4-20 mA Signal Unstable or Jumping - Troubleshooting Guide Malaysia
4-20 mA Signal Unstable or Jumping - Troubleshooting Guide Malaysia
A 4-20 mA signal should normally provide a stable representation of the process value.
But what if the PLC reading keeps jumping?
For example:
Pressure changes from 5.0 bar to 5.8 bar, then 4.7 bar
Tank level moves up and down even though the tank is stable
Temperature fluctuates rapidly without an obvious process change
PLC analog value is continuously unstable
The problem may come from the process, sensor, transmitter, wiring, electrical interference, power supply, PLC analog input, grounding or software configuration.
For suitable troubleshooting applications, the FNIRSI SG-003A Signal Generator can provide a known test signal to help determine whether the instability originates on the field side or receiving side.
For factory maintenance, instrumentation and automation teams in Malaysia, this can make troubleshooting much more systematic.
First Question: Is the Process Actually Stable?
Before checking electronics, confirm whether the physical process itself is changing.
A fluctuating signal does not automatically mean there is an electrical fault.
For example:
A pressure transmitter installed near a rapidly cycling pump may genuinely detect changing pressure.
A flow transmitter may show changing flow because a control valve is continuously adjusting.
A level transmitter may respond to turbulence inside the tank.
A temperature sensor may be located where airflow or process conditions vary.
First ask:
Is the process stable enough that the reading should be stable?
Understand the Signal Chain
A typical system may look like:
Sensor > Transmitter > 4-20 mA > Field Wiring > PLC > HMI
Instability can originate at any stage.
The objective is to determine where the unstable behaviour begins.
Problem 1: The Sensor Reading Is Actually Unstable
The sensor itself may be responding to a changing physical condition.
Examples include:
Pressure pulsation
Tank turbulence
Flow variation
Temperature cycling
Mechanical vibration
In this situation, the 4-20 mA signal may simply be accurately representing the changing process.
Check the process before adjusting the electronics.
Problem 2: Loose Wiring
A loose terminal or poor electrical connection can cause intermittent behaviour.
Inspect:
Transmitter terminals
Junction boxes
Field wiring
Control-panel terminals
PLC analog input terminals
Connectors
A connection that appears acceptable visually may still require further checking according to the maintenance procedure.
Problem 3: Power Supply Problem
Transmitters and control circuits require a suitable power supply.
If the supply is unstable or incorrectly configured, the transmitter output may also become unstable.
Check:
Power-supply specification
Actual supply condition
Terminal connections
Shared loads
Wiring
Transmitter requirements
Do not assume the power supply is healthy simply because the transmitter display is on.
Problem 4: Electrical Noise
Industrial environments can contain significant electrical interference.
Potential sources may include:
Variable frequency drives
Large motors
Contactors
High-current cables
Welding equipment
Switching power equipment
Motor starters
If analog signal cables are installed incorrectly or routed close to strong interference sources, signal quality may be affected.
The correct wiring and shielding practice depends on the equipment manufacturer's requirements and site design.
Problem 5: Grounding or Shielding Issue
Grounding and cable shielding can influence analog signal performance.
Incorrect shield termination or grounding arrangements may contribute to noise problems.
However, technicians should not randomly connect or disconnect grounds in an attempt to solve the problem.
Follow:
Equipment documentation
Control-panel design
Site grounding requirements
Instrumentation wiring practices
A grounding change can create new problems if performed incorrectly.
Problem 6: Transmitter Problem
If the process is stable but the transmitter output itself fluctuates, the transmitter or sensor system may require further investigation.
Possible areas include:
Sensor condition
Transmitter configuration
Sensor connection
Power supply
Internal transmitter fault
Environmental effects
The appropriate checks depend on the transmitter type.
Problem 7: PLC Analog Input Problem
Sometimes the incoming field signal appears stable, but the PLC value fluctuates.
Possible areas to investigate include:
Analog input module
PLC configuration
Incorrect input mode
Terminal connection
Grounding
Electrical noise near the control panel
A known test signal can help isolate this part of the system.
How Can the FNIRSI SG-003A Help?
Suppose the process reading is unstable.
Instead of relying on the field transmitter, technicians can apply a suitable known test signal to the receiving side under an approved test procedure.
For example:
12 mA
For a system configured as:
4-20 mA = 0-100%
the expected value is:
12 mA = 50%
Now observe the PLC.
Does the PLC remain close to a stable 50%?
Or does the displayed value continue jumping?
This provides an important troubleshooting clue.
If the Known Signal Is Stable at the PLC
Suppose the normal transmitter signal produces:
48% > 55% > 46% > 53%
But when a stable known signal is correctly applied, the PLC remains around the expected value.
This suggests that the receiving side can respond stably under the test condition.
Investigate the field side more closely:
Sensor
Process
Transmitter
Field wiring
Power supply
Electrical interference
If the PLC Still Jumps with a Known Signal
Suppose a stable known test signal is applied correctly, but the PLC reading still fluctuates.
The investigation can move towards:
PLC analog input
Control-panel wiring
Input configuration
Grounding
Electrical interference
PLC software processing
The field transmitter becomes less likely to be the only cause because it is no longer providing the test input.
Example: Pressure Reading Is Jumping
Suppose a pressure transmitter has:
0-10 bar = 4-20 mA
The process should be approximately:
5 bar
The HMI fluctuates between:
4.4 bar
and
5.7 bar
A known midpoint test signal can help.
For this range:
12 mA = 5 bar
If a stable 12 mA test produces a stable 5 bar display, investigate the pressure transmitter, process condition and field side.
If the displayed value continues fluctuating significantly, investigate the receiving side.
Example: Tank Level Fluctuates
A tank is physically stable at approximately 50%, but the HMI displays:
45%
52%
48%
56%
47%
For a system configured as:
4-20 mA = 0-100%
the midpoint is:
12 mA = 50%
A stable test signal can help determine whether the PLC display itself remains stable.
However, remember that some level measurement technologies can naturally be affected by:
Tank turbulence
Foam
Moving liquid
Obstructions
Installation conditions
Do not assume every fluctuating level reading is an electrical problem.
Example: Temperature Reading Jumps Rapidly
Suppose a temperature transmitter is configured as:
0-100掳C = 4-20 mA
The actual process temperature is stable.
But the HMI changes rapidly between:
42掳C
48掳C
44掳C
51掳C
At:
12 mA
the expected value is approximately:
50掳C
If the PLC remains stable when receiving a known signal, investigate the temperature sensor, transmitter and field wiring.
Check Whether the PLC Uses Filtering
Some PLC systems use digital filtering or averaging for analog inputs.
This may be used to reduce the effect of small fluctuations.
However, filtering should not be used to hide an actual electrical or process problem.
Before changing filtering settings, determine why the signal is unstable.
Check:
PLC analog input filter
Moving average settings
Software damping
Transmitter damping
HMI update rate
Changing these parameters can alter system response.
Transmitter Damping Can Affect the Reading
Some industrial transmitters include configurable damping.
Higher damping may make the displayed process value appear smoother but slower to respond.
Lower damping may show process changes more quickly.
If a replacement transmitter behaves differently from the old unit, compare the configuration.
Do not automatically assume that a faster-changing signal means the new transmitter is faulty.
Compare the Actual Signal with the PLC Value
A useful troubleshooting approach is to compare:
Actual loop signal
with
PLC raw value
and
HMI displayed value
If the actual signal is stable but the PLC value jumps, investigate the receiving side.
If the actual signal itself jumps, investigate the field side and process.
This comparison helps avoid guessing.
Check Whether the Problem Happens Only When Machinery Runs
This can be an important clue.
Ask whether the unstable signal appears when:
A motor starts
A VFD operates
A compressor runs
A pump starts
A welding machine is used
A large load switches
If the problem appears only during certain equipment operation, electrical interference, grounding, power quality or installation conditions may deserve further investigation.
Check Multiple Test Points
Do not test only one value.
For a 0-100% system, suitable functional points may include:
4 mA = 0%
12 mA = 50%
20 mA = 100%
Observe whether the PLC is stable at all three points.
If instability appears only at certain parts of the range, document the behaviour for further investigation.
Do Not Replace the Transmitter Immediately
When a reading jumps, replacing the transmitter may seem like the fastest solution.
But the transmitter may not be the problem.
Before replacement, check:
Actual process condition
Existing signal
Power supply
Field wiring
Connections
PLC input
Configuration
Response to a known test signal
Systematic testing is usually more useful than changing components one by one.
FNIRSI SG-003A for Unstable Signal Troubleshooting
For suitable applications, the FNIRSI SG-003A can support troubleshooting involving:
Unstable 4-20 mA signals
PLC analog inputs
Industrial transmitters
Control panels
Loop checking
Factory maintenance
Automation commissioning
Instrumentation troubleshooting
The key benefit is the ability to introduce a known, controlled test condition when checking the receiving system.
Important Safety Reminder
Before disconnecting a field transmitter or applying a test signal:
Review the wiring diagram
Confirm the signal type
Identify the correct terminals
Check polarity
Understand the loop power arrangement
Confirm the permitted signal range
Determine what equipment may respond
Follow site isolation and safety procedures
Changing an analog input can potentially activate:
Pumps
Motors
Valves
Alarms
Interlocks
Automatic control sequences
Never inject test signals into an operating system without understanding the possible response.
Looking for FNIRSI SG-003A in Malaysia?
MTM Precision Sdn Bhd supplies the FNIRSI SG-003A Signal Generator in Malaysia for 4-20 mA troubleshooting, PLC testing, control-panel commissioning and industrial maintenance applications.
If your 4-20 mA signal or PLC reading is unstable, send us a photo of the transmitter, PLC analog input module, wiring terminals or wiring diagram through WhatsApp.
We can help evaluate whether the SG-003A is suitable for your troubleshooting application.
MTM Precision Sdn Bhd
Showroom & Service Centre
No 29-1 & 2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
Serving customers across Selangor, Kuala Lumpur, Johor, Penang, Melaka, Negeri Sembilan, Perak, Pahang, Kelantan, Terengganu, Kedah, Perlis, Sabah and Sarawak.
04 Oct 2026