Anchor Pull-Out Tester for M12, M16 & M20 Chemical Anchors Malaysia
Anchor Pull-Out Tester for M12, M16 & M20 Chemical Anchors Malaysia
What Pull-Out Tester Do I Need for M12, M16 or M20 Chemical Anchors?
Customers looking for an anchor pull-out tester often start with the anchor size:
“I need to test M12 chemical anchors.”
“Can this tester test M16?”
“What tonnage do I need for M20 anchors?”
Anchor size is important because it affects the mechanical connection between the anchor and the pull-out tester.
However, M12, M16 or M20 alone does not determine the required tester capacity.
To select the correct anchor pull-out tester, you should confirm at least:
Anchor Size + Required Test Load + Test Application + Connection Configuration
For suitable applications requiring up to 200kN measurement range, the Langry APT200 Anchor Pull-Out Tester is one option for professional chemical anchor testing in Malaysia.
Quick Answer: M12, M16 and M20
A simple equipment-selection approach is:
Anchor SizeCan Tester Be Selected from Size Alone?What You Must ConfirmM12NoRequired test load + connectionM16NoRequired test load + connectionM20NoRequired test load + connection
Do not automatically assume:
M12 = 10 Ton
M16 = 20 Ton
M20 = 30 Ton
There is no universal relationship like this.
Why Anchor Diameter Does Not Determine Test Load
Consider two M16 chemical anchors.
They may have the same nominal threaded-rod diameter but different:
Chemical anchoring systems
Embedment depths
Concrete conditions
Design loads
Installation configurations
Project requirements
One project may specify a relatively modest proof load.
Another M16 installation may have a substantially different requirement.
Therefore:
Anchor Diameter ≠ Required Pull-Out Force
M12 Chemical Anchor Pull-Out Testing
M12 threaded rods are commonly encountered in many construction fixing applications.
Potential applications can include:
Steel brackets
M&E supports
Façade components
Equipment supports
General structural fixings
Before testing an M12 chemical anchor, confirm:
Exact anchor/thread size
Exposed thread length
Chemical anchor system
Required test load
Test objective
Test procedure
Do not select tester capacity solely because the rod is M12.
M16 Chemical Anchor Pull-Out Testing
M16 is another commonly encountered size in construction anchoring.
Applications may include:
Façade brackets
Structural steelwork
Heavy supports
Retrofit installations
Equipment anchoring
When a customer asks:
“Can Langry APT200 test M16?”
the answer requires more than the diameter.
We need to know:
What load does the project require?
and:
Can the test connection be configured correctly?
M20 Chemical Anchor Pull-Out Testing
M20 anchors may be used in heavier anchoring applications.
However, the same principle applies.
Do not assume that every M20 anchor requires 200kN or 300kN testing.
The correct load should come from the approved engineering or project requirements.
Before testing, check:
Required force
Thread condition
Exposed length
Embedment
Adapter arrangement
Reaction setup
What About M6, M8, M10 and M22?
The Langry APT200 configuration includes converters covering M6–M22 according to the manufacturer's stated configuration.
However, nominal converter availability alone does not establish that every anchor installation can automatically be tested.
You must still consider:
Required force
Thread engagement
Exposed length
Surrounding clearance
Test geometry
Reaction arrangement
For unusual installations, send photographs and dimensions before testing or purchasing equipment.
Langry APT200 Pulling Configuration
The Langry APT200 includes:
Pull Rod: M24
Converters: M6–M22
This provides flexibility for a range of supported threaded anchor configurations.
For M12, M16 and M20 applications, the actual connection should still be checked before testing.
Why Exposed Thread Length Matters
Imagine an M16 chemical anchor.
The customer confirms:
“Yes, it is M16.”
But only a very short section of thread remains exposed above the bracket.
The adapter may not have sufficient engagement.
Therefore, before going to site, ask:
How much usable thread is exposed?
A photograph with dimensions can be very useful.
Existing Nuts and Brackets Can Affect Testing
Some installed chemical anchors already contain:
Nuts
Washers
Steel plates
Façade brackets
Structural brackets
These components can affect how the pull-out tester is connected.
Do not assume the test setup from anchor diameter alone.
Check the Area Around the Anchor
The hydraulic cylinder needs physical clearance.
Potential obstructions include:
Nearby anchors
Steel plates
Concrete upstands
Walls
Façade profiles
Machinery bases
For complicated locations, send MTM Precision a photograph before purchasing or mobilising equipment.
How Do I Choose Tester Capacity for M12?
First ask:
What is the maximum required test load?
For example, if an approved M12 anchor test requires a load well within 100kN, a 100kN-class tester may potentially provide sufficient capacity, subject to the complete testing requirements.
If the required load exceeds 100kN, a higher-range model should be considered.
The anchor being M12 does not determine this by itself.
How Do I Choose Tester Capacity for M16?
The same process applies.
If the required load is:
Below or within 100kN
APT100 may potentially be considered.
If the requirement is:
Above 100kN but within 200kN
APT200 may be considered.
The exact selection should account for the test method and connection.
How Do I Choose Tester Capacity for M20?
Again, use the actual required load.
If the required test exceeds the APT200's maximum range, a higher-capacity model such as APT300 may need to be considered.
Do not buy APT300 simply because the anchor says M20.
Langry APT100 vs APT200 vs APT300
ModelMaximum Measurement RangeApproximate CapacityAPT100100kN10 TonAPT200200kN20 TonAPT300300kN30 Ton
The best model depends primarily on the required test range and actual test configuration.
Example 1 – M12 Anchor, Required Load 45kN
Suppose the project information is:
Anchor: M12 Chemical Anchor
Required Proof Load: 45kN
The first conclusion is:
A tester must be suitable for at least the required testing range.
Then check:
Adapter compatibility
Exposed thread
Reaction setup
Project procedure
There is no reason to assume 200kN is required simply because APT200 is available.
Example 2 – M16 Anchor, Required Load 120kN
Suppose:
Anchor: M16
Required Test Load: 120kN
A 100kN tester does not provide sufficient range for a 120kN requirement.
A 200kN-class system such as the Langry APT200 may therefore be considered, subject to the complete test configuration.
Example 3 – M20 Anchor, Required Load 180kN
Suppose:
Anchor: M20
Required Test Load: 180kN
The requirement is within the APT200's 200kN measurement range.
The next questions are:
Is the connection suitable?
Is the reaction arrangement appropriate?
Is there sufficient clearance?
Does the approved procedure require any additional measurement?
Capacity alone does not complete equipment selection.
Example 4 – M16 Anchor, Required Load 220kN
Suppose:
Anchor: M16
Required Test Load: 220kN
The APT200 has a maximum range of 200kN.
Therefore, it does not provide sufficient measurement range for a 220kN requirement.
A higher-capacity tester such as the APT300 should be evaluated.
Notice that this is still an M16 anchor.
This clearly demonstrates why anchor diameter and tester capacity are not directly interchangeable.
Chemical Anchor Type Also Matters
Different chemical anchoring systems may have different:
Installation requirements
Hole dimensions
Embedment requirements
Curing conditions
Approved applications
Always follow the relevant anchor system requirements.
Concrete Condition Matters
The base material forms part of the anchoring system.
Testing behaviour can be influenced by:
Concrete condition
Cracking
Local defects
Edge location
Installation quality
The test result should therefore be interpreted within the actual project context.
Chemical Anchor Curing Before Testing
Before testing M12, M16 or M20 chemical anchors, confirm that the applicable curing requirement has been achieved.
Do not test simply because:
“The resin looks dry.”
Use the approved chemical anchor installation information and project requirements.
Proof Test or Failure Test?
Before selecting equipment, clarify the test objective.
Proof Load Test
The anchor is tested to a predetermined load according to the approved procedure without intentionally loading it to ultimate failure.
Ultimate / Failure Test
The test may continue toward a defined failure condition according to the applicable test method.
This distinction can affect equipment selection, site preparation and safety controls.
Common Mistake: Asking Only for “20 Ton”
Customers sometimes request:
“Give me one 20-ton pull-out tester.”
A better enquiry is:
“We test M16 chemical anchors. Maximum required test load is 135kN.”
This gives the supplier useful engineering information for equipment selection.
What Information Should You Send MTM Precision?
For faster model selection, send:
1. Anchor Size
Example: M16.
2. Anchor Type
Example: chemical anchor with threaded rod.
3. Required Test Load
Example: 120kN.
4. Exposed Thread Length
Provide dimensions if possible.
5. Application
Example: façade bracket.
6. Photograph
Especially useful for unusual installations.
With this information, equipment selection becomes much easier.
Langry APT200 Key Specifications
For suitable M12, M16, M20 and other supported anchor configurations, the APT200 provides:
SpecificationLangry APT200Measurement Range0–200kNApproximate Capacity20 TonCylinder Centre Hole35mmCylinder Stroke70mmCommon AnchorageΦ6–Φ25Pull RodM24ConverterM6–M22Data Storage500 RecordsAccuracy ClassificationEN ISO 7500-1 Class 1
Actual suitability should be confirmed for each application.
Who Typically Needs This Equipment?
Potential users include:
Anchor installation contractors
Façade contractors
Structural steel contractors
Main contractors
QA/QC teams
M&E contractors
Inspection companies
Testing laboratories
Companies working across many anchor sizes may benefit from equipment that supports multiple adapter configurations.
Frequently Asked Questions
Can Langry APT200 test M12 chemical anchors?
Potentially yes, for suitable configurations within the equipment's range. Confirm the required test load, thread engagement and test setup.
Can APT200 test M16 anchors?
M16 can fall within supported converter configurations, but the actual test load and connection must still be confirmed.
Can APT200 test M20 anchors?
Potentially yes for suitable configurations within the 200kN range. Confirm the complete test setup before testing.
Does M20 automatically require a 20-ton tester?
No. Anchor size alone does not determine tester capacity.
Does M16 automatically require 100kN?
No. The required load comes from the project requirements.
What happens if my required load is 220kN?
A 200kN tester does not provide sufficient range. A higher-capacity model should be considered.
What if I do not know the required load?
Obtain it from the appropriate project engineer, consultant or approved project documentation before selecting equipment.
Should I send a photo before buying?
For unusual installations, yes. A photograph together with dimensions can help identify connection and clearance issues.
Where can I buy M12, M16 and M20 chemical anchor pull-out testing equipment in Malaysia?
Contact MTM Precision Sdn. Bhd. for Langry APT-series model selection and quotation in Malaysia.
M12, M16 & M20 Chemical Anchor Pull-Out Tester Supplier Malaysia
MTM Precision supplies professional construction and civil engineering testing equipment for anchor testing applications throughout Malaysia.
Instead of sending only:
“Need pull-out tester price.”
send us:
Anchor Size + Anchor Type + Required Test Load + Application + Photo
For example:
M16 Chemical Anchor + 120kN + Curtain Wall Bracket + Site Photo
This allows us to recommend the appropriate Langry capacity and configuration more accurately.
Contact MTM Precision
MTM Precision Sdn. Bhd.
Showroom & Service Centre
No. 29-1 & 29-2, Jalan Bandar 18,
Pusat Bandar Puchong,
47160 Puchong, Selangor, Malaysia
🌐 Website: www.mtmpre.com.my
📧 Email: mtmpre@yahoo.com
📱 WhatsApp: +6016-660 7346
For M12, M16 & M20 Chemical Anchor Pull-Out Tester Malaysia, Langry APT100, APT200 and APT300 model selection, current quotation and professional construction testing equipment enquiries, contact MTM Precision.
12 Aug 2026