4-20 mA Endpoints Correct but Midpoint Reading Is Wrong - Troubleshooting Malaysia
4-20 mA Endpoints Correct but Midpoint Reading Is Wrong - Troubleshooting Malaysia
Your 4-20 mA system appears correct at both ends.
At 4 mA, the PLC displays the correct minimum value.
At 20 mA, the PLC displays the correct maximum value.
But at 12 mA, the midpoint is wrong.
What does this mean?
Many technicians check only 4 mA and 20 mA during troubleshooting. However, correct endpoints do not always prove that every part of the signal chain is behaving as expected.
Testing intermediate points such as 8 mA, 12 mA and 16 mA can reveal problems involving PLC scaling, custom calculations, signal linearization, HMI processing or control logic.
For suitable applications, the FNIRSI SG-003A Signal Generator can provide known test signals to help technicians investigate these problems.
What Should a Linear 4-20 mA Signal Look Like?
For a standard linear 0-100% relationship:
4 mA = 0%
8 mA = 25%
12 mA = 50%
16 mA = 75%
20 mA = 100%
This relationship is important.
If the system is intended to be linear, a 12 mA input should represent the midpoint of the configured engineering range.
Example: 0-10 Bar Pressure Range
Suppose:
4-20 mA = 0-10 bar
Expected values are:
4 mA = 0 bar
8 mA = 2.5 bar
12 mA = 5 bar
16 mA = 7.5 bar
20 mA = 10 bar
Now imagine the PLC displays:
4 mA = 0 bar
8 mA = 1.8 bar
12 mA = 4.0 bar
16 mA = 7.0 bar
20 mA = 10 bar
Both endpoints are correct.
But the intermediate values are not following the expected linear relationship.
This tells you that more investigation is required.
Why Endpoint Testing Alone Can Miss Problems
If you test only:
4 mA
and
20 mA
you are checking only two points.
A calculation can still produce the correct values at both endpoints while producing incorrect values between them.
This is particularly important when the PLC program contains:
Custom calculations
Lookup tables
Linearization
Piecewise scaling
Correction factors
Special process logic
Intermediate testing gives a clearer picture of system behaviour.
Problem 1: Incorrect PLC Scaling Formula
A PLC programmer may use a custom mathematical formula to convert the analog input into engineering units.
If that formula contains an error, the endpoints may sometimes appear correct while intermediate values are wrong.
Check:
Raw analog value
Scaling formula
Constants
Offsets
Multiplication factors
Division factors
Do not assume that the scaling block is correct simply because 4 mA and 20 mA look right.
Problem 2: Non-Linear Processing in the PLC
Not every process signal is intended to be displayed linearly.
The PLC may intentionally apply:
Square-root extraction
Lookup tables
Curve correction
Tank-volume calculations
Sensor linearization
Custom engineering formulas
If so, 12 mA may not necessarily correspond to 50% of the final displayed variable.
Before diagnosing a fault, understand what the PLC program is supposed to calculate.
Example: Tank Level vs Tank Volume
This is an important example.
Imagine a transmitter measures liquid level.
The transmitter output may be linear with level:
4 mA = 0% level
12 mA = 50% level
20 mA = 100% level
But the HMI displays tank volume, not level.
If the tank shape is non-linear, 50% liquid height may not equal exactly 50% of total volume.
Therefore:
12 mA = 50% level
does not automatically mean:
12 mA = 50% volume
Always identify what the HMI is actually displaying.
Problem 3: HMI Applies Additional Processing
The PLC value may be correct while the HMI modifies it.
Possible HMI functions include:
Additional scaling
Unit conversion
Offset
Multiplication
Decimal adjustment
Custom expression
Compare the PLC engineering value directly with the HMI value.
If the PLC shows the correct midpoint but the HMI does not, the problem is probably downstream of the analog input.
Problem 4: Wrong Raw Input Conversion
PLC manufacturers may represent analog signals using different raw numerical ranges.
The program must correctly convert the module's raw value into engineering units.
If the programmer assumes the wrong raw range, scaling can be incorrect.
Check the documentation for the exact PLC analog input module.
Do not copy a scaling formula from a different PLC model without confirming that the raw input representation is the same.
Problem 5: Old Correction Values Remain in the Program
Sometimes maintenance teams add correction factors to compensate for a previous sensor or process condition.
Later, the transmitter is replaced but the old correction remains in the PLC.
For example:
Displayed Value = Scaled Value + Correction
or
Displayed Value = Scaled Value x Correction Factor
This may cause unexpected readings.
Review the PLC logic if the electrical input appears correct.
Problem 6: Transmitter and PLC Use Different Engineering Ranges
Consider a transmitter configured as:
0-16 bar = 4-20 mA
while the PLC program assumes:
0-10 bar = 4-20 mA
Normally this will also affect the upper endpoint.
However, additional software limits or clamping may make the problem less obvious.
For example, the HMI may be programmed not to display above 10 bar.
Always compare the actual transmitter configuration with the PLC engineering range.
Why 12 mA Is a Useful Test Point
For a standard linear 4-20 mA range:
12 mA = 50%
This makes 12 mA one of the easiest troubleshooting points.
Examples:
For 0-10 bar:
12 mA = 5 bar
For 0-100掳C:
12 mA = 50掳C
For 0-5 m tank level:
12 mA = 2.5 m
For 0-100%:
12 mA = 50%
If the system is supposed to be linear and these midpoint values are wrong, investigate the scaling and processing.
Why 8 mA and 16 mA Are Also Useful
Testing only 12 mA gives you one intermediate point.
Adding:
8 mA = 25%
and
16 mA = 75%
provides a better picture.
A useful functional test sequence is:
4 mA = 0%
8 mA = 25%
12 mA = 50%
16 mA = 75%
20 mA = 100%
Record both the expected and actual values.
Patterns in the error can help identify the problem.
Example: Temperature Transmitter
Suppose a temperature system is configured as:
0-200掳C = 4-20 mA
Expected:
4 mA = 0掳C
8 mA = 50掳C
12 mA = 100掳C
16 mA = 150掳C
20 mA = 200掳C
But the HMI shows:
4 mA = 0掳C
8 mA = 40掳C
12 mA = 90掳C
16 mA = 145掳C
20 mA = 200掳C
This is not the expected linear response.
Check whether the HMI is displaying the directly scaled transmitter signal or another calculated process value.
Check the Raw PLC Value First
When troubleshooting this type of problem, divide the system into stages.
Stage 1: Test Signal
Is the known test signal correct?
Stage 2: PLC Raw Input
Does the raw PLC value change consistently?
Stage 3: PLC Engineering Value
Does the PLC scaling produce the expected engineering value?
Stage 4: HMI
Does the HMI display the same correct value?
This helps locate where the error begins.
How the FNIRSI SG-003A Helps
For suitable applications, the FNIRSI SG-003A can provide known test signals so technicians can compare expected and actual system response.
Instead of relying on an operating process, technicians can check defined points such as:
4 mA
8 mA
12 mA
16 mA
20 mA
This is particularly useful during:
PLC commissioning
Control-panel testing
Scaling troubleshooting
HMI troubleshooting
Loop checking
Factory maintenance
Do Not Assume Every Process Is Linear
This is an important limitation.
A 4-20 mA electrical signal may be linear, but the final process calculation may not be.
Examples may include:
Flow calculations
Tank volume calculations
Special sensor curves
Square-root processing
Custom process equations
Therefore, before saying the midpoint is "wrong", confirm what the system is designed to display.
Functional Check vs Calibration
Applying several known signals and observing the PLC response is useful for functional testing and troubleshooting.
It is not automatically equivalent to formal calibration.
Formal calibration may require:
Specified accuracy
Traceable reference equipment
Measurement uncertainty
Documented procedures
Calibration records
Certificates
Choose the test equipment according to the required job.
Important Safety Reminder
Before applying a test signal:
Confirm the correct signal type
Check the PLC input specification
Identify the correct terminals
Check polarity
Understand the loop power arrangement
Confirm the permitted signal range
Review PLC logic
Determine what equipment may respond
Follow site isolation and safety procedures
A simulated analog value can potentially affect pumps, motors, valves, alarms and interlocks.
Looking for FNIRSI SG-003A in Malaysia?
MTM Precision Sdn Bhd supplies the FNIRSI SG-003A Signal Generator in Malaysia for PLC troubleshooting, 4-20 mA testing, control-panel commissioning and industrial maintenance applications.
If your 4 mA and 20 mA readings are correct but the midpoint is wrong, send us a photo of your PLC analog input module, transmitter range, HMI reading or wiring diagram through WhatsApp.
We can help evaluate the application and suitable test method.
MTM Precision Sdn Bhd
Showroom & Service Centre
No 29-1 & 2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
Serving customers across Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.
04 Oct 2026