How to Compare AHU Airflow Before and After Maintenance Malaysia
How to Compare AHU Airflow Before and After Maintenance Malaysia
After an Air Handling Unit (AHU) has been serviced, technicians often report that the system is operating normally.
But did the airflow actually change?
Taking before-and-after airflow measurements can provide useful evidence of AHU condition and help maintenance teams determine whether further investigation is required.
A portable digital anemometer such as the TASI TA642C High Accuracy Digital Anemometer can support air velocity and airflow measurements during AHU preventive maintenance in Malaysia.
Why Measure Before AHU Maintenance?
If measurements are only taken after servicing, there is no baseline for comparison.
Whenever practical, record selected measurements before starting maintenance.
This allows technicians to compare:
Before Maintenance → After Maintenance
The objective is not necessarily to perform a complete air-balancing exercise.
It is to create repeatable measurement data that supports maintenance and troubleshooting.
What Can Affect AHU Airflow?
AHU airflow can be influenced by many parts of the system.
These may include:
Filters
Cooling coils
Fans
Dampers
Ductwork
Supply grilles
Return-air path
Control settings
System operating conditions
This is why one airflow measurement should not automatically be used to diagnose a specific component.
Step 1: Choose Repeatable Measurement Points
Before servicing the AHU, identify suitable measurement locations.
Possible points may include:
Main supply duct
Selected branch ducts
Supply air outlets
Return-air locations
Fresh-air duct
Other accessible ventilation points
Document the location clearly.
For example:
AHU-01 – Main Supply Duct – Point A
This allows the same point to be measured again after maintenance.
Step 2: Record the Operating Condition
Airflow measurements are difficult to compare if the AHU is operating differently each time.
Record relevant information such as:
Fan operating condition
HVAC mode
Damper position
Measurement location
Measurement unit
If the system uses variable-speed control, operating conditions become particularly important.
Step 3: Measure Air Velocity
Use the anemometer to measure air velocity at the selected location.
The TA642C separate probe design can be useful when the sensor needs to be positioned at a duct or ventilation point while the technician views the main instrument separately.
Avoid unnecessary obstruction around the sensor.
Step 4: Take Multiple Readings Where Required
Air velocity inside a duct is not necessarily uniform.
The centre may have a different velocity from locations closer to the duct wall.
Bends, dampers and other components can also disturb the airflow profile.
Depending on the measurement objective, multiple readings may provide a more representative result.
Formal HVAC testing and balancing should follow the appropriate procedure.
Step 5: Record Airflow Volume if Required
If airflow volume is required, the relevant measurement area must be known.
The basic relationship is:
Airflow = Air Velocity × Area
Depending on the reporting requirement, airflow may be expressed as:
CFM
CMM
CMS
Incorrect duct dimensions or units can produce incorrect airflow calculations.
Step 6: Perform the AHU Maintenance
The required maintenance depends on the system condition.
Typical work may involve:
Filter replacement
Coil cleaning
Fan inspection
General cleaning
Damper inspection
Belt or mechanical inspection where applicable
Other scheduled maintenance
Follow the AHU manufacturer's and facility's maintenance procedures.
Step 7: Repeat the Measurement
After maintenance, return to the same measurement points.
Try to reproduce the previous operating condition as closely as practical.
Use the same:
Measurement location
Probe orientation
Measurement unit
Measurement method
Now the before-and-after readings can be compared more meaningfully.
What If Airflow Improves?
Suppose the post-maintenance measurements are higher than the baseline.
This indicates that the measured airflow condition changed.
However, avoid automatically attributing the entire difference to one maintenance action if several components were serviced simultaneously.
Document what work was performed and what measurements changed.
What If Airflow Does Not Improve?
This is also useful information.
If airflow remains lower than expected after maintenance, additional investigation may be necessary.
Possible areas include:
Fan operation
Damper position
Duct restriction
Return-air condition
Control settings
Other system factors
The measurement helps show that further troubleshooting may be required.
What If Airflow Becomes Lower?
Before assuming that something went wrong during servicing, first confirm the test conditions.
Ask:
Was the fan operating at the same condition?
Were the dampers in the same position?
Was the measurement taken at exactly the same location?
Was the probe positioned consistently?
Were the same units used?
Measurement consistency should be checked before conclusions are made.
Example: AHU Filter Replacement
Consider an AHU with a filter scheduled for replacement.
Before changing the filter, the technician records selected airflow measurements.
The filter is replaced.
The AHU is returned to comparable operating conditions.
The technician repeats the measurements.
These readings can now be included in the maintenance record.
This provides more information than simply writing:
“Filter replaced.”
Example: AHU Coil Cleaning
The same method can be used before and after coil cleaning.
If airflow has been affected by system condition, measurement may help show whether the airflow situation changed after servicing.
Temperature and other HVAC parameters may also be relevant when evaluating overall system performance.
Create an AHU Baseline
One of the most useful long-term practices is establishing baseline measurements when an AHU is known to be operating normally.
For example:
AHU-01 Main Supply – Baseline
AHU-01 Fresh Air – Baseline
AHU-01 Return Air – Baseline
Future maintenance measurements can then be compared against these references.
A significant change can trigger further inspection.
Why Trending Is Useful
Imagine an AHU is checked every three months.
The measurements remain reasonably consistent for several inspections.
Later, the recorded airflow begins to decrease.
This trend may provide useful maintenance information before occupants start reporting major comfort problems.
The purpose is not to predict every failure from airflow alone.
It is to add another measurable parameter to the preventive maintenance programme.
Using TA642C Data Storage
When several AHUs or measurement points need to be checked, technicians can accumulate many readings.
The TA642C provides data storage capability for this type of work.
USB/PC connectivity can also support later review and organisation of measurement data.
This can be useful for:
Facility maintenance records
Service reports
Before-and-after comparisons
Troubleshooting documentation
AHU Airflow and Energy Consumption
Airflow is important, but an anemometer alone cannot determine total AHU energy efficiency.
A more complete assessment may require additional measurements such as:
Electrical power
Temperature
Pressure
Humidity
Fan operating data
Cooling-system data
Airflow measurement should be interpreted as one part of the overall system condition.
AHU Airflow and Indoor Air Quality
Similarly, airflow measurement alone does not constitute a complete indoor air quality assessment.
If parameters such as CO2, PM2.5, VOCs or other contaminants need to be evaluated, suitable IAQ instruments are required.
The TA642C is used to measure airflow-related parameters, not contaminant concentration.
Suitable Applications in Malaysia
Before-and-after AHU airflow measurements can be useful in:
Commercial buildings
Offices
Shopping centres
Hotels
Hospitals
Factories
Schools
Warehouses
Data centres
Facility management operations
The required measurement method should match the building and maintenance objective.
TASI TA642C for AHU Preventive Maintenance Malaysia
The TASI TA642C High Accuracy Digital Anemometer can support HVAC contractors, M&E contractors and facility management teams that need portable airflow measurements before and after AHU maintenance.
By establishing repeatable measurement points and keeping operating conditions consistent, technicians can create more useful maintenance records and identify changes that may require further investigation.
For product availability and technical enquiries:
MTM Precision Sdn Bhd
Showroom & Service Centre: Puchong, Selangor, Malaysia
Tel: 03-8080 7172
WhatsApp: +6016-660 7346
Email: mtmpre@yahoo.com
Website: www.mtmpre.com.my
Contact MTM Precision for more information about the TASI TA642C Digital Anemometer for AHU airflow measurement, HVAC preventive maintenance and ventilation testing in Malaysia.
26 Sep 2026