Professional Fuzrr ES6030 Transformer Turns Ratio Tester (Malaysia)
Professional Fuzrr ES6030 Transformer Turns Ratio Tester (Malaysia)
Product Applications
-
Transformer turns ratio, transformation ratio, and connection vector group testing for three-phase power transformers
-
Polarity, transformation ratio, and phase angle testing for single-phase transformers, potential transformers (PT), and current transformers (CT)
-
Turns ratio and phase vector verification for Z-type grounding transformers and specialized phase-shifting transformers
-
Three-phase blind testing for transformers with unknown tap connection groups or unlabelled nameplates
-
Quality inspection, factory acceptance testing (FAT), and routine field maintenance for transformer manufacturers, distributors, and power utilities
Key Features & Operational Advantages
-
Versatile Multi-Mode Testing Architecture: Supports single-phase test, three-phase test, three-phase blind test, and Z-type transformer test modes in a single handheld unit.
-
Wide Variable Ratio Range (0.9 to 10000): Measures turns ratios from 0.9 to 10000 with high resolution (0.0001) and high accuracy (0.2% for ratios 0.9 to 2000, and 0.5% for ratios 2000 to 10000).
-
5-Inch Full-Color Touch Screen Display: Features a bright 5-inch color LCD display (854 x 480 dots,LCD size: 108mm x 65mm) with dual touch screen and button navigation, supporting English and Chinese languages.
-
Dual Wireless & Wired Control (Bluetooth APP + USB PC): Supports wireless mobile APP control via Bluetooth as well as upper-computer PC software control and data export via USB interface.
-
Rechargeable Lithium Battery Power: Powered by a built-in DC 9.6V 3800mAh large-capacity lithium battery, eliminating field dependency on external AC power outlets.
-
500-Group Data Memory & Safety Features: Stores up to 500 sets of data with data access functions,overload port protection, real-time battery voltage monitoring, and customizable auto shut-off (1 to 30 minutes).
Technical Specifications — Fuzrr ES6030
Core Measurement Parameters
-
Primary Functions: Mainly used for transformer ratio and group test of three-phase transformer,transformer ratio and polarity test of single-phase transformer, PT and CT; conducts blind test of three-phase transformer and change ratio
-
Type of Test Products: Single-phase transformer, three-phase transformer, Z-type transformer, Potential Transformer (PT), Current Transformer (CT)
-
Variable Ratio Measurement Range: 0.9 to 10000
-
Maximum Resolution: 0.0001
-
Measurement Accuracy:
-
0.2% when variable ratio is 0.9 to 2000
-
0.5% when variable ratio is 2000 to 10000
-
-
Overload Protection: Supported
Functional Features & Data Management
-
Test Modes: Single-phase test, three-phase test, three-phase blind test, Z-type test
-
Display Mode: 5-inch touchscreen (854 dots x 480 dots) full-color LCD display (LCD Size: 108mm x 65mm)
-
Interactive Mode: Touch screen and button operation
-
Mobile APP Control: Supported via Bluetooth connection
-
Computer Connection: Supported via USB cable connection
-
Data Storage Capacity: 500 groups
-
Data Access Function: Built-in data review and query functions
-
Battery Voltage Indicator: Real-time display of battery power, indicating timely charging when battery voltage is low
-
Automatic Shutdown: Automatic shutdown can be set from 1 to 30 minutes
Hardware, Physical & Environmental Parameters
-
Power Supply: DC 9.6V 3800mAh large capacity rechargeable lithium battery
-
Charging Function: Supported
-
Power Dissipation:
-
Standby: Approx. 2W (100% brightness)
-
Measurement: 12W Max
-
-
Instrument Dimensions: Length 229mm x Width 166mm x Height 74mm
-
Weights:
-
Host Instrument: 1.5kg (including battery)
-
Test Cables: 1.7kg
-
-
Insulation Resistance: Above 10 MΩ (500V between circuit and housing)
-
Withstand Voltage: AC 3700V / rms (between circuit and enclosure)
-
Electromagnetic Characteristics: IEC61010-4-3, Wireless frequency electromagnetic fields <= 1V/m
-
Ingress Protection Rating: IP45
-
Suitable Safety Regulations & Standards: IEC61010-1, CAT III 600V, Pollution Grade 2
Why Choose MTM Precision in Malaysia?
10 Nov 2026