4-20 mA Signal Unstable or Jumping - Troubleshooting Guide Malaysia

4-20 mA Signal Unstable or Jumping - Troubleshooting Guide Malaysia

 

A 4-20 mA signal should normally provide a stable representation of the process value.

 

But what if the PLC reading keeps jumping?

 

For example:

 

Pressure changes from 5.0 bar to 5.8 bar, then 4.7 bar

 

Tank level moves up and down even though the tank is stable

 

Temperature fluctuates rapidly without an obvious process change

 

PLC analog value is continuously unstable

 

The problem may come from the process, sensor, transmitter, wiring, electrical interference, power supply, PLC analog input, grounding or software configuration.

 

For suitable troubleshooting applications, the FNIRSI SG-003A Signal Generator can provide a known test signal to help determine whether the instability originates on the field side or receiving side.

 

For factory maintenance, instrumentation and automation teams in Malaysia, this can make troubleshooting much more systematic.

 

First Question: Is the Process Actually Stable?

 

Before checking electronics, confirm whether the physical process itself is changing.

 

A fluctuating signal does not automatically mean there is an electrical fault.

 

For example:

 

A pressure transmitter installed near a rapidly cycling pump may genuinely detect changing pressure.

 

A flow transmitter may show changing flow because a control valve is continuously adjusting.

 

A level transmitter may respond to turbulence inside the tank.

 

A temperature sensor may be located where airflow or process conditions vary.

 

First ask:

 

Is the process stable enough that the reading should be stable?

 

Understand the Signal Chain

 

A typical system may look like:

 

Sensor > Transmitter > 4-20 mA > Field Wiring > PLC > HMI

 

Instability can originate at any stage.

 

The objective is to determine where the unstable behaviour begins.

 

Problem 1: The Sensor Reading Is Actually Unstable

 

The sensor itself may be responding to a changing physical condition.

 

Examples include:

 

Pressure pulsation

 

Tank turbulence

 

Flow variation

 

Temperature cycling

 

Mechanical vibration

 

In this situation, the 4-20 mA signal may simply be accurately representing the changing process.

 

Check the process before adjusting the electronics.

 

Problem 2: Loose Wiring

 

A loose terminal or poor electrical connection can cause intermittent behaviour.

 

Inspect:

 

Transmitter terminals

 

Junction boxes

 

Field wiring

 

Control-panel terminals

 

PLC analog input terminals

 

Connectors

 

A connection that appears acceptable visually may still require further checking according to the maintenance procedure.

 

Problem 3: Power Supply Problem

 

Transmitters and control circuits require a suitable power supply.

 

If the supply is unstable or incorrectly configured, the transmitter output may also become unstable.

 

Check:

 

Power-supply specification

 

Actual supply condition

 

Terminal connections

 

Shared loads

 

Wiring

 

Transmitter requirements

 

Do not assume the power supply is healthy simply because the transmitter display is on.

 

Problem 4: Electrical Noise

 

Industrial environments can contain significant electrical interference.

 

Potential sources may include:

 

Variable frequency drives

 

Large motors

 

Contactors

 

High-current cables

 

Welding equipment

 

Switching power equipment

 

Motor starters

 

If analog signal cables are installed incorrectly or routed close to strong interference sources, signal quality may be affected.

 

The correct wiring and shielding practice depends on the equipment manufacturer's requirements and site design.

 

Problem 5: Grounding or Shielding Issue

 

Grounding and cable shielding can influence analog signal performance.

 

Incorrect shield termination or grounding arrangements may contribute to noise problems.

 

However, technicians should not randomly connect or disconnect grounds in an attempt to solve the problem.

 

Follow:

 

Equipment documentation

 

Control-panel design

 

Site grounding requirements

 

Instrumentation wiring practices

 

A grounding change can create new problems if performed incorrectly.

 

Problem 6: Transmitter Problem

 

If the process is stable but the transmitter output itself fluctuates, the transmitter or sensor system may require further investigation.

 

Possible areas include:

 

Sensor condition

 

Transmitter configuration

 

Sensor connection

 

Power supply

 

Internal transmitter fault

 

Environmental effects

 

The appropriate checks depend on the transmitter type.

 

Problem 7: PLC Analog Input Problem

 

Sometimes the incoming field signal appears stable, but the PLC value fluctuates.

 

Possible areas to investigate include:

 

Analog input module

 

PLC configuration

 

Incorrect input mode

 

Terminal connection

 

Grounding

 

Electrical noise near the control panel

 

A known test signal can help isolate this part of the system.

 

How Can the FNIRSI SG-003A Help?

 

Suppose the process reading is unstable.

 

Instead of relying on the field transmitter, technicians can apply a suitable known test signal to the receiving side under an approved test procedure.

 

For example:

 

12 mA

 

For a system configured as:

 

4-20 mA = 0-100%

 

the expected value is:

 

12 mA = 50%

 

Now observe the PLC.

 

Does the PLC remain close to a stable 50%?

 

Or does the displayed value continue jumping?

 

This provides an important troubleshooting clue.

 

If the Known Signal Is Stable at the PLC

 

Suppose the normal transmitter signal produces:

 

48% > 55% > 46% > 53%

 

But when a stable known signal is correctly applied, the PLC remains around the expected value.

 

This suggests that the receiving side can respond stably under the test condition.

 

Investigate the field side more closely:

 

Sensor

 

Process

 

Transmitter

 

Field wiring

 

Power supply

 

Electrical interference

 

If the PLC Still Jumps with a Known Signal

 

Suppose a stable known test signal is applied correctly, but the PLC reading still fluctuates.

 

The investigation can move towards:

 

PLC analog input

 

Control-panel wiring

 

Input configuration

 

Grounding

 

Electrical interference

 

PLC software processing

 

The field transmitter becomes less likely to be the only cause because it is no longer providing the test input.

 

Example: Pressure Reading Is Jumping

 

Suppose a pressure transmitter has:

 

0-10 bar = 4-20 mA

 

The process should be approximately:

 

5 bar

 

The HMI fluctuates between:

 

4.4 bar

 

and

 

5.7 bar

 

A known midpoint test signal can help.

 

For this range:

 

12 mA = 5 bar

 

If a stable 12 mA test produces a stable 5 bar display, investigate the pressure transmitter, process condition and field side.

 

If the displayed value continues fluctuating significantly, investigate the receiving side.

 

Example: Tank Level Fluctuates

 

A tank is physically stable at approximately 50%, but the HMI displays:

 

45%

 

52%

 

48%

 

56%

 

47%

 

For a system configured as:

 

4-20 mA = 0-100%

 

the midpoint is:

 

12 mA = 50%

 

A stable test signal can help determine whether the PLC display itself remains stable.

 

However, remember that some level measurement technologies can naturally be affected by:

 

Tank turbulence

 

Foam

 

Moving liquid

 

Obstructions

 

Installation conditions

 

Do not assume every fluctuating level reading is an electrical problem.

 

Example: Temperature Reading Jumps Rapidly

 

Suppose a temperature transmitter is configured as:

 

0-100掳C = 4-20 mA

 

The actual process temperature is stable.

 

But the HMI changes rapidly between:

 

42掳C

 

48掳C

 

44掳C

 

51掳C

 

At:

 

12 mA

 

the expected value is approximately:

 

50掳C

 

If the PLC remains stable when receiving a known signal, investigate the temperature sensor, transmitter and field wiring.

 

Check Whether the PLC Uses Filtering

 

Some PLC systems use digital filtering or averaging for analog inputs.

 

This may be used to reduce the effect of small fluctuations.

 

However, filtering should not be used to hide an actual electrical or process problem.

 

Before changing filtering settings, determine why the signal is unstable.

 

Check:

 

PLC analog input filter

 

Moving average settings

 

Software damping

 

Transmitter damping

 

HMI update rate

 

Changing these parameters can alter system response.

 

Transmitter Damping Can Affect the Reading

 

Some industrial transmitters include configurable damping.

 

Higher damping may make the displayed process value appear smoother but slower to respond.

 

Lower damping may show process changes more quickly.

 

If a replacement transmitter behaves differently from the old unit, compare the configuration.

 

Do not automatically assume that a faster-changing signal means the new transmitter is faulty.

 

Compare the Actual Signal with the PLC Value

 

A useful troubleshooting approach is to compare:

 

Actual loop signal

 

with

 

PLC raw value

 

and

 

HMI displayed value

 

If the actual signal is stable but the PLC value jumps, investigate the receiving side.

 

If the actual signal itself jumps, investigate the field side and process.

 

This comparison helps avoid guessing.

 

Check Whether the Problem Happens Only When Machinery Runs

 

This can be an important clue.

 

Ask whether the unstable signal appears when:

 

A motor starts

 

A VFD operates

 

A compressor runs

 

A pump starts

 

A welding machine is used

 

A large load switches

 

If the problem appears only during certain equipment operation, electrical interference, grounding, power quality or installation conditions may deserve further investigation.

 

Check Multiple Test Points

 

Do not test only one value.

 

For a 0-100% system, suitable functional points may include:

 

4 mA = 0%

 

12 mA = 50%

 

20 mA = 100%

 

Observe whether the PLC is stable at all three points.

 

If instability appears only at certain parts of the range, document the behaviour for further investigation.

 

Do Not Replace the Transmitter Immediately

 

When a reading jumps, replacing the transmitter may seem like the fastest solution.

 

But the transmitter may not be the problem.

 

Before replacement, check:

 

Actual process condition

 

Existing signal

 

Power supply

 

Field wiring

 

Connections

 

PLC input

 

Configuration

 

Response to a known test signal

 

Systematic testing is usually more useful than changing components one by one.

 

FNIRSI SG-003A for Unstable Signal Troubleshooting

 

For suitable applications, the FNIRSI SG-003A can support troubleshooting involving:

 

Unstable 4-20 mA signals

 

PLC analog inputs

 

Industrial transmitters

 

Control panels

 

Loop checking

 

Factory maintenance

 

Automation commissioning

 

Instrumentation troubleshooting

 

The key benefit is the ability to introduce a known, controlled test condition when checking the receiving system.

 

Important Safety Reminder

 

Before disconnecting a field transmitter or applying a test signal:

 

Review the wiring diagram

 

Confirm the signal type

 

Identify the correct terminals

 

Check polarity

 

Understand the loop power arrangement

 

Confirm the permitted signal range

 

Determine what equipment may respond

 

Follow site isolation and safety procedures

 

Changing an analog input can potentially activate:

 

Pumps

 

Motors

 

Valves

 

Alarms

 

Interlocks

 

Automatic control sequences

 

Never inject test signals into an operating system without understanding the possible response.

 

Looking for FNIRSI SG-003A in Malaysia?

 

MTM Precision Sdn Bhd supplies the FNIRSI SG-003A Signal Generator in Malaysia for 4-20 mA troubleshooting, PLC testing, control-panel commissioning and industrial maintenance applications.

 

If your 4-20 mA signal or PLC reading is unstable, send us a photo of the transmitter, PLC analog input module, wiring terminals or wiring diagram through WhatsApp.

 

We can help evaluate whether the SG-003A is suitable for your troubleshooting application.

 

MTM Precision Sdn Bhd

 

Showroom & Service Centre

No 29-1 & 2, Jalan Bandar 18,

Pusat Bandar Puchong,

47160 Puchong, Selangor, Malaysia

 

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com

Website: www.mtmpre.com.my

 

Serving customers across Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.


 

04 Oct 2026