressure transmitter correctly measures 5 bar.

 

The SG-003A should therefore not be treated as a replacement for every physical calibration instrument.

 

Loop Check vs PLC Analog Input Calibration

 

Similarly, observing that a PLC displays approximately 50% when a test signal is applied is useful for functional troubleshooting.

 

Formal calibration may require:

 

Specified accuracy

 

Traceable reference equipment

 

Known uncertainty

 

Documented procedures

 

Recorded results

 

Calibration certificates

 

The required equipment depends on the purpose of the test.

 

Why the FNIRSI SG-003A Is Useful for Loop Troubleshooting

 

For suitable applications, the FNIRSI SG-003A gives technicians a controlled test condition.

 

Instead of relying entirely on the process transmitter, technicians can introduce a known supported signal and observe the receiving system.

 

This can help isolate problems involving:

 

PLC inputs

 

Scaling

 

HMI displays

 

Channel assignments

 

Control-panel wiring

 

Automation configuration

 

A Practical Troubleshooting Sequence

 

When a 4-20 mA loop is not working correctly, a systematic sequence is better than replacing components randomly.

 

Check:

 

1. What is the expected signal?

 

2. What is the transmitter range?

 

3. Is the transmitter powered correctly?

 

4. Is the wiring correct?

 

5. What signal is actually present?

 

6. Is the PLC configured for the correct input type?

 

7. Does the PLC respond to a known signal?

 

8. Is the scaling correct?

 

9. Does the HMI display the PLC value correctly?

 

This approach can significantly reduce troubleshooting time.

 

Applications in Malaysian Industry

 

4-20 mA loops are used across many industrial environments.

 

Potential applications include:

 

Manufacturing plants

 

Water and wastewater systems

 

Pump systems

 

HVAC plants

 

Boilers and chillers

 

Chemical processes

 

Food and beverage production

 

Building services

 

Process plants

 

Factory automation

 

For maintenance teams working with these systems, signal simulation can be a useful troubleshooting capability.

 

Important Safety Reminder

 

Before performing a loop check:

 

Review the wiring diagram

 

Confirm the correct signal type

 

Check the input terminals

 

Check polarity

 

Understand the loop power arrangement

 

Verify the allowed signal range

 

Identify any automatic control actions

 

Follow site isolation and safety procedures

 

Never inject a signal into an operating control system without understanding what the PLC may do with that signal.

 

Looking for FNIRSI SG-003A for 4-20 mA Loop Checking in Malaysia?

 

MTM Precision Sdn Bhd supplies the FNIRSI SG-003A Signal Generator in Malaysia for 4-20 mA troubleshooting, PLC testing, control-panel commissioning and industrial automation applications.

 

If you need to perform a 4-20 mA loop check and are unsure whether the SG-003A is suitable, send us a photo of your transmitter, PLC analog input module, wiring terminals or loop diagram through WhatsApp.

 

We can help evaluate your application before you purchase.

 

MTM Precision Sdn Bhd

 

Showroom & Service Centre

No 29-1 & 2, Jalan Bandar 18,

Pusat Bandar Puchong,

47160 Puchong, Selangor, Malaysia

 

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com

Website: www.mtmpre.com.my

 

Serving customers across Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.


 

04 Oct 2026