How to Check Perforated Floor Tile Airflow in a Data Centre Malaysia

How to Check Perforated Floor Tile Airflow in a Data Centre Malaysia

 

In raised-floor data centres, perforated floor tiles can be an important part of cooling air distribution.

 

Cold air supplied beneath the raised floor passes through selected perforated tiles and enters the cold aisle, where IT equipment draws in cooling air.

 

But how can facility teams check whether different floor tiles are delivering consistent airflow?

 

A portable digital anemometer such as the TASI TA642C High Accuracy Digital Anemometer can be used for spot measurements and comparative airflow checks around selected perforated tiles.

 

Why Check Perforated Tile Airflow?

 

Simply seeing or feeling air coming through a perforated tile does not tell you whether airflow distribution is consistent.

 

Two tiles may look identical while delivering different airflow.

 

Possible differences can be related to:

 

Underfloor air distribution

 

Tile location

 

Dampers

 

Obstructions

 

Cable congestion

 

Cooling unit operation

 

Raised-floor configuration

 

System adjustments

 

Measurement helps facility teams identify locations that deserve further investigation.

 

Air Velocity or Airflow?

 

There are two related measurements to understand.

 

Air velocity describes how fast air is moving.

 

Airflow describes the volume of air moving through a defined area.

 

For a quick comparison between similar tiles, air velocity measurements may provide useful information.

 

For airflow volume, the measurement area must also be considered.

 

The basic relationship is:

 

Airflow = Air Velocity × Area

 

What Is CFM?

 

CFM means Cubic Feet per Minute.

 

It is commonly used to describe airflow volume.

 

Depending on the project or engineering documentation, other units may include:

 

CMM – Cubic Metres per Minute

 

CMS – Cubic Metres per Second

 

The TA642C supports airflow measurement functions that can be useful when these values are required.

 

Step 1: Identify the Tiles to Be Compared

 

Do not begin by randomly measuring tiles.

 

Create a simple measurement plan.

 

For example:

 

Cold Aisle A – Tile 01

 

Cold Aisle A – Tile 02

 

Cold Aisle A – Tile 03

 

Cold Aisle B – Tile 01

 

Numbering or documenting the measurement points makes future comparison easier.

 

Step 2: Keep the Data Centre Operating Condition Stable

 

Before comparing measurements, consider whether the cooling system is operating under comparable conditions.

 

Changes in fan operation or cooling control can affect airflow.

 

If possible, avoid comparing measurements taken under completely different system conditions.

 

Step 3: Position the Probe Carefully

 

Position the anemometer probe at the selected measurement point without unnecessarily blocking the airflow.

 

The TA642C separate probe design can be useful because the sensor can be positioned at the tile while the technician holds and views the main instrument separately.

 

Probe position should remain consistent when comparing different locations.

 

Step 4: Do Not Depend on One Centre Reading

 

A perforated tile contains many openings.

 

Airflow may not be uniform across the entire surface.

 

A centre reading may therefore be different from measurements taken at other parts of the tile.

 

For better comparison, technicians may take readings at several consistent positions.

 

Step 5: Compare the Measurements

 

Suppose five similar tiles are checked.

 

Four show relatively consistent measurements.

 

One is substantially different.

 

This does not automatically mean the tile itself is defective.

 

Instead, it provides information for further investigation.

 

Possible areas to inspect may include:

 

Underfloor obstruction

 

Damper position

 

Cable congestion

 

Air distribution

 

Cooling configuration

 

Tile arrangement

 

Why Cable Congestion Matters

 

Raised-floor spaces may contain cables and other infrastructure.

 

These can influence the available airflow path.

 

If a particular cold aisle shows unusual airflow distribution, the underfloor condition may need to be considered as part of the investigation.

 

An anemometer cannot see under the floor, but measurement can help identify where inspection may be useful.

 

Check After Moving a Floor Tile

 

Changing the position or type of perforated floor tiles can alter cooling-air distribution.

 

If tiles are rearranged, technicians can measure selected points before and after the change.

 

This provides more useful information than relying only on whether the cold aisle “feels cooler”.

 

Check After Installing New Racks

 

New IT equipment can change cooling demand and airflow requirements.

 

After a rack installation or major equipment change, facility teams may perform spot checks at selected cooling points.

 

These measurements can be considered together with rack inlet temperatures and other environmental data.

 

Check Upper and Lower Rack Conditions

 

Airflow from a floor tile is only one part of the cooling path.

 

Facility teams may also investigate conditions around different heights of the rack.

 

For example:

 

Lower rack intake

 

Middle rack intake

 

Upper rack intake

 

Differences may provide useful information about air distribution.

 

However, an anemometer reading alone does not determine whether rack inlet conditions meet the required data centre specification.

 

Don't Confuse High Velocity with Good Cooling

 

A high air velocity reading at one location does not automatically mean that the entire rack is being cooled effectively.

 

Cooling performance also depends on factors such as:

 

Air distribution

 

Temperature

 

IT heat load

 

Rack arrangement

 

Hot-air recirculation

 

Cold-air bypass

 

Containment

 

Cooling-system design

 

Air velocity is one measurement within a larger cooling assessment.

 

What If One Tile Has Very Low Airflow?

 

If one tile produces substantially lower readings than comparable tiles, investigate systematically.

 

Check whether:

 

The tile is obstructed

 

The damper is correctly positioned

 

Underfloor airflow is restricted

 

Cable congestion is present

 

Cooling conditions have changed

 

The tile configuration is appropriate

 

Avoid immediately increasing cooling capacity without understanding the airflow distribution.

 

What If One Tile Has Very High Airflow?

 

Higher airflow is not automatically better.

 

Excessive airflow at one location may indicate that cooling air is not being distributed as intended elsewhere.

 

The objective should be appropriate air distribution according to the data centre design, not simply obtaining the highest possible reading.

 

Before-and-After Airflow Measurement

 

One useful workflow is:

 

Measure → Adjust → Measure Again

 

For example:

 

Before Adjustment

 

Record selected tile measurements.

 

Make the Required Change

 

Adjust the airflow configuration according to the facility procedure.

 

After Adjustment

 

Repeat measurements at the same locations.

 

This provides measurable information about the effect of the change.

 

Build a Perforated Tile Airflow Map

 

For larger facilities, selected measurement points can be documented on a floor plan.

 

Each tile can be assigned an ID.

 

For example:

 

CA-A-T01

 

CA-A-T02

 

CA-B-T01

 

Recorded measurements can then be associated with these locations.

 

Over time, the facility team can compare changes more systematically.

 

Data Logging for Multiple Tiles

 

Checking many floor tiles can produce a large number of readings.

 

The TA642C provides data storage capability that can support multi-point measurement work.

 

USB/PC connectivity can also be useful when data needs to be reviewed or organised after the inspection.

 

Portable Measurement vs Continuous Monitoring

 

The TA642C is a portable measurement instrument.

 

It is suitable for activities such as:

 

Spot checking

 

Troubleshooting

 

Maintenance inspection

 

Before-and-after comparison

 

Airflow investigation

 

It does not replace a permanent data centre environmental monitoring system where continuous measurements and alarms are required.

 

Other Data Centre Measurements

 

A more complete cooling investigation may also consider:

 

Temperature

 

Relative humidity

 

Differential pressure

 

Electrical load

 

Power consumption

 

Other environmental parameters

 

Airflow measurement should be interpreted together with the wider operating condition.

 

TASI TA642C for Data Centre Perforated Tile Airflow Malaysia

 

The TASI TA642C High Accuracy Digital Anemometer can support facility teams that need portable measurements around perforated floor tiles and other data centre cooling-air locations.

 

Its separate probe configuration is useful for positioning the sensor while keeping the display accessible.

 

Air velocity and airflow measurements can help technicians compare cooling points and identify unusual conditions that may require further investigation.

 

For product availability and technical enquiries:

 

MTM Precision Sdn Bhd

Showroom & Service Centre: Puchong, Selangor, Malaysia

 

Tel: 03-8080 7172

WhatsApp: +6016-660 7346

Email: mtmpre@yahoo.com

Website: www.mtmpre.com.my

 

Contact MTM Precision for more information about the TASI TA642C Digital Anemometer for perforated floor tile airflow, cold aisle inspection and data centre cooling applications in Malaysia.


 

26 Sep 2026